Plan Review Details - Permit 18060580
Plan Review Stops For Permit 18060580
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 16:05 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:30 Sent To  
Notes
2019-06-11 16:07:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW BY THIS PLANS EXAMINER
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING: (SEE ITEM K ) 3RD
 REQUEST - CORRECTED
  
 K. FINISHED FLOOR ELEVATION - (R403.1.7.3 FOUNDATION
 ELEVATION.CORRECTED - FINISH FLOOR ELEVATION HAS BEEN
 ESTABLISHED AT 12.0 FEET.
  
 2. PROVIDE SITE DRAINAGE PLAN - CORRECTED
 FBC R401.3 SITE DRAINAGE
  
 3. VALUE - (ADJUSTED TO $551,070.00) (CORRECTED)
  
 NOTE: APPLICANT MAY PETITION ROBERT BROWN, B.O. FOR
 ADJUSTMENT TO VALUE.
  
 4. PROVIDE ENERGY SUBMITTAL - CORRECTED (U-FACTORS FOR
 GLAZING TO BE VERIFIED IN FIELD)
 (BUILDER TO SIGN EPL CARD, OWNER/AGENT TO SIGN ENERGY
 SUBMITTAL)
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. - NOT ADDRESSED -
 4TH REQUEST (DESIGN PRESSURES MAY BE PLACED ON PLANS
 NEXT TO EACH OPENING IN LIEU OF WINDOW AND DOOR
 SCHEDULE)
  
 R301.2.1 WIND DESIGN CRITERIA. (PROVIDE DESIGN
 PRESSURES FOR EACH OPENING)
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. -
 NOT ADDRESSED - 4TH REQUEST (SEE OPTION BELOW)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 (107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.)
  
  
 7. OK
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY
 INSPECTOR) TO VERIFY BOLT INSTALLATION.
 (SEE THRESHOLD REVIEW COMMENTS) 4TH REQUEST
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. (
 REMOVED FROM PLAN )
  
 NEW COMMENTS
  
 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL
 BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND
 SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED. (SEE
 SIGNATURE REVIEW COMMENTS)
  
 11. PROVIDE FOUNDATION PLAN. CORRECTED
  
 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES.
 CORRECTED
  
 13. REFERENCE PLAN PAGE A-1. CORRECT GOVERNING CODE TO
 6TH ED 2017. CORRECTED
  
 14. SPECIFY WHAT TYPE OF INSULATION WILL BE INSTALLED
 TO OBTAIN REQUIRED R VALUE.
  
 15. IN THE SUPPORTING DOCUMENTS THERE ARE SEVERAL
 DUPLICATE PLAN PAGES. PLEASE REMOVE ANY DUPLICATE PAGES
 IN PROJECT DOX.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 EXPIDITED PLAN REVIEW FEES WILL BE ASSESSED.
  
 ADDITIONAL FEES MAY APPLY AS FOLLOWS:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 08:59 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 12:42 Sent To  
Notes
2019-05-08 09:47:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW BY THIS PLANS EXAMINER
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING: (SEE ITEM K ) 3RD
 REQUEST
  
 K. FINISHED FLOOR ELEVATION - (R403.1.7.3 FOUNDATION
 ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE).
  
 2. PROVIDE SITE DRAINAGE PLAN - CORRECTED
 FBC R401.3 SITE DRAINAGE
  
 3. VALUE - (ADJUSTED TO $551,070.00) (CORRECTED)
  
 NOTE: APPLICANT MAY PETITION ROBERT BROWN, B.O. FOR
 ADJUSTMENT TO VALUE.
  
 4. PROVIDE ENERGY SUBMITTAL - (U-FACTORS FOR GLAZING TO
 BE VERIFIED IN FIELD)
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. - NOT ADDRESSED -
 3RD REQUEST (DESIGN PRESSURES MAY BE PLACED ON PLANS
 NEXT TO EACH OPENING IN LIEU OF WINDOW AND DOOR
 SCHEDULE)
  
 R301.2.1 WIND DESIGN CRITERIA. (PROVIDE DESIGN
 PRESSURES FOR EACH OPENING)
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. -
 NOT ADDRESSED - 3RD REQUEST (SEE OPTION BELOW)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 (107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.)
  
  
 7. OK
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY
 INSPECTOR) TO VERIFY BOLT INSTALLATION.
 (SEE THRESHOLD REVIEW COMMENTS) 3RD REQUEST
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. (
 REMOVED FROM PLAN )
  
 NEW COMMENTS
  
 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL
 BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND
 SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED. (SEE
 SIGNATURE REVIEW COMMENTS)
  
 11. PROVIDE FOUNDATION PLAN. CORRECTED
  
 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES.
 CORRECTED
  
 13. REFERENCE PLAN PAGE A-1. CORRECT GOVERNING CODE TO
 6TH ED 2017. CORRECTED
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 EXPIDITED PLAN REVIEW FEES WILL BE ASSESSED.
  
 ADDITIONAL FEES MAY APPLY AS FOLLOWS:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 09:49 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:22 Sent To  
Notes
2019-04-23 09:52:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW BY THIS PLANS EXAMINER
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING: SEE K BELOW
 A. CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 B. ORIENTATION OF BUILDING TO NORTH.
 C. EXPOSURE
 D. RISK
 E. DESIGN WIND LOADS
 F. TYPE OF CONSTRUCTION
 G. NUMBER OF FLOORS/BEDROOMS/BATHROOMS
 H. SQUARE FOOTAGE - 1. CONDITIONED SPACE
 2. UNCONDITIONED SPACE
 3. TOTAL SQUARE FOOTAGE
 I. SPRINKLER SYSTEM
 J. SPECIAL FLOOD HAZARD AREA
  
 K. FINISHED FLOOR ELEVATION - (R403.1.7.3 FOUNDATION
 ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE).
  
 L. DESIGN LIVE LOADS AND DESIGN DEAD LOADS.
 M. DESIGN TEAM -
 1. ARCHITECT OF RECORD
 2. ENGINEER OF RECORD
 3. SPECIALTY ENGINEER
  
 2. PROVIDE SITE DRAINAGE PLAN - CORRECTED
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 3. VALUE - (ADJUSTED TO $551,070.00) SEE NOTE BELOW
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 BASED ON THE CURRENT ICC BUILDING VALUATION DATA
 PUBLISHED AUGUST 2018 THE VALUE OF THIS STRUCTURE HAS
 BEEN DETERMINED TO BE ($551,070.00).
  
 NOTE: APPLICANT MAY PETITION ROBERT BROWN, B.O. FOR
 ADJUSTMENT TO VALUE.
  
 4. PROVIDE ENERGY SUBMITTAL - (ENERGY SUBMITTAL CANNOT
 BE REVIEWED AT THIS TIME. SUBMIT MECHABICAL SYSTEM TO
 BE INSTALLED TO PROVIDE HEATING AND COOLING WITH
 EQUIPMENT SIZING CALCULATIONS. U-VALUES OF FENESTRATION
 CANNOT BE DETERMINED AT THIS TIME DUE TO NO WINDOW
 PRODUCT APPROVALS
 SUBMITTED FOR REVIEW. R405.4.3ADDITIONAL DOCUMENTATION.
 THE CODE OFFICIAL SHALL BE PERMITTED TO REQUIRE THE
 FOLLOWING DOCUMENTS:
 1. 1.VERIFICATION THAT AN EPL DISPLAY CARD SIGNED BY
 THE BUILDER PROVIDING THE BUILDING COMPONENT
 CHARACTERISTICS OF THE PROPOSED DESIGN WILL BE PROVIDED
 TO THE PURCHASER OF THE HOME AT TIME OF TITLE TRANSFER.
 2. 2.DOCUMENTATION OF THE COMPONENT EFFICIENCIES USED
 IN THE SOFTWARE CALCULATIONS FOR THE PROPOSED DESIGN.)
  
  
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE LOCATION
 OF DEVICES ON PLAN. PROVIDE DESIGN PRESSURE FOR EACH
 OPENING. - NOT ADDRESSED
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. -
 NOT ADDRESSED
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 7. OK
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY
 INSPECTOR) TO VERIFY BOLT INSTALLATION.
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. PROVIDE
 FOUNDATION DETAIL AND ATTACHMENT DETAIL TO STRUCTURE. -
 REMOVED FROM PLAN
  
 NEW COMMENTS
  
 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL
 BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND
 SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED. NO OTHER
 SIGNATURE OR SEAL CAN BE VALIDAITED.
  
