Plan Review Details - Permit 18060588
Plan Review Stops For Permit 18060588
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-30 Cont ID  
Sent By jwitmer Date 2018-06-30 Time 17:01 Rev Time 0.00
Received By shill Date 2018-06-30 Time 17:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-10 Cont ID  
Sent By jpearson Date 2018-07-10 Time 09:22 Rev Time 0.00
Received By jpearson Date 2018-07-10 Time 08:14 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-15 Cont ID  
Sent By pleduc Date 2018-06-15 Time   Rev Time 0.00
Received By pleduc Date 2018-06-15 Time 13:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 14:57 Sent To  
Notes
2018-08-01 14:57:25RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-13 Time 12:49 Sent To  
Notes
2018-06-14 12:49:30B28

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-25 Cont ID  
Sent By ccole Date 2018-06-25 Time 11:38 Rev Time 0.00
Received By ccole Date 2018-06-25 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2018-08-02 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By gjohnson Date 2018-07-05 Time 16:31 Rev Time 0.00
Received By gjohnson Date 2018-07-05 Time 16:31 Sent To  
Notes
2018-07-05 16:43:571ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR SUMP PUMP. PER WPB AMEND TO FBC 107.2.1
 ADDITIONAL INFORMATION REQUIRED.
  
 2. PER MANUFACTURE AIR ADMITTANCE VALVES ARE NOT
 ALLOWED FOR INSTALLATION ON LIBERTY PUMP #405.
  
 3. A BACKFLOW IS REQUIRED ON THE REFRIGERATOR ICE
 MACHINE. PER FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  