Plan Review Details - Permit 18060562
Plan Review Stops For Permit 18060562
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-08-13 Cont ID  
Sent By shill Date 2018-08-13 Time 10:47 Rev Time 0.00
Received By shill Date 2018-08-13 Time 10:47 Sent To  
Notes
2018-08-13 10:47:41EXEMPT FROM AIPP PER S.WELTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 15:50 Rev Time 0.00
Received By shill Date 2019-05-06 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By jwitmer Date 2018-11-26 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2018-11-26 Time 08:30 Sent To  
Notes
2018-11-26 10:10:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18060562
 ADD: 3501 N MILITARY TRAIL
 CONT: RALPH DELLA-PIETRA INC.
 TEL: 561-723-3116
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. NOV. 26/2018
  
 ACTION: BUILDING PROVISO
  
 1) SHEET A1.01 SHOWS 2 BUILDINGS. PHASE 1 IS FOR THE
 CONCESSION AND RESTROOM BUILDING ONLY.
 PHASE 2 BUILDING (1,298 SQ. FT.) NEW SHOWN AS REVISION
 # 3 IS TO BE UNDER A SEPARATE PERMIT, PLANS AND
 ASSOCIATED FEES.
  
 2) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 3) 107.3.4.2 DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & COILING DOORS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND OR FANS
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717/ FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 19:17 Rev Time 0.00
Received By shill Date 2018-08-11 Time 19:17 Sent To  
Notes
2018-08-11 19:22:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING
 2017 FBC B 2204.4.2 BOLTING.
  
 PLEASE ADVISE; WHO WILL BE PERFORMING THE INSPECTIONS
 FOR WELDED/BOLTED CONNECTIONS?
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS AS THEY
 ARE APPLICABLE FOR BUILDING REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-06 Cont ID  
Sent By jpearson Date 2019-05-06 Time 15:31 Rev Time 0.00
Received By jpearson Date 2019-05-06 Time 15:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By jpearson Date 2018-10-26 Time 14:33 Rev Time 0.00
Received By jpearson Date 2018-10-26 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 17:13 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 16:46 Sent To  
Notes
2018-07-26 17:13:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET A0.01
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 3. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 4. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 IN KITCHEN/CONCESSION AREA. NEC 210.8
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION
 TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY
 WITH CODE. FBC EC C405.5.1
 8. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO
 THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM
 OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2.
 FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
 DISTRIBUTION.? FBC EC C405.6.4.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2019-05-20 Cont ID  
Sent By Mgonzale Date 2019-05-20 Time   Rev Time 1.00
Received By mgonzale Date 2019-05-20 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By rrossano Date 2019-05-08 Time   Rev Time 0.00
Received By rrossano Date 2019-05-08 Time   Sent To I
Notes
2019-05-07 06:43:06ENGINEERING REVIEW WILL BE DONE NEXT REVIEW CYCLE
 (SPOKE W/RR; MG IS OUT OF OFFICE). SPOKE WITH
 APPLICANT; HE INFORMED THAT HE IS AWARE OF THE
 ENGINEERING REQUIREMENT / S.HILL
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 18:30 Rev Time 0.00
Received By shill Date 2018-12-21 Time 18:30 Sent To  
Notes
2018-12-21 18:31:06CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 13:10 Rev Time 0.00
Received By shill Date 2018-08-02 Time 13:10 Sent To  
Notes
2018-08-02 13:11:30CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-29 Cont ID  
Sent By pleduc Date 2019-04-29 Time   Rev Time 0.00
Received By pleduc Date 2019-04-29 Time 14:36 Sent To  
Notes
2019-04-29 14:55:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET C 5 - CRUSHED CONCRETE IS NOTED FOR THE FIRE
 DEPT. ACCESS LANE. THIS ROADWAY SHALL MEET DOT
 STANDARDS FOR ROADS AS THIS ROAD WILL BE USED BY
 EMERGENCY VEHICLES.
  
 18.2.3.4.2 SURFACE. FIRE DEPARTMENT ACCESS ROADS SHALL
 BE DESIGNED
 AND MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE
 APPARATUS AND
 SHALL BE PROVIDED WITH AN ALL-WEATHER DRIVING SURFACE.
  
