Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2018-07-02 Time 11:09 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-28 Cont ID  
Sent By rmcdouga Date 2018-06-28 Time 18:14 Rev Time 0.00
Received By rmcdouga Date 2018-06-28 Time 18:02 Sent To I
Notes
2018-06-28 18:22:48PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By rmcdouga Date 2018-06-13 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2018-06-13 Time 11:03 Sent To  
Notes
2018-06-13 11:25:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ROOF COVERING ASSEMBLY THAT IS SELECTED ON PAGE
 33 OF NOA NO. 17-1004.09 IS DIFFERENT FROM THE ONE THAT
 IS LISTED ON THE CONTRACT THAT WAS SUBMITTED. PLEASE
 CLARIFY. FBC 107.2.1
  
 2) THE ASSEMBLY THAT MATCHES THE CONTRACT ON PAGE 10
 AND 11 OF THE NOA, HAS A DESIGN PRESSURE OF -52.5 PSF.
 WHICH IS NOT ADEQUATE FOR A FLAT ROOF ON A STRUCTURE
 WITH A 15' MEAN ROOF HEIGHT IN EXPOSURE C WITH A 170
 MPH VULT WIND SPEED. IF THIS ASSEMBLY IS TO BE USED,
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING WILL BE REQUIRED. SEE LIMITATION #7 ON PAGE
 34 OF THE NOA. FBC-R905.11.3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By rmcdouga Date 2018-06-28 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2018-06-27 Time 13:12 Sent To  
Notes
2018-06-28 13:12:25RESUB ROUTED TO RMCDOUGAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2018-07-02 Time 11:09 Sent To  
Notes
2018-07-02 11:10:47DOCUMENTS WITH ENGINEER'S ELECTRONIC STAMP AND
 SIGNATURE WAS EMAILED AND HAS BEEN VERIFIED AND SENT TO
 SCANNING.