 11. PROVIDE FOUNDATION PLAN. CORRECTED
  
 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES.
 CORRECTED
  
 13. REFERENCE PLAN PAGE A-1. CORRECT GOVERNING CODE TO
 6TH ED 2017.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 EXPIDITED PLAN REVIEW - DUE TO OUR CURRENT WORK LOAD,
 REVIEWS WERE NOT EXPIDITED AND NO EXPIDITED FEE WILL BE
 APPLIED TO THIS SUBMITTAL. SHOULD APPLICANT WISH TO
 HAVE FUTURE REVIEWS EXPIDITED PLEASE FILL OUT A NEW
 EXPIDITED PLAN REVIEW REQUEST FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 11:57 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 08:52 Sent To  
Notes
2019-03-27 12:07:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING: NOT ADDRESSED
 A. CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 B. ORIENTATION OF BUILDING TO NORTH.
 C. EXPOSURE
 D. RISK
 E. DESIGN WIND LOADS
 F. TYPE OF CONSTRUCTION
 G. NUMBER OF FLOORS/BEDROOMS/BATHROOMS
 H. SQUARE FOOTAGE - 1. CONDITIONED SPACE
 2. UNCONDITIONED SPACE
 3. TOTAL SQUARE FOOTAGE
 I. SPRINKLER SYSTEM
 J. SPECIAL FLOOD HAZARD AREA
 K. FINISHED FLOOR ELEVATION
 L. DESIGN LIVE LOADS AND DESIGN DEAD LOADS.
 M. DESIGN TEAM -
 1. ARCHITECT OF RECORD
 2. ENGINEER OF RECORD
 3. SPECIALTY ENGINEER
  
 2. PROVIDE SITE DRAINAGE PLAN - NOT ADDRESSED
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 3. VALUE - (ADJUSTED TO $551,070.00)
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 BASED ON THE CURRENT ICC BUILDING VALUATION DATA
 PUBLISHED AUGUST 2018 THE VALUE OF THIS STRUCTURE HAS
 BEEN DETERMINED TO BE ($551,070.00).
  
 4. PROVIDE ENERGY SUBMITTAL - NOT ADDRESSED
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE LOCATION
 OF DEVICES ON PLAN. PROVIDE DESIGN PRESSURE FOR EACH
 OPENING. - NOT ADDRESSED
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. -
 NOT ADDRESSED
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 7. OK
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY
 INSPECTOR) TO VERIFY BOLT INSTALLATION.
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. PROVIDE
 FOUNDATION DETAIL AND ATTACHMENT DETAIL TO STRUCTURE. -
 NOT ADDRESSED
  
 NEW COMMENTS
  
 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL
 BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND
 SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED.
  
 11. PROVIDE FOUNDATION PLAN.
  
 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 13:07 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 08:40 Sent To  
Notes
2019-02-06 13:51:14BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING:
 A. CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 B. ORIENTATION OF BUILDING TO NORTH.
 C. EXPOSURE
 D. RISK
 E. DESIGN WIND LOADS
 F. TYPE OF CONSTRUCTION
 G. NUMBER OF FLOORS/BEDROOMS/BATHROOMS
 H. SQUARE FOOTAGE - 1. CONDITIONED SPACE
 2. UNCONDITIONED SPACE
 3. TOTAL SQUARE FOOTAGE
 I. SPRINKLER SYSTEM
 J. SPECIAL FLOOD HAZARD AREA
 K. FINISHED FLOOR ELEVATION
 L. DESIGN LIVE LOADS AND DESIGN DEAD LOADS.
 M. DESIGN TEAM -
 1. ARCHITECT OF RECORD
 2. ENGINEER OF RECORD
 3. SPECIALTY ENGINEER
  
 2. PROVIDE SITE DRAINAGE PLAN -
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 3. VALUE -
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 BASED ON THE CURRENT ICC BUILDING VALUATION DATA
 PUBLISHED AUGUST 2018 THE VALUE OF THIS STRUCTURE HAS
 BEEN DETERMINED TO BE $543,375.00.
  
 4. PROVIDE ENERGY SUBMITTAL -
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE LOCATION
 OF DEVICES ON PLAN. PROVIDE DESIGN PRESSURE FOR EACH
 OPENING.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 7. REFERENCE PLAN PAGE A-1. PROVIDE DETAIL FOR FOOTINGS
 F-1 AND F-2. PLEASE CLARIFY WHAT F002 REFERS TO.
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A SPECIAL INSPECTOR TO
 VERIFY BOLT INSTALLATION.
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. PROVIDE
 FOUNDATION DETAIL AND ATTACHMENT DETAIL TO STRUCTURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-05 Cont ID  
Sent By shill Date 2018-09-06 Time 08:58 Rev Time 0.00
Received By shill Date 2018-09-06 Time 10:35 Sent To  
Notes
2019-02-05 09:06:55PLAN WAS PULLED FROM REVIEW. SPOKE WITH ENGINEER; PLANS
 ARE SEVERELY DEFICIENT AND HE WAS NOT FAMILIAR WITH THE
 PROJECT TO PROVIDE CLARIFICATION, SO PULLED FROM
 REVIEW.
  
  
2018-09-06 10:44:43***PLAN REVIEW IN PROGESS***
  
 ***CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE HAVE THE ENGINEER CONTACT ME. I HAVE LEFT A
 MESSAGE FOR HIM ON THE NUMBER I FOUND ON THE INTERNET.
 ANOTHER NUMBER I HAVE FOR HIM (845-496-6610) IS
 DISCONNECTED.
  
 WITHOUT BASIC INFORMATION, AN ACCURATE PLAN REVIEW
 CANNOT BE DONE. PLANS STATE "REVIEWED BY" SO IT IS NOT
 CLEAR IS IT IS DESIGNED BY THE ENGINEER. PLAN STATES IT
 IS 3 STORIES, BUT IT IS 4 STORIES.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By shill Date 2018-06-14 Time 17:33 Rev Time 0.00
Received By shill Date 2018-06-14 Time 17:33 Sent To  
Notes
2018-06-14 17:33:28***CORRECTIONS****
 REVISED 6/28/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE VALUE ON THE APPLICATION IS TOO LOW; FBC 109,
 VALUE HAS BEEN ADJUSTED (ESTIMATED) PER ICC TABLES.
  
 2. PLAN REVIEW FEE WAS NOT PAID AT TIME OF SUBMITTAL,
 BUT WAS SUBSEQUENTLY PAID.
  
 3. FBC 107, THE PLAN SUBMITTED IS DEFICIENT, SO WE ARE
 UNABLE TO DO A PLAN REVIEW AT THIS TIME. FOR INSTANCE:
 SOME AREAS DO NOT INCLUDE ROOM DESIGNATIONS - FOR
 EXAMPLE, DRAWING 9 HAS AREAS WITH NO ROOM DESIGNATIONS
 NO FOUNDATION DETAIL
 MAIN ENTRY DOOR NOT CLEAR
 CANNOT DETERMINE MEANS OF EGRESS FROM FLOOR TO FLOOR;
 NOT CLEAR IF STAIR IS THE ONLY ACCESS, STAIR APPEARS TO
 BE LOCATED IN THE PORCH RATHER THAN INSIDE OF THE UNIT
 FIRST FLOOR MAIN ENTRY DOOR APPEARS TO ENTER INTO A
 BEDROOM
 NO FIRE RESISTANT RATED WALLS OR FLOORS SHOWN
 SHAFTS, EXITS NOT SHOWN
  
 FOR INFORMATION REQUIRED FOR PLAN REVIEW, SEE CITY OF
 WEST PALM BEACH MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS, FBC 107.3.5, AS APPLICABLE. FOR YOUR
 CONVENIENCE, THAT CODE SECTION IS PROVIDED FOR YOU AT
 THE END OF THIS REVIEW.
  
 4. NA.
  
 5. APPLICANT HAS COMPLETED THE OWNER BUILDER AFFIDAVIT.
 CONFIRM THAT THE TWO UNITS PROPOSED WILL NOT BE SOLD,
 RENTED, LEASED, OR ADVERTISED FOR SALE, RENT, OR LEASE
 FOR AT LEAST A YEAR AFTER COMPLETION.
  