 PLEASE ENSURE COMPLIANCE WITH DOT STANDARDS FOR ROADS
 FOR THE FD ACCESS LANE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-05 Cont ID  
Sent By pleduc Date 2018-10-05 Time   Rev Time 0.00
Received By pleduc Date 2018-10-05 Time 12:24 Sent To  
Notes
2018-10-05 12:38:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD PLEASE
 CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.01 WAS NOT CORRECTED WITH THE COORECT
 EDITIONS OF THE CURRENT NFPA CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
  
 PLEASE ENSURE COMPLIANCE AND UPDATE YOUR REFERNECES FOR
 FUTURE SUBMITTALS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By pleduc Date 2018-06-20 Time   Rev Time 0.00
Received By pleduc Date 2018-06-19 Time 12:57 Sent To ENG
Notes
2018-06-20 09:26:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 0.01 - THERE ARE INCORRECT EDITIONS OF THE
 FIRE CODE INDICATED.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE WITH
 CURRENT EDITIONS.
  
  
  
 2) SHEET 0.02 - NOTE # 7 INDICATES THAT FIRE SPRINKLER
 WORK WILL BE UNDERSEPARATE SHOP DRAWINGS.
  
 PLEASE CONFRM THAT THIS BUILDING WILL HAVE FIRE
 SPRINKLERS.
  
 PROPOSED FIRE SPRINKLER DETAILS SHALL BE SUBMITTED WITH
 THIS MASTER PERMIT IN COMPLIANCE WITH F.A.C. 61G
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 SHOP DRAWINGS CAN BE DEVELOPED AND SUBMITTED OFF THESE
 REQUIRMENTS.
  
 IF FIRE SPRINKLERS ARE NOT PROPOSED THESE DOCUMENTS ARE
 NOT REQUIRED AND PROVIDE AN APPICABLE NOTE OR ROMOVE #
 7 FROM THE PAGE.
  
  
  
 3) SHEET P 0.1 - THE EQUIPMENT SCHEDULE INDICATES ITEMS
 002 & 002A AS "SEE SHOP DRAWINGS". THERE ARE NO SHOP
 DRAWINGS.
  
 ALL COOKING EQUIPMENT SHALL COMPLY WITH NFPA 96 WITH
 THE HOOD AND SUPPRESSION SYSTEMS SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLOE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By gjohnson Date 2019-04-30 Time 10:21 Rev Time 0.00
Received By gjohnson Date 2019-04-30 Time 10:21 Sent To  
Notes
2019-04-30 10:24:30GAS:
  
 A SEPARATE PERMIT AND PLANS REQUIRED FOR THE KITCHEN
 GAS EQUIPMENT AND METER CONNECTION.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 15:31 Rev Time 0.00
Received By gjohnson Date 2018-12-11 Time 15:31 Sent To  
Notes
2018-12-11 15:48:132ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS GAS COMMENTS:
  
 1. NOT COMPLIED SHT. P5.1 UNDER THE GAS NOTES #5 IT IS
 REFERENCING A 5LB TO 1/2LB REGULATOR AT EACH APPLIANCE
 IS THIS A 5LB SYSTEM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1 SHT WAS CHANGED TO P6.1 NOTE #6
  
 2.NOT COMPLIED PLEASE INDICATE SYSTEM PRESSURE ON THE
 RISER. PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 3.NOT COMPLIED SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2. SHOW METER ON
 RISER RESPONSE LETTER STATED IT WAS SHOWN ON CIVIL I
 COULD NOT FIND ON CIVIL.
  
 4. COMPLIED
  
 5. NOT COMPLIED SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6.NOT COMPLIED PER FBC FG TABLE 402.4(2) AT A MBTU LOAD
 OF 480 AND A DISTANCE OF 30' THE FIRST SECTION OF PIPE
 BETWEEN THE METER AND FRYER SHALL BE 11/4 THE TWO
 SECTIONS OF PIPE BETWEEN THE FRYERS AND GRIDDLE SHALL
 BE 1" PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 7.NOT COMPLIED SHOW THE SIZES OF THE BRANCH PIPING
 CONNECTING EACH APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 8. COMPLIED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By gjohnson Date 2018-08-08 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2018-08-08 Time 11:21 Sent To  
Notes
2018-08-08 11:43:031ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. P5.1 UNDER THE GAS NOTES #5 IT IS REFERENCING A
 5LB TO 1/2LB REGULATOR AT EACH APPLIANCE IS THIS A 5LB
 SYSTEM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE SYSTEM PRESSURE ON THE RISER. PLAN
 PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR
 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6. PER FBC FG TABLE 402.4(2) AT A MBTU LOAD OF 480 AND
 A DISTANCE OF 30' THE FIRST SECTION OF PIPE BETWEEN THE
 METER AND FRYER SHALL BE 11/4 THE TWO SECTIONS OF PIPE
 BETWEEN THE FRYERS AND GRIDDLE SHALL BE 1" PLEASE
 CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 7. SHOW THE SIZES OF THE BRANCH PIPING CONNECTING EACH
 APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 8. SHOW AUTOMATIC EMERGENCY SHUTOFF VALVE ON THE RISER.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-06-06 Cont ID  
Sent By jgomez Date 2019-06-06 Time 18:57 Rev Time 0.00
Received By jgomez Date 2019-06-05 Time 18:53 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-22 Cont ID  
Sent By lmarchan Date 2019-05-22 Time 09:55 Rev Time 0.00
Received By lmarchan Date 2019-05-08 Time 11:42 Sent To  
Notes
2019-05-09 11:42:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-07 Cont ID  
Sent By shill Date 2019-05-07 Time 06:43 Rev Time 0.00
Received By shill Date 2019-04-10 Time 16:01 Sent To  
Notes
2019-04-11 16:01:24C27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-16 Cont ID  
Sent By cpuell Date 2019-01-16 Time 08:07 Rev Time 0.00
Received By cpuell Date 2018-10-01 Time 16:35 Sent To  
Notes
2018-10-02 16:35:15C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 19:24 Rev Time 0.00
Received By shill Date 2018-06-13 Time 12:44 Sent To  
Notes
2018-06-14 12:44:36C32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By jgomez Date 2019-06-06 Time 18:56 Rev Time 0.00
Received By jgomez Date 2019-06-06 Time 18:11 Sent To  
Notes
2019-06-06 18:57:15$265.21 PAID. MU-2019-016112.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 19:17 Rev Time 0.00
Received By shill Date 2018-08-11 Time 19:17 Sent To  
Notes
2018-08-11 19:17:30PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By ccole Date 2019-05-02 Time 10:12 Rev Time 0.00
Received By ccole Date 2019-05-02 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-06 Cont ID  
Sent By ccole Date 2018-11-06 Time 09:25 Rev Time 0.00
Received By ccole Date 2018-11-06 Time 09:25 Sent To  
Notes
2018-11-06 10:03:492ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18060562
 11/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CORRECT THE ENERGYGAUGE COMPLIANCE FORM WHICH IS
 SPECIFYING THE JURISDICTION AS ALACHUA COUNTY FL. ON
 PAGE 2.
  
 2) 2ND REQUEST FOR THE MANUFACTURER'S PRODUCT DATA
 (CUT) SHEETS FOR THE GAS-FIRED COOKING APPLIANCES.
 THESE SUBMITTAL DOCUMANTS CAN BE DEFERRED IF REQUESTED
 BY THE DESIGN PROFESSIONAL, HOWEVER ENGINEER STAMPED
 COPIES WILL HAVE TO BE SUBMITTED PRIOR TO INSPECTION TO
 AVOID A FAILURE IN THE FIELD.
  
 3) THE AIR BALANCE INDICATES ALL 2000 CFMS OF O/A FROM
 RTU-1 IS DEDICATED TO THE RESTROOMS, HOWEVER THE
 COMBUSTION AIR CALCULATION FOR THE KITCHEN INDICATES
 THAT 750 CFMS OF O/A FROM THE UNIT WILL BE PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By ccole Date 2018-07-12 Time 15:39 Rev Time 0.00
Received By ccole Date 2018-07-12 Time 15:34 Sent To  
Notes
2018-07-12 16:39:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060562
 7/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-17 EC.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD
 AND FIRE SUPPRESSION SYSTEM, HOWEVER THE PLANS FOR THE
 MAIN PERMIT SHALL PROVIDE THE FOLLOWING INFORMATION:
  
 A) A MEANS OF SUPPLYING MAKEUP AIR DURING THE OPERATION
 OF THE HOOD EXHAUST SYSTEM- SECTION 508.1 FBC M.
 CONCERNING THE SEQUENCE OF OPERATIONS NOTE ON SHEET
 M2.1, THE WINDOWS CANNOT BE USED AS MAKEUP AIR OPENINGS
 BECAUSE THEY ARE NOT CONSIDERED GRAVITY OPENINGS.
  
 B) EQUIPMENT SCHEDULES FOR THE HOOD, EXHAUST FAN, AND
 MAKEUP AIR UNIT.
  
 C) LOCATIONS OF THE FANS AND REQUIRED CLEARANCE
 DISTANCES- SECTIONS 401.4 AND 506.3.13 FBC M.
  
 D) AN AIR BALANCE SCHEDULE OR DIAGRAM INDICATING THE
 DESIGN OUTDOOR AIR BALANCE. THE DESIGN OUTDOOR AIR
 BALANCE SHALL INDICATE ALL EXHAUST AND REPLACEMENT AIR
 FOR THE FACILITY, PLUS THE NET EXFILTRATION IF
 APPLICABLE. THE TOTAL REPLACEMENT AIR AIRFLOW RATE
 SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE PLUS THE NET
 EXFILTRATION- SECTION 508.1.1
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 4) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 COOKING APPLIANCES AND PROVIDE CALCULATIONS- SECTION
 304 FBC FG. PLEASE NOTE THAT THERE IS NO KITCHEN
 EQUIPMENT SCHEDULE ON SHEET A1.11.
  
 5) INDICATE HOW THE DRY STORAGE ROOM WILL BE VENTILATED
 AND PROVIDE A CALCULATION- SECTION 401.2.
  
 6) SHEET M2.1 & M6.1: A SPACE HEATING SYSTEM SHALL BE
 PROVIDED TO THE KITCHEN IN COMPLIANCE WITH SECTION
 309.1 FBC M. THE AC EQUIPMENT SCHEDULE INDICATES NO
 HEAT FOR THE AHU'S.
  
 7) M2.1: CLARIFY HOW THE AC SYSTEMS WILL ONLY RUN AFTER
 HOURS ONLY WHEN THE PLAN SHOWS THEY ARE BEING
 CONTROLLED THERMOSTATICALLY. PLEASE SEE SECTION
 C403.2.4- C403.2.4.2.3 FBC EC.
  
 8) M6.1: THE GH-1 (COOK 16X16 GI) IS A GRAVITY
 VENTILATOR, HOWEVER IT IS INCLUDED IN THE EXHAUST FAN
 SCHEDULE WITH AN EXHAUST RATE OF 750 CFMS.
  
 9) SUBMIT FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR
 THE AC STANDS, AND THE ROOF MOUNTED EXHAUST FANS.
 PROVIDE SITE SPECIFIC ENGINEERING FOR UNIT ANCHORING
 AND ATTACHMENTS TO THE ROOF STRUCTURE- SECTION 301.15
 FBC M.
  
 10) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS- SECTION 307.2 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By gjohnson Date 2019-04-30 Time 10:00 Rev Time 0.00
Received By gjohnson Date 2019-04-30 Time 08:40 Sent To  
Notes
2019-04-30 10:02:54PLUMBING PROVISO:
  
 COMPLETE PRIOR TO ROUGH INSPECTION
  
 1. SHOW SLOPE OF PIE ON STORM RISER ISOMETRIC. PER FBC
 PL 1106.2
  
 2. SHT P2.2 PROVIDE HEADINGS ON ROOF SQFT CALCULATION
 AND GPM TO COMPLY WITH CURRENT CODE. PER FBC PL 1106.2
  
  
 PLUMBING:
  
 A SEPARATE PERMIT AND PLANS REQUIRED FOR THE KITCHEN
 FIXTURE CONNECTIONS TO GREASE LINE AND HOT AND COLD
 WATER.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 12:57 Rev Time 0.00
Received By gjohnson Date 2018-12-11 Time 12:56 Sent To  
Notes
2018-12-11 13:16:062ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS PLUMBING COMMENTS:
  
 1. COMPLIED
  
 2. PARTIALLY COMPLIED THE FLOOR DRAINS AND THE MOP SINK
 SHALL BE INCLUDED IN THE GREASE TRAP SIZING
 CALCULATIONS. PER FBC PL 1003.3.1 FLOOR DRAIN NOT
 INCLUDED
  
 3. NOT COMPLIED SHT. P2.1, P3.1 THE FLOOR PLAN SHOWS A
 SINK NEXT TO THE REACH IN FREEZER #007 IT DOES NOT SHOW
 UP ON THE ISOMETRIC DRAWINGS THE SINK SHALL CONNECT TO
 THE GREASE SYSTEM. PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
  
 4. NOT COMPLIED PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS AND INSTALLATION GUIDE FOR THE GREASE
 TRAP. PER WPB AMEND TO FBC 107.2.1
  
 5. NOT COMPLIED PLEASE EXPAND THE ISOMETRIC DRAWING
 THEY ARE TO CONGESTED TO DETERMINE CODE COMPLIANCE. PER
 WPB AMEND TO FBC 107.2.1
  
 6. COMPLIED
  
 NEW COMMENTS:
  
 1. SHOW SLOPE OF PIE ON STORM RISER ISOMETRIC. PER FBC
 PL 1106.2
  
 2. SHT P2.2 PROVIDE HEADINGS ON ROOF SQFT CALCULATION
 AND GPM TO COMPLY WITH CURRENT CODE. PER FBC PL 1106.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By gjohnson Date 2018-08-08 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2018-08-07 Time 15:54 Sent To  
Notes
2018-08-08 11:20:281ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MOPSINK SHALL DISCHARGE THROUGH THE GREASE TRAP.
 PER FBC PL 1003.3.1
  
 2. THE FLOOR DRAINS AