| 2018-06-14 17:22:18 | 1ST REVIEW FBC-2014 MECHANICAL |
| | REVISION #18060593 |
| | MASTER #17101112 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014 |
| | FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION |
| | 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC FIFTH |
| | EDITION 2014 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN |
| | FOR THE ERV AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTION 514.1 FBC M. |
| | |
| | 2) M-1: THE AIR BALANCE CALCULATION DOES NOT INCLUDE |
| | THE REQUIRED 488.4 CFMS OF EXHAUST FROM THE THE BEAUTY |
| | SALON. THE REQUIREMENT FOR THE ERV IS BASED ON THAT |
| | AMOUNT OF EXHAUST AIR WHICH IS 94% OF THE 517.68 CFMS |
| | OUTSIDE AIR BEING SUPPLIED FOR THE OCCUPANTS- SEE TABLE |
| | C403.2.6 FBC EC. THE TYPICAL INSTALLATION UNDER THESE |
| | CIRCUMSTANCES IS TO DUCT THE EXHAUST AIR INTO THE ERV |
| | SO THAT THE AIR CAN BE EXHAUSTED, BUT THE ENERGY CAN BE |
| | CAPTURED ON THE HEAT WHEEL TO MIX WITH THE INCOMING |
| | OUTSIDE AIR. THE CURRENT PLAN SHOWING THE EXHAUST FROM |
| | THE SALON DIRECTLY DISCHARGED TO THE OUTDOORS IS NOT IN |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| | |