 * * * * * * * * * * * * * * *
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1:
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE SECTION 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE
 RESISTANCE
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 SMOKE CONTROL
 STAIR PRESSURIZATION
 SYSTEMS SCHEMATIC
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 THRESHOLD INSPECTION PLAN
 STAIR SYSTEMS
 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 FAIR HOUSING REQUIREMENTS
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 12. SPECIAL SYSTEMS:
 ELEVATORS
 ESCALATORS
 LIFTS
 13. LOCATION AND INSTALLATION DETAILS. THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EACH
 FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER
 107.3.5.1.2 ELECTRICAL
 1. ELECTRICAL:
 WIRING
 SERVICES
 FEEDERS AND BRANCH CIRCUITS
 OVERCURRENT PROTECTION
 GROUNDING
 WIRING METHODS AND MATERIALS
 GFCLS
 2. EQUIPMENT
 3. SPECIAL OCCUPANCIES
 4. EMERGENCY SYSTEMS
 5. COMMUNICATION SYSTEMS
 6. LOW VOLTAGE
 7. LOAD CALCULATIONS
 8. DESIGN FLOOD ELEVATION
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. ROOF DRAINAGE
 8. BACK FLOW PREVENTION
 9. IRRIGATION
 10. LOCATION OF WATER SUPPLY LINE
 11. GREASE TRAPS
 12. ENVIRONMENTAL REQUIREMENTS
 13. PLUMBING RISER
 14. DESIGN FLOOD ELEVATION
 107.3.5.1.4 MECHANICAL
 1 . ENERGY CALCULATIONS
 2 . EXHAUST SYSTEMS:
 CLOTHES DRYER EXHAUST
 KITCHEN EQUIPMENT EXHAUST
 SPECIALTY EXHAUST SYSTEMS
 3. EQUIPMENT
 4. EQUIPMENT LOCATION
 5. MAKE-UP AIR
 6. ROOF-MOUNTED EQUIPMENT
 7. DUCT SYSTEMS
 8. VENTILATION
 9. COMBUSTION AIR
 10. CHIMNEYS, FIREPLACES AND VENTS
 11. APPLIANCES
 12. BOILERS
 13. REFRIGERATION
 14. BATHROOM VENTILATION
 15. LABORATORY
 16. DESIGN FLOOD ELEVATION
 107.3.5.1.5 GAS
 1. GAS PIPING
 2. VENTING
 3. COMBUSTION AIR
 4. CHIMNEYS AND VENTS
 5. APPLIANCES
 6. TYPE OF GAS
 7. FIREPLACES
 8. LP TANK LOCATION
 9. RISER DIAGRAM/SHUTOFFS
 10. DESIGN FLOOD ELEVATION
 107.3.5.1.6 ENERGY CALCULATIONS
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2019-06-13 Cont ID  
Sent By jpearson Date 2019-06-13 Time 11:20 Rev Time 0.00
Received By jpearson Date 2019-06-13 Time 09:21 Sent To  
Notes
2019-06-13 09:30:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 6TH REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM PROVIDED BUT NEEDS CORRECTIONS. SEE
 NEW COMMENTS.
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (6TH REVIEW: LOAD
 CALCULATION IS NOT ACCURATE, SEE PREVIOUS COMMENTS.)
 3. PANEL SCHEDULES PROVIDED BUT NOT CORRECT. SEE
 COMMENTS BELOW.
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 (6TH REVIEW: NOT PROVIDED.)
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3 (6TH REVIEW, AIC
 RATING OF ELECRTICAL EQUIPMENT STILL NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (6TH
 REVIEW: NOT PROVIDED.)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (6TH
 REVIEW: NOT PROVIDED.)
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 (6TH REVIEW: NOT PROVIDED.)
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2 (6TH REVIEW: NOT PROVIDED. IN ADDITION, THE
 20 AMP SMALL APPLIANCE CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. NEC 210.52(B)(2))
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (5TH REVIEW: NOT
 CORRECTED.)
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8 (6TH REVIEW: NOT TO CODE.)
 15. CORRECTED.
 16. CORRECTED.
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1 (6TH REVIEW: NOT PROVIDED COMPLETELY. WHERE
 IS THE METER CAN LOCATED? SHOW ON PLAN.)
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. LOAD CALCULATION DOES NOT MATCH THE METHOD IN FBC
 RESIDENTIAL OR THE NEC, WHICHEVER WOULD APPLY DEPENDING
 ON SERVICE TYPE. PROVIDE A RESIDENTIAL LOAD CALCULATION
 THAT INCLUDES ALL LOADS AND DEMAND FACTORS AS
 PERMITTED. PROVIDE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS TO MATCH THE TYPE OF SERVICE. NEC 220; FBC RE
 E3602.2 (6TH REVIEW, NOT PROVIDED ACCURATELY.)
 24. CORRECTED.
 25. CORRECTED.
 26. CORRECTED.
 27. PANEL SCHEDULES SHOW 10 GAUGE WIRE ON A 32 AMP
 BREAKER IN SEVERAL LOCATIONS. THIS IS NOT A STANDARD
 BREAKER SIZE, AND THE WIRE SIZE IS NOT PERMITTED TO BE
 USED ON A BREAKER OVER 30 AMPS. PROVIDE CORRECTION. NEC
 240.4(D), 240.6, 310.15(B)(16) (NOT CORRECTED.)
 28. NEW PLAN SHEETS SUBMITTED HAVE THE SAME NAME:
 EL-100.01. PLAN SHEETS NEED TO HAVE DISTINCT NAMES.
 PROVIDE CORRECTION. WPB FBC 107.2.1 (NOT CORRECTED.)
 29. PROVIDE SPEC SHEET FOR 32 AMP BREAKER AS THIS IS
 NOT A STANDARD SIZE BREAKER. NEC 240.6 (NOT PROVIDED.)
 30. PROVIDE SPEC SHEET FOR 160 AMP BREAKER AS THIS IS
 NOT A STANDARD SIZE BREAKER. NEC 240.6 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2019-05-31 Cont ID  
Sent By jpearson Date 2019-05-31 Time 07:43 Rev Time 0.00
Received By jpearson Date 2019-05-31 Time 07:42 Sent To  
Notes
2019-05-31 07:38:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM PROVIDED BUT NEEDS CORRECTIONS. SEE
 NEW COMMENTS.
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (5TH REVIEW: LOAD
 CALCULATION IS NOT ACCURATE, SEE NEW COMMENTS.)
 3. PANEL SCHEDULES PROVIDED BUT NOT CORRECT. SEE NEW
 COMMENTS BELOW.
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 (5TH REVIEW: NOT PROVIDED.)
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3 (5TH REVIEW, AIC
 RATING OF ELECRTICAL EQUIPMENT STILL NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (5TH
 REVIEW: NOT PROVIDED.)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (5TH
 REVIEW: NOT PROVIDED.)
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 (5TH REVIEW: NOT PROVIDED.)
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2 (5TH REVIEW: NOT PROVIDED. IN ADDITION, THE
 20 AMP SMALL APPLIANCE CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. NEC 210.52(B)(2))
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (5TH REVIEW: NOT
 CORRECTED.)
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8 (5TH REVIEW: NOT TO CODE.)
 15. CORRECTED.
 16. CORRECTED.
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1 (5TH REVIEW: NOT PROVIDED COMPLETELY. WHERE
 IS THE METER CAN LOCATED? SHOW ON PLAN.)
 18. FOUR TIMES PLAN REVIEW FEE ADDED.
  
 NEW COMMENTS:
  
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. LOAD CALCULATION DOES NOT MATCH THE METHOD IN FBC
 RESIDENTIAL OR THE NEC, WHICHEVER WOULD APPLY DEPENDING
 ON SERVICE TYPE. PROVIDE A RESIDENTIAL LOAD CALCULATION
 THAT INCLUDES ALL LOADS AND DEMAND FACTORS AS
 PERMITTED. PROVIDE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS TO MATCH THE TYPE OF SERVICE. NEC 220; FBC RE
 E3602.2 (5TH REVIEW, NOT PROVIDED ACCURATELY.)
 24. CORRECTED.
 25. CORRECTED.
 26. CORRECTED.
 27. PANEL SCHEDULES SHOW 10 GAUGE WIRE ON A 32 AMP
 BREAKER IN SEVERAL LOCATIONS. THIS IS NOT A STANDARD
 BREAKER SIZE, AND THE WIRE SIZE IS NOT PERMITTED TO BE
 USED ON A BREAKER OVER 30 AMPS. PROVIDE CORRECTION. NEC
 240.4(D), 240.6, 310.15(B)(16) (NOT CORRECTED.)
 28. NEW PLAN SHEETS SUBMITTED HAVE THE SAME NAME:
 EL-100.01. PLAN SHEETS NEED TO HAVE DISTINCT NAMES.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 29. PROVIDE SPEC SHEET FOR 32 AMP BREAKER AS THIS IS
 NOT A STANDARD SIZE BREAKER. NEC 240.6
 30. PROVIDE SPEC SHEET FOR 160 AMP BREAKER AS THIS IS
 NOT A STANDARD SIZE BREAKER. NEC 240.6
  
 END OF COMMENTS.
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 07:05 Rev Time 0.00
Received By jpearson Date 2019-05-06 Time 07:55 Sent To  
Notes
2019-05-07 07:05:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM PROVIDED BUT NEEDS CORRECTIONS. SEE
 NEW COMMENTS.
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (4TH REVIEW: LOAD
 CALCULATION IS NOT ACCURATE, SEE NEW COMMENTS.)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (4TH
 REVIEW: PANEL SCHEDULE FOR LPP-FF NOT PROVIDED. OTHER
 PANEL SCHEDULES NEED CORRECTION, SEE NEW COMMENTS.)
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 (4TH REVIEW: NOT PROVIDED.)
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3 (NOT PROVIDED.)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (4TH REVIEW: NOT PROVIDED.)
 7. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (4TH REVIEW: NOT PROVIDED.)
 8. CORRECTED.
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (4TH
 REVIEW: NOT PROVIDED.)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (4TH
 REVIEW: NOT PROVIDED.)
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 (4TH REVIEW: NOT PROVIDED.)
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2 (4TH REVIEW: NOT PROVIDED. IN ADDITION, THE
 20 AMP SMALL APPLIANCE CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. NEC 210.52(B)(2))
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (4TH REVIEW: NOT
 CORRECTED.)
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8 (4TH REVIEW: NOT TO CODE.)
 15. CORRECTED.
 16. CORRECTED.
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1 (4TH REVIEW: NOT PROVIDED COMPLETELY. WHERE
 IS THE METER CAN LOCATED? SHOW ON PLAN.)
 18. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $8,816.04
  
 NEW COMMENTS:
  
 19. RISER DIAGRAM SHOWS THERE IS A 3 PHASE, 120/240
 VOLT SERVICE. THIS TYPE OF SERVICE WOULD HAVE A HIGH
 LEG AND SHOULD BE DESIGNED ACCORDINGLY. IF THIS IS
 ACCURATE, MANY LOCATIONS SHOW SINGLE PHASE LOADS ON THE
 HIGH LEG OF THE PANELS, WHICH IS A CODE VIOLATION. IF
 THERE IS A HIGH LEG SERVICE, PROVIDE DETAILS OF MARKING
 OF THE HIGH LEG PER CODE. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS AS NEEDED. NEC 110.3, 110.15; WPB FBC
 107.2.1
 20. IF THIS IS A THREE PHASE SERVICE, THE FBC
 RESIDENTIAL DOES NOT APPLY. PROVIDE CLARIFICATION. WPB
 FBC 107.2.1
 21. RISER DIAGRAM SHOWS WHAT APPEARS TO BE PANEL MDB
 HAVING CIRCUIT BREAKERS FEEDING LOADS. HOWEVER, THERE
 IS NOMENCLATURE AT EACH OF THE BREAKERS THAT INDICATE
 THESE ARE FUSED DISCONNECTS. WHICH IS IT? PROVIDE
 CLARIFICATION AND/OR CORRECTIONS AS NEEDED.
 22. RISER DIAGRAM SHOWS THE WIRE FROM FPL AS HAVING 4
 CONDUCTORS THE SAME SIZE, AND A CONDUCTOR MARKED ?E?.
 IT APPEARS THIS IS AN EQUIPMENT GROUNDING CONDUCTOR.
 THIS CONDUCTOR SHOULD NOT BE INCLUDED IN THE SERVICE
 DROP. IS THIS SERVICE UNDERGROUND OR OVERHEAD? PROVIDE
 CLARIFICATIONS AND/OR CORRECTIONS. NEC 250.6; WPB FBC
 107.2.1
 23. LOAD CALCULATION DOES NOT MATCH THE METHOD IN FBC
 RESIDENTIAL OR THE NEC, WHICHEVER WOULD APPLY DEPENDING
 ON SERVICE TYPE. PROVIDE A RESIDENTIAL LOAD CALCULATION
 THAT INCLUDES ALL LOADS AND DEMAND FACTORS AS
 PERMITTED. THE CURRENT NUMBERS SUPPLIED FOR VA ARE NOT
 EXPLAINED, AND THEN THESE NUMBERS ARE DIVIDED BY THE
 SINGLE PHASE VOLTAGE TO DETERMINE THE AMPERAGE
 REQUIREMENT. SEE NOTES 19 AND 20, IS THIS A 3 PHASE OR
 SINGLE PHASE SERVICE? PROVIDE ACCURATE LOAD CALCULATION
 INCLUDING ALL LOADS TO MATCH THE TYPE OF SERVICE. NEC
 220; FBC RE E3602.2
 24. PANEL MDB SHOWS 3/0 WIRE FEEDING PANEL LPP-GF, FED
 FROM A 250 AMP BREAKER. THIS WIRE IS NOT RATED FOR 250
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 25. PANEL MDB SHOWS 4/0 WIRE FEEDING PANEL LPP-FF, FED
 FROM A 300 AMP BREAKER. THIS WIRE IS NOT RATED FOR 300
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 26. PANEL LPP-GF SHOWS 14 GAUGE WIRE ON A 16 AMP
 BREAKER IN SEVERAL LOCATIONS. THIS IS NOT A STANDARD
 BREAKER SIZE, AND THE WIRE SIZE IS NOT PERMITTED TO BE
 USED ON A BREAKER OVER 15 AMPS. PROVIDE CORRECTION. NEC
 240.4(D), 240.6, 310.15(B)(16)
 27. PANEL LPP-GF SHOWS 10 GAUGE WIRE ON A 32 AMP
 BREAKER IN SEVERAL LOCATIONS. THIS IS NOT A STANDARD
 BREAKER SIZE, AND THE WIRE SIZE IS NOT PERMITTED TO BE
 USED ON A BREAKER OVER 30 AMPS. PROVIDE CORRECTION. NEC
 240.4(D), 240.6, 310.15(B)(16)
  
 END OF COMMENTS.
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 14:39 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 12:44 Sent To  
Notes
2019-04-05 13:15:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.)
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (NOT PROVIDED.)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT
 PROVIDED.)
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 (NOT PROVIDED.)
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3 (NOT PROVIDED.)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (NOT PROVIDED.)
 7. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOT PROVIDED.)
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (NOT
 PROVIDED.)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOT
 PROVIDED.)
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 (NOT PROVIDED.)
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2 (NOT PROVIDED.)
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (NOT PROVIDED.)
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8 (NOT PROVIDED.)
 15. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6 (NOT PROVIDED.)
 16. CORRECTED.
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1 (NOT PROVIDED.)
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
  
 NEW COMMENT:
  
 18. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $8,816.04
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-07 Cont ID  
Sent By jpearson Date 2019-03-07 Time 14:45 Rev Time 0.00
Received By jpearson Date 2019-03-07 Time 14:45 Sent To  
Notes
2019-03-07 14:45:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.)
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (NOT PROVIDED.)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT
 PROVIDED.)
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 (NOT PROVIDED.)
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3 (NOT PROVIDED.)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (NOT PROVIDED.)
 7. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOT PROVIDED.)
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (NOT
 PROVIDED.)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOT
 PROVIDED.)
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 (NOT PROVIDED.)
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2 (NOT PROVIDED.)
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (NOT PROVIDED.)
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8 (NOT PROVIDED.)
 15. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6 (NOT PROVIDED.)
 16. CORRECTED.
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1 (NOT PROVIDED.)
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 11:23 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 09:53 Sent To  
Notes
2019-02-05 11:02:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 7. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2
 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8
 15. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 16. PROVIDE LOCATION OF ALL ELECTRICAL PANELS ON PLAN
 TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1
 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1
  
 BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF
 INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT
 REVIEW, FURTHER COMMENTS ARE POSSIBLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2019-03-06 Cont ID  
Sent By scaldero Date 2019-03-06 Time 12:49 Rev Time 0.00
Received By scaldero Date 2019-03-06 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2019-02-01 Cont ID  
Sent By scaldero Date 2019-02-01 Time 13:26 Rev Time 0.00
Received By scaldero Date 2019-02-01 Time 13:20 Sent To  
Notes
2019-02-01 13:26:47PERMIT #18060580
 FIRE COMMENTS
  
 PER DISCUSSION WITH MS. TERRY MAUNEY, THE PROPERTY
 OWNER, A FIRE REVIEW IS NOT REQUIRED, AS THIS PERMIT IS
 FOR A STRUCTURE THAT IS TO BE USED SOLELY AS A SINGLE
 FAMILY HOME.
 MS. MAUNEY STATED AND CONFIRMED THAT THERE WILL BE NO
 SECONDARY USE TO THIS STRUCTURE THAT WOULD NEED TO BE
 REVIEWED UNDER THE FIRE CODE. THIS INCLUDES BUSINESS,
 RESIDENTIAL BOARD
 AND CARE, AND/OR ROOMING HOUSE OCCUPANCIES. MS. TAUNEY,
 STATED THAT THE ONLY USE OF THE PROPERTY WILL BE AS A
 PERMANENT RESIDENTIAL SINGLE FAMILY HOME.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 WPBFD
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-01-23 Cont ID  
Sent By scaldero Date 2019-01-23 Time 09:55 Rev Time 0.00
Received By scaldero Date 2019-01-23 Time 09:18 Sent To  
Notes
2019-01-23 09:54:45PERMIT # 18060580
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW - FAIL COMMENTS
  
 THIS SUBMISSION APPEARS TO BE MISSING SHEETS AND
 DETAILS THAT WERE IN THE ORIGINAL SUBMISSION. IT DOES
 NOT APPEAR THAT ANY OF THE COMMENTS HAVE BEEN
 ADDRESSED.
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3
 OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 3) SHEET CS1.0: PROVIDE CORRECT NUMBER OF STORIES.
  
 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 5) SHEET F2.01: PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By scaldero Date 2018-09-13 Time 15:15 Rev Time 0.00
Received By scaldero Date 2018-09-13 Time 14:49 Sent To  
Notes
2018-09-13 15:14:58PERMIT # 18060580
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3
 OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 3) SHEET CS1.0: PROVIDE CORRECT NUMBER OF STORIES.
  
 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 5) SHEET F2.01: PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2019-06-20 Cont ID  
Sent By shill Date 2019-06-20 Time 07:41 Rev Time 0.00
Received By shill Date 2019-06-03 Time 06:59 Sent To  
Notes
2019-06-20 07:42:18REMOVED ZONING STOP AND CLOSED REVIEW CYCLE AS
 APPLICANT WILL BE SUBMITTING A NEW PACKAGE WITH NEW
 DESIGN PROFESSIONAL UNDER A NEW PERMIT NUMBER
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-06-03 Cont ID  
Sent By cpuell Date 2019-06-03 Time 05:58 Rev Time 0.00
Received By cpuell Date 2019-05-29 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 10:11 Rev Time 0.00
Received By cthroop Date 2019-04-30 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 11:19 Rev Time 0.00
Received By cthroop Date 2019-04-03 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 13:23 Rev Time 0.00
Received By cthroop Date 2019-03-05 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-07 Cont ID  
Sent By cpuell Date 2019-02-07 Time 15:37 Rev Time 0.00
Received By cpuell Date 2019-01-18 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-18 Cont ID  
Sent By shill Date 2018-09-18 Time 14:49 Rev Time 0.00
Received By shill Date 2018-08-23 Time 16:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 16:48 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:31 Sent To  
Notes
2019-06-11 16:48:57PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 09:48 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 12:42 Sent To  
Notes
2019-05-08 09:49:05PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 07:19 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:22 Sent To  
Notes
2019-04-23 07:20:08PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 12:07 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 08:52 Sent To  
Notes
2019-03-27 12:08:32PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 11:10 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 13:35 Sent To  
Notes
2019-02-06 11:11:17PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2019-06-17 Cont ID  
Sent By cthroop Date 2019-06-17 Time 07:49 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:30 Sent To  
Notes
2019-06-17 07:51:46MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW BY THIS PLANS EXAMINER.
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. (ENERGY SUBMITTAL RECIEVED - (GLAZING U-FACTORS
 SHALL BE VERIFIED BY FIELD INSPECTOR) (EQUIPMENT SIZING
 TO BE VERIFIED UPON RECEIPT OF EQUIPMENT
 SPECIFICATIONS)
  
 2. PLAN PAGE A0.1 STATE INSULATION SHALL BE 2 LAYERS OF
 BATT. ENERGY SUBMITTAL STATES INSULATION SHALL BE BLOWN
 IN. PLEASE CLARIFY. NOT CORRECTED - 4TH REQUEST
  
 3. PROVIDE MECHANICAL PLAN. (NOT PROVIDED) DEMONSTRATE
 HOW SPACE SHALL BE CONDITIONED. PROVIDE MECHANICAL
 EQUIPMENT SPECIFICATIONS AND SIZING. - 4TH REQUEST
 FBC E R403.7.1EQUIPMENT SIZING.
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING.
 RE403.7HEATING AND COOLING EQUIPMENT (MANDATORY).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 10:00 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 12:43 Sent To  
Notes
2019-05-08 10:11:31MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW BY THIS PLANS EXAMINER.
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. (ENERGY SUBMITTAL RECIEVED - (GLAZING U-FACTORS
 SHALL BE VERIFIED BY FIELD INSPECTOR) (EQUIPMENT SIZING
 TO BE VERIFIED UPON RECEIPT OF EQUIPMENT
 SPECIFICATIONS)
  
 2. PLAN PAGE A0.1 STATE INSULATION SHALL BE 2 LAYERS OF
 BATT. ENERGY SUBMITTAL STATES INSULATION SHALL BE BLOWN
 IN. PLEASE CLARIFY. NOT CORRECTED - 3RD REQUEST
  
 3. PROVIDE MECHANICAL PLAN. (NOT PROVIDED) DEMONSTRATE
 HOW SPACE SHALL BE CONDITIONED. PROVIDE MECHANICAL
 EQUIPMENT SPECIFICATIONS AND SIZING.
 FBC E R403.7.1EQUIPMENT SIZING.
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING.
 RE403.7HEATING AND COOLING EQUIPMENT (MANDATORY).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 11:10 Rev Time 0.00
Received By cthroop Date 2019-04-23 Time 11:04 Sent To  
Notes
2019-04-23 11:17:25MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW BY THIS PLANS EXAMINER.
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. (ENERGY SUBMITTAL CANNOT BE REVIEWED AT THIS TIME.
 SUBMIT MECHABICAL SYSTEM TO BE INSTALLED TO PROVIDE
 HEATING AND COOLING WITH EQUIPMENT SIZING CALCULATIONS.
 U-VALUES OF FENESTRATION CANNOT BE DETERMINED AT THIS
 TIME DUE TO NO WINDOW PRODUCT APPROVALS
 SUBMITTED FOR REVIEW.
 R405.4.3ADDITIONAL DOCUMENTATION.
 THE CODE OFFICIAL SHALL BE PERMITTED TO REQUIRE THE
 FOLLOWING DOCUMENTS:
 1. 1.VERIFICATION THAT AN EPL DISPLAY CARD SIGNED BY
 THE BUILDER PROVIDING THE BUILDING COMPONENT
 CHARACTERISTICS OF THE PROPOSED DESIGN WILL BE PROVIDED
 TO THE PURCHASER OF THE HOME AT TIME OF TITLE TRANSFER.
 2. 2.DOCUMENTATION OF THE COMPONENT EFFICIENCIES USED
 IN THE SOFTWARE CALCULATIONS FOR THE PROPOSED DESIGN.)
  
 2. PLAN PAGE A0.1 STATE INSULATION SHALL BE 2 LAYERS OF
 BATT. ENERGY SUBMITTAL STATES INSULATION SHALL BE BLOWN
 IN. PLEASE CLARIFY.
  
 3. PROVIDE MECHANICAL PLAN. ENERGY SUBMITTAL AND MANUAL
 J SHOULD BE RE-EVALUATED AT TIME OF MECHANICAL PLAN
 SUBMITTAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-04-06 Cont ID  
Sent By cmontell Date 2019-04-06 Time 07:46 Rev Time 0.00
Received By cmontell Date 2019-04-06 Time 07:45 Sent To  
Notes
2019-04-06 07:46:17MECHANICAL PLAN REVIEW FAIL 3RD TIME NEED MECHANICAL
 PLAN
  
  
 CHRIS MONTELLO
 805-6733
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-16 Cont ID  
Sent By cmontell Date 2019-03-16 Time 05:47 Rev Time 0.00
Received By cmontell Date 2019-03-16 Time 05:39 Sent To  
Notes
2019-03-16 05:42:33MECHANICAL PLAN REVIEW FAIL
  
 NEED MECHANICAL PLANS
 NEED MANUAL J
 NEED ENERGY CALC
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cmontell Date 2019-02-05 Time 14:46 Rev Time 0.00
Received By cmontell Date 2019-02-05 Time 14:45 Sent To  
Notes
2019-02-05 14:46:05NEED MECHANICAL PLANS
 NEED MANUAL J
 NEED ENERGY CALC
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 6 Status F Date 2019-06-12 Cont ID  
Sent By gjohnson Date 2019-06-12 Time 11:24 Rev Time 0.00
Received By gjohnson Date 2019-06-12 Time 10:39 Sent To  
Notes
2019-06-12 12:35:38PLUMBING 6TH REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS COMMENTS NOT ADDRESSED:
  
 2) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-RES P2903.9.3 PLACE NOTE ON PLAN
  
 3) PROVIDE MANUFACTURE INSTALLATION MANUAL FOR THE
 WATER HEATERS BEING USED. PLACE NOT ON PLAN WATER
 HEATER SHALL COMPLY WITH FBC RES P2801.2, P2801.6,
 P2801.6.2, P2804.6.1 DETAIL SHOWN ON PLAN DOES NOT
 COMPLY WITH CODE PLEASE CORRECT OR REMOVE FROM PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 4) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK CLOSING
 VALVES. FBC-RES P2903.5
 REQUIRED ON HOT PIPING FOR DISHWASHER AND CLOTHES
 WASHING MACHINE SHOW ON WATER ISOMETRIC. ARRESTORS NOT
 SHOWN ON HOT PIPING PLEASE SHOW ARRESTOR ON HOT AND
 COLD PIPING FOR DISHWASHER AND CLOTHES WASHING MACHINE.
 PER FBC RES P2903.5
  
 5.) THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPARATE PERMIT. PER WPB UTILITIES DEPARTMENT.
 ON THE PLUMBING SITE LATOUT SHEET IT SHOWS A 2" WATER
 SERVICE PLACE NOTE ON THE PLAN RPZ BACKFLOW REQUIRED
 WITH SEPARATE PERMIT. PLACE NOTE ON PLAN RPZ SHALL BE
 INSTALLED NEXT TO METER AND SHALL HAVE SEPARATE PERMIT.
  
 NEW COMMENTS;
  
 1. THE VENTS FOR THE TOILETS AND THE TUBS ARE SHOWN AS
 HORIZONTAL DRY VENT WHICH ARE NOT ALLOWED PER FBC RES
 P3104.3, P3104.4 THE CORRECT WAY OF VENTING THE
 BATHROOM GROUP IS TO CONNECT THE BRANCH DRAIN OF THE
 LAVATORY TO THE BUILDING DRAIN BETWEEN THE TOILET AND
 TUB THE VENT ON THE LAVATORY WILL VENT THE BATHROOM
 GROUP MAKING IT A HORIZONTAL WET VENT SYSTEM. PER FBC
 RES P3108.4
  
 2. FIXTURES CAN NOT BE DOUBLE TRAPPED THE PLAN SHOWS
 THE LAVATORY AND TUB CONNECTING TO THE FLOOR DRAIN
 TRAPS TH IS NOT ALLOWED THE BRANCH DRAINS FROM THE
 LAVATORY AND TUB SHALL BE CONNECTED SEPARATELY TO THE
 BUILDING DRAIN. PER FBC RES P3201.6
  
 3. THE KITCHEN DRAIN SHALL NOT CONNECT TO THE BATHROOM
 GROUP IT SHALL CONNECT TO THE BUILDING DRAIN DOWN STEAM
 OF THE BATHROOM GROUP. PER FBC RES FBC RES P3108.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2019-05-02 Cont ID  
Sent By gjohnson Date 2019-05-02 Time 11:05 Rev Time 0.00
Received By gjohnson Date 2019-05-01 Time 17:00 Sent To  
Notes
2019-05-02 10:58:25PLUMBING 5TH REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS COMMENTS NOT ADDRESSED:
  
 1) WASHING MACHINES SHALL NOT DISCHARGE INTO THE
 HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S. FBC
 RES P3108.1
  
 2) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-P 604.10.3
  
 3) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS
 BEING USED. FBC 107.1
  
 4) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK CLOSING
 VALVES. FBC-RES P2903.5
 REQUIRED ON HOT PIPING FOR DISHWASHER AND CLOTHES
 WASHING MACHINE SHOW ON WATER ISOMETRIC.
  
 5.) THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPARATE PERMIT. PER WPB UTILITIES DEPARTMENT.
 ON THE PLUMBING SITE LATOUT SHEET IT SHOWS A 2" WATER
 SERVICE PLACE NOTE ON THE PLAN RPZ BACKFLOW REQUIRED
 WITH SEPARATE PERMIT
  
 6). THE WASHING MACHINES REQUIRE HOT WATER. PER FBC PL
 607.1
  
 NEW COMMENTS;
  
 1) FIXTURES ARE NOT VENTED EACH FIXTURE SHALL BE VENTED
 OR CONNECTED TO A VENTED LINE THE KITCHEN AND WASHING
 MACHINE SHALL BE VENTED SEPARATELY THE CANNOT CONNECT
 TO THE BATHROOM GROUP. PER FBC RES P3101.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-04-10 Cont ID  
Sent By gjohnson Date 2019-04-10 Time 16:03 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 13:19 Sent To  
Notes
2019-04-10 16:15:12PLUMBING 3RD REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS CMMENTS NOT ADDRESSED:
  
 1) DIGITAL PLANS SHALL COMPLY WITH 61G15-23.003 AND BE
 ELECTRONICALLY SIGNED ON ELECTRONICALLY TRANSMITTED
 PLANS. SOME PLANS ARE NOT SIGNED AT ALL.
  
 2) EVERY TOILET AND TUB ARE DRY VENTED. DRY VENTING OF
 FIXTURES ARE NOT PERMITTED AND MUST COMPLY WITH FBC-P
 912.2, 912.2.1, 912.2.2.
  
 3) WASHING MACHINES SHALL NOT DISCHARGE INTO THE
 HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S.
 FBC-P 912.1
  
 4) FITTING ON FLAT DRAWING APPEAR TO BE SANITARY TEE'S
 WHICH ARE NOT PERMITTED FOR USE ON THERE BACK OR SIDE
 FOR DRAINAGE. FBC-P 706.3
  
 5) THE TERM GULLY TRAP IS NOT DEFINED IN THE FBC.
 PLEASE CLARIFY. FBC 107.1
  
 6) MISSING P-TRAPS ON FLAT DRAWING. EACH FIXTURE HAS BE
 TRAPPED AND VENTED. FBC-P 1002.1
  
 7) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-P 604.10.3
  
 8)PROVIDE A COMPLETE SANITARY ISOMETRIC. FBC-P 107.3.5
  
 9) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS
 BEING USED. FBC 107.1
  
 10) HOT WATER SHALL BE ON THE LEFT SIDE OF ALL
 FIXTURES. FBC-P 607.4
  
 11) SHT.1007 LIST WATER PIPING AS BOT POLYPROPYLENE AND
 UPVC. PLEASE CLEARIFY AS UPVC IS NOT AN APPROVED PIPING
 SYSTEM PER FBC-P 605.4
  
 12) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK
 CLOSING VALVES. FBC-P 604.9
  
 13) WHY IS THERE AN AIR ADMITTANCE VALVE LOCATED ON THE
 WATER RISER DIAGRAM ON SHT. WS106? PLEASE CLEARIFY IT
 USE. FBC-P 107.1
  
  
 NEW COMMENTS :
  
 1. THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPERATE PERMIT. PER WPB UTILITIES DEPARMENT
 2. THE WASHING MACINES REQUIRE HOT WATER. PER FBC RES
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-03-19 Cont ID  
Sent By thunt Date 2019-03-19 Time 15:58 Rev Time 0.00
Received By thunt Date 2019-03-19 Time 11:30 Sent To  
Notes
2019-03-19 16:02:11PLUMBING 3RD REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 1) DIGITAL PLANS SHALL COMPLY WITH 61G15-23.003 AND BE
 ELECTRONICALLY SIGNED ON ELECTRONICALLY TRANSMITTED
 PLANS. SOME PLANS ARE NOT SIGNED AT ALL.
  
 2) EVERY TOILET AND TUB ARE DRY VENTED. DRY VENTING OF
 FIXTURES ARE NOT PERMITTED AND MUST COMPLY WITH FBC-P
 912.2, 912.2.1, 912.2.2.
  
 3) WASHING MACHINES SHALL NOT DISCHARGE INTO THE
 HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S.
 FBC-P 912.1
  
 4) FITTING ON FLAT DRAWING APPEAR TO BE SANITARY TEE'S
 WHICH ARE NOT PERMITTED FOR USE ON THERE BACK OR SIDE
 FOR DRAINAGE. FBC-P 706.3
  
 5) THE TERM GULLY TRAP IS NOT DEFINED IN THE FBC.
 PLEASE CLARIFY. FBC 107.1
  
 6) MISSING P-TRAPS ON FLAT DRAWING. EACH FIXTURE HAS BE
 TRAPPED AND VENTED. FBC-P 1002.1
  
 7) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-P 604.10.3
  
 8)PROVIDE A COMPLETE SANITARY ISOMETRIC. FBC-P 107.3.5
  
 9) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS
 BEING USED. FBC 107.1
  
 10) HOT WATER SHALL BE ON THE LEFT SIDE OF ALL
 FIXTURES. FBC-P 607.4
  
 11) SHT.1007 LIST WATER PIPING AS BOT POLYPROPYLENE AND
 UPVC. PLEASE CLEARIFY AS UPVC IS NOT AN APPROVED PIPING
 SYSTEM PER FBC-P 605.4
  
 12) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK
 CLOSING VALVES. FBC-P 604.9
  
 13) WHY IS THERE AN AIR ADMITTANCE VALVE LOCATED ON THE
 WATER RISER DIAGRAM ON SHT. WS106? PLEASE CLEARIFY IT
 USE. FBC-P 107.1
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 11:07 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 11:07 Sent To  
Notes
2019-02-06 11:08:23PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE PLUMBING PLAN.
 2. PROVIDE PLUMBING RISER DIAGRAHM.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By tklarge Date 2018-09-21 Time 06:47 Rev Time 0.00
Received By tklarge Date 2018-09-17 Time 13:32 Sent To  
Notes
2018-09-20 06:40:451) COVER SHEET - DEFINE THE OCCUPANCY OF THE STRUCTURE
 IN ACCORDANCE WITH CHAPTER 3 OF THE 2017
 FBC-BUILDING.THE PLAN NOTES THE OCCUPANCY AS "POR"
 WHICH IS NOT DEFINE IN THE FBC. CLARIFY.
 2) COVER SHEET - A NOTE ON THE LEFT SIDE OF THE COVER
 SHEET REFERS TO THE 2010 FLORIDA BUILDING CODE. REMOVE
 THIS NOTE. THE CODE IN EFFECT IS THE 2017 FBC.
 3) SHT.A1.01 - THE BREAK ROOM SINKS AND COUNTERTOPS
 SHALL COMPLY WITH THE 2017 FBC-ACCESSIBILITY SECS.
 212.3, 606.1 THROUGH 606.5. SHOW THE REQUIRED CLEAR
 FLOOR SPACE FOR THE BREAK ROOM SINKS ON THE PLANS.
 4) INDICATE THE OCCUPANT LOAD OF EACH COMMERCIAL SPACE
 ON THE FIRST FLOOR IN ACCORDANCE WITH THE 2017 FBC
 TABLE 1004.1.2.
 5) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET ROOMS ON
 THE FIRST FLOOR CANNOT SWING INTO THE REQUIRED CLEAR
 FLOOR SPACE FOR THE LAVATORY PER THE 2017 FBC-ACCESS.
 SEC.603.2.3.
 6) THE CONFIGURATION OF THE FIRST FLOOR PLAN ON SHT.
 A1.01 DOES NOT CORRELATE WITH SHT. P1.01. THIS ALSO
 OCCURS ON THE ELECTRICAL SHEET E1.02, AND THE
 MECHANICAL SHEET M0.01.
 7) THE WATER SUPPLY SHUTOFF VALVES FOR THE STACKED
 WASHER/DRYER UNITS THAT ARE LOCATED BEHIND THE UNITS
 SHALL BE PROVIDED WITH ACCESS OR THE VALVES SHALL BE
 RELOCATED TO PROVIDE ACCESS PER THE 2017 FBC-PLUMBING
 SEC.606.3.
 8) SHT. A1.02. - SUBMIT STORM DRAIN PIPING CALCULATIONS
 IN ACCORDANCE WITH THE 2017 FBC-PLUMBING SECS. L106.2,
 1106.3, 1106.4.
 9) SECONDARY ( EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL
 BE PROVIDED FOR THE ROOF PER 2017 FBC-PLUMBING
 SEC.1108.1. SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE
 END POINT OF DISCHARGE SEPARATE FROM THE PRIMARY
 SYSTEM. 2017 FBC-PLUMBING SEC. 1108.2.
 10) SHOW THE OCCUPANT LOAD FOR THE ROOF DECK /
 RECREATIONAL ROOM. FBC 107.2.1.
 11) TEMPERED WATER IS REQUIRED TO ALL THE TOILET ROOM
 LAVATORIES TO BE USED BY THE PUBLIC, CUSTOMERS, PATRONS
 AND GUESTS PER THE 2017 FBC-PLUMBING SEC.416.5.
 TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 12) HOT WATER SHALL BE SUPPLIED TO ALL BREAKROOM SINKS
 ON THE FIRST FLOOR. 2017 FBC-PLUMBING SEC.607.1.
 13) THE HOT WATER RECIRCULATION LINE SHALL BE INSULATED
 IN ITS ENTIRETY PER THE 2017 FBC-PLUMBING SEC. 607.5 &
 2017 FBC-ENERGY SEC.R403.5.3.MINIMUM WALL THICKNESS
 SHALL BE ONE INCH.
 14) THE FIRST FLOOR PLAN ON SHT. P2.01 DOES NOT
 CORRELATE WITH THE FIRST FLOOR PLAN ON SHT. A1.01.
 CLARIFY.
 15) THE FIRST FLOOR WATER RISER ON P3.01 DOES NOT
 CORRELATE WITH THE FIRST FLOOR PLAN ON SHT. A1.01 FOR
 THE TYPE OF PLUMBING FIXTURES AND AMOUNT. CLARIFY.
 16) SHT. P3.02 - THE WASTE AND VENT RISER DIAGRAM FOR
 THE FIRST FLOOR DOES NOT CORRELATE WITH THE THE FIRST
 FLOOR PLAN ON SHT.A1.01 FOR THE TYPE OF PLUMBING
 FIXTURES AND AMOUNT. CLARIFY.
 17.)THE BUILDING APPEARS TO BE OVER THREE STORIES,
 THEREFORE AN ELEVATOR WILL BE REQUIRED PER FL. STATUTE
 399.305 (2).
 18) SUBMIT COMPLETE DETAILS FOR THE ACCESSIBLE TOILET
 ROOMS ON THE FIRST FLOOR.COMPLY WITH 2017
 FBC-ACCESSIBILITY. DETAILS REQUIRED FOR GRAB BARS (
 HEIGHT, LOCATIONS, LENGTHS, ETC.), PLUMBING FIXTURE,
 TOILET PAPER AND HAND TOWEL DISPENSERS, MIRRORS, ETC.
 2017 FBC 107.2.1.
 19) IF AN ELEVATOR IS INSTALLED IN THIS BUILDING THEN
 ALL THE RESIDENTIAL UNITS SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF THE FEDERAL FAIR HOUSING ACT &
 GUIDELINES.
 20) SUBMIT FIRESTOPPING DETAILS FOR THE HORIZONTAL AND
 VERTICAL PIPE PENETRATIONS. SUBMIT MANUFACTURER'S
 INFORMATION, LISTING, INSTALLATION DETAILS, ETC. FBC
 107.2.1.
 21) BACKFLOW PREVENTION DEVICES ARE REQUIRED ON THE
 DOMESTIC WATER SERVICE AND THE FIRE SERVICE LINES. A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICES. A
 FIRE PROTECTION CONTRACTOR LICENSED AS A CONTRACTOR I,
 II OR V SHALL APPLY FOR THE PERMIT FOR THE FIRE
 BACKFLOW AND A LICENSED PLUMBING CONTRACTOR SHALL APPLY
 FOR DOMESTIC BACKFLOW. PLEASE CONTACT THE CITY OF WPB
 UTILITIES DEPT. AT 561-822-2240 FOR THE TYPE OF DEVICE
 REQUIRED AND LOCATION.
 22) THE FLOOR DRAINS ON THE FOURTH FLOOR ARE NOT
 PROPERLY VENTED. 2017 FBC-PLUMBING SEC.901.2, 901.2.1.
 23) VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL
 BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE. 2017 FBC-PLUMBING
 SEC.906.2.
 24) SHT. P4.01 - VENT INCREASER DETAIL - NOTE #1 STATES
 "VENT THROUGH ROOF TO BE 4 INCHES." THE SANITARY RISER
 ON SHT. P3.02 SHOWS ALL 2 INCH VENTS. CLARIFY.
 25) SHT.P4.01 - SHOW THE SIZE OF THE EXPANSION TANK.
 26) THE MINIMUM SIZE OF THE PAN DRAIN FOR THE WATER
 HEATER SHALL BE 3/4 INCH. 2017 FBC-PLUMBING SEC.
 504.7.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 16:46 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 11:04 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:22 Sent To  
Notes
2019-04-23 11:10:27BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE APPROPRIATE WIND LOADS PER FBCR CHPT.3.
 VERIFY THEIR COMPATIBILITY WITH THE LOAD TABLES OF THE
 SUBMITTED PRODUCT APPROVAL.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 2. DESIGNER SHALL SELECT APPROPRIATE FASTENER PATTERN
 AND PANEL GAUGE PER PAGE 2 OF 4 OF THE SUBMITTED
 PRODUCT APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 13:20 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 08:52 Sent To  
Notes
2019-03-27 13:22:56BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS. (STANDING SEAM METAL ROOF) - NOT ADDRESSED
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 2. PER AISI STANDARD S100-2007-C THE FOLLOWING MAY
 APPLY: - NOT ADDRESSED
 D6.2.1A STRENGTH (RESISTANCE) OF STANDING SEAM ROOF
 PANEL SYATEMS - IN ADDITION TO THE PROVISIONS IN
 SECTION D6.2.1, FOR LOAD COMBINATIONS THAT INCLUDE WIND
 UPLIFT, THE NOMINAL WIND LOAD SHALL BE PERMITTED TO BE
 MULTIPLIED BY 0.67 PROVIDED THE TESTED SYSTEM AND WIND
 LOAD EVALUATION SATIFIES THE FOLLOWING CONDITIONS:
 A. THE ROOF SYSTEM IS TESTED IN ACCORDANCE WITH AISI
 S906.
 B. THE WIND LOAD IS CALCULATED USING ASCE/SEI 7 FOR
 COMPONENTS AND CLADDING, METHOD 1 (SIMPLIFIED
 PROCEDURE) OR METHOD 2 (ANALYTICAL PROCEDURE).
 C. THE AREA OF THE ROOF BEING EVALUATED IS IN ZONE 2
 (EDGE ZONE) OR ZONE 3 (CORNER ZONE).
  
 PLEASE INDICATE ON THE PLAN IF THIS OPTION WILL BE
 UTILIZED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 10:26 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 13:35 Sent To  
Notes
2019-02-06 10:58:47BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS. (STANDING SEAM METAL ROOF)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 2. PER AISI STANDARD S100-2007-C THE FOLLOWING MAY
 APPLY:
 D6.2.1A STRENGTH (RESISTANCE) OF STANDING SEAM ROOF
 PANEL SYATEMS - IN ADDITION TO THE PROVISIONS IN
 SECTION D6.2.1, FOR LOAD COMBINATIONS THAT INCLUDE WIND
 UPLIFT, THE NOMINAL WIND LOAD SHALL BE PERMITTED TO BE
 MULTIPLIED BY 0.67 PROVIDED THE TESTED SYSTEM AND WIND
 LOAD EVALUATION SATIFIES THE FOLLOWING CONDITIONS:
 A. THE ROOF SYSTEM IS TESTED IN ACCORDANCE WITH AISI
 S906.
 B. THE WIND LOAD IS CALCULATED USING ASCE/SEI 7 FOR
 COMPONENTS AND CLADDING, METHOD 1 (SIMPLIFIED
 PROCEDURE) OR METHOD 2 (ANALYTICAL PROCEDURE).
 C. THE AREA OF THE ROOF BEING EVALUATED IS IN ZONE 2
 (EDGE ZONE) OR ZONE 3 (CORNER ZONE).
  
 PLEASE INDICATE ON THE PLAN IF THIS OPTION WILL BE
 UTILIZED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 16:49 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:30 Sent To  
Notes
2019-06-11 16:51:06SIGNATURE AND SEAL ON PLAN PAGES 008 THRU 025 HAVE BEEN
 VERIFIED. SIGNATURES AND SEALS ON SEVERAL SUBMITTAL
 DOCUMENTS ARE INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 NOTE: THE DESIGN PROFESSIONALS HAVE 2 OPTIONS, EITHER
 COMPLY WITH FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SUBMIT ORIGINAL PAPER DOCUMENT SIGNED AND
 SEALED.
  
 THERE WILL BE A PRINT HOLD PLACED ON THE PERMIT UNTIL
 VERIFICATION OF DESIGN PROFESSIONALS SIGNATURES AND
 SEALS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 09:51 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 12:49 Sent To  
Notes
2019-05-08 10:00:16SIGNATURE AND SEAL ON PLAN PAGES 008 THRU 025 HAVE BEEN
 VERIFIED. ALL OTHER SIGNATURES AND SEALS ON SUBMITTAL
 DOCUMENTS ARE INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 NOTE: THE DESIGN PROFESSIONALS HAVE 2 OPTIONS, EITHER
 COMPLY WITH FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SUBMIT ORIGINAL PAPER DOCUMENT SIGNED AND
 SEALED.
  
 THERE WILL BE A PRINT HOLD PLACED ON THE PERMIT UNTIL
 VERIFICATION OF DESIGN PROFESSIONALS SIGNATURES AND
 SEALS.
  
  
2019-05-06 08:46:07ELECTRICAL SHEETS NOT OK. ONLY ONE SHEET HAS THE
 REQUIRED SIGNATURE. SIGNATURE STOP FAILS FOR
 ELECTRICAL. WPB FBC 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 07:20 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:22 Sent To  
Notes
2019-04-23 07:24:06SIGNATURE AND SEAL ON PLAN PAGES 008 THRU 025 HAVE BEEN
 VERIFIED. ALL OTHER SIGNATURES AND SEALS ON SUBMITTAL
 DOCUMENTS ARE INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
2019-04-05 12:51:18SIGNATURE REVIEW STATUS FOR ELECTRICAL SHEETS: DENIED,
 SEE COMMENTS BELOW.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. PROVIDE CORRECTIONS.
 IN LIEU OF DIGITAL SIGNATURES, YOU MAY ALSO SUPPLY
 PAPER COPIES OF EACH SHEET WITH THE PROPER SIGNATURE
 AND SEAL. WPB FBC 107.1; FS 471/481
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 13:23 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 13:23 Sent To  
Notes
2019-03-27 13:25:13SIGNATURE AND SEAL OF DESIGN PROFESSIONAL HAS BEEN
 VERIFIED ON PLAN PAGES 008 THRU 025. ADDITIONAL REVIEW
 MAY BE REQUIRED UPON RE-SUBMITTAL. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-03-07 Time 13:52 Rev Time 0.00
Received By jpearson Date 2019-03-07 Time 13:52 Sent To  
Notes
2019-03-07 13:52:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 SIGNATURE REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. PROVIDE CORRECTIONS.
 IN LIEU OF DIGITAL SIGNATURES, YOU MAY ALSO SUPPLY
 PAPER COPIES OF EACH SHEET WITH THE PROPER SIGNATURE
 AND SEAL. WPB FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 10:52 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 10:52 Sent To  
Notes
2019-02-05 10:52:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 SIGNATURE REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. PROVIDE CORRECTION FOR
 COVER SHEET, STRUCTURAL SHEETS 1 - 17, AND SHEET A-1
 FOUNDATION PLAN. IN LIEU OF DIGITAL SIGNATURES, YOU MAY
 ALSO SUPPLY PAPER COPIES OF EACH SHEET WITH THE PROPER
 SIGNATURE AND SEAL. WPB FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 6 Status F Date 2019-06-11 Cont ID  
Sent By cthroop Date 2019-06-11 Time 16:46 Rev Time 0.00
Received By cthroop Date 2019-06-07 Time 09:30 Sent To  
Notes
2019-06-11 16:47:40THIRD PARTY INSPECTOR REQUIRED FOR BOLT TENSIONING.
 PROVIDE RESUME AND FLORIDA REGISTRATION OF 3RD PARTY
 INSPECTOR. CT

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status F Date 2019-05-08 Cont ID  
Sent By cthroop Date 2019-05-08 Time 09:49 Rev Time 0.00
Received By cthroop Date 2019-05-02 Time 12:45 Sent To  
Notes
2019-05-08 09:50:54THIRD PARTY INSPECTOR REQUIRED FOR BOLT TENSIONING.
 PROVIDE RESUME AND FLORIDA REGISTRATION OF 3RD PARTY
 INSPECTOR. CT

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status N Date 2019-04-23 Cont ID  
Sent By cthroop Date 2019-04-23 Time 07:24 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:22 Sent To  
Notes
2019-04-23 07:25:15THIRD PARTY INSPECTOR REQUIRED FOR BOLT TENSIONING. CT

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status N Date 2019-03-27 Cont ID  
Sent By cthroop Date 2019-03-27 Time 13:18 Rev Time 0.00
Received By cthroop Date 2019-03-27 Time 08:51 Sent To  
Notes
2019-03-27 13:20:00THIRD PARTY INSPECTOR REQUIRED FOR BOLT TENSIONING. CT

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 10:02 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 10:02 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By shill Date 2018-06-14 Time 16:06 Rev Time 0.00
Received By shill Date 2018-06-14 Time 16:06 Sent To  
Notes
2018-06-14 16:07:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FLORIDA STATUTE 553.79(5) 2016, THIS IS A THRESHOLD
 BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO
 COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 APPLICANT.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2019-05-07 Cont ID  
Sent By ajones Date 2019-05-07 Time 10:06 Rev Time 0.00
Received By ajones Date 2019-05-07 Time 10:06 Sent To  
Notes
2019-05-07 10:07:285/7/19- PASSED
 1. A SEPERATE LANDSCAPE PERMIT IS REQUIRED TO BE
 SUBMITTED PRIOR TO THE ISSUANCE OF THIS PERMIT OR A
 CONDITIONAL PERMIT FORM CAN BE ISSUED UPON APPROVAL.
 2. SEPERATE PERMITS ARE REQUIRED FOR THE DRIVEWAY,
 PARKING SPACES AND ANY FENCING.
 3. THIS PROPERTY CAN NOT BE RUN AS A ROOMING HOUSE.
  
 ANGELLA VANN, AICP
 561-317-8177
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2019-04-10 Cont ID  
Sent By ajones Date 2019-04-10 Time 17:00 Rev Time 0.00
Received By ajones Date 2019-04-19 Time 16:21 Sent To  
Notes
2019-04-10 17:01:044/10/19- PASSED
 1. A SEPERATE LANDSCAPE PERMIT IS REQUIRED TO BE
 SUBMITTED PRIOR TO THE ISSUANCE OF THIS PERMIT OR A
 CONDITIONAL PERMIT FORM CAN BE ISSUED UPON APPROVAL.
 2. SEPERATE PERMITS ARE REQUIRED FOR THE DRIVEWAY,
 PARKING SPACES AND ANY FENCING.
 3. THIS PROPERTY CAN NOT BE RUN AS A ROOMING HOUSE.
  
 ANGELLA VANN, AICP
 561-317-8177
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-03-13 Cont ID  
Sent By ajones Date 2019-03-13 Time 11:23 Rev Time 0.00
Received By ajones Date 2019-03-13 Time 11:23 Sent To  
Notes
2019-03-13 11:30:153/13/19- FAILED.
 1. REMOVE THE DOORS INTO THE BEDROOMS ON THE NORTH AND
 SOUTH SIDES OF THE 1ST FLOOR.
 2. A SEPERATE LANDSCAPE PERMIT IS REQUIRED TO BE
 SUBMITTED PRIOR TO THE ISSUANCE OF THIS PERMIT OR A
 CONDITIONAL PERMIT FORM CAN BE ISSUED UPON APPROVAL.
 3. SEPERATE PERMITS ARE REQUIRED FOR THE DRIVEWAY,
 PARKING SPACES AND ANY FENCING.
 4. THIS PROPERTY CAN NOT BE RUN AS A ROOMING HOUSE.
  
 ANGELLA VANN, AICP
 561-317-8177
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-07 Cont ID  
Sent By ajones Date 2019-02-07 Time 11:32 Rev Time 0.00
Received By ajones Date 2019-02-07 Time 11:32 Sent To  
Notes
2019-02-07 11:36:192/7/19- FAILED. PLEASE PROVIDE A WRITTEN EXPLANATION AS
 TO THE USE OF THE STRUCTURE. THE FLOOR PLANS INDICATE
 THAT IT WILL NOT BE USED AS A SINGLE FAMILY HOME.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By ajones Date 2018-06-26 Time 13:43 Rev Time 0.00
Received By ajones Date 2018-06-21 Time 16:39 Sent To  
Notes
2018-06-26 15:50:026/26/18-FAILED SEE COMMENTS BELOW:
  
 1. MAXIMUM BUILDING HEIGHT IS 30 FT. SECTION 94-75
 (A)(3)
 2. NO PARKING WAS PROVIDED ON THE SITE PLAN. 4 PARKING
 SPACES ARE REQUIRED FOR A DUPLEX.
 3. ARE THERE INTERNAL STAIRS?
 4. WHAT IS THE SETBACKS OF THE EXTERNAL STAIRCASE?
 5. LANDSCAPING SHALL BE PROVIDED AS FOLLOWS:
 1 SHADE TREE FOREACH 1500 SQ. FT. OF OPEN SPACE
 1 FLOWERING TREE FOR EACH 6,000 SQ. FT OF OPEN SPACE
 1 SHURB FOR EACH 500 SQ. FT. OF OPEN SPACE
 GRASS SHALL NOT EXCEED 60 PERCENT OF THE REQUIRED
 LANDSCAPING.
 6. A DETAIL FLOOR PLAN SHALL BE PROVIDED SO STAFF CAN
 UNDERSTAND HOW MANY UNITS ARE BEING PROPOSED.
 7. SEPERATE PERMITS ARE REQUIRED FOR LANDSCAPING,
 PARKING AND CURB CUT.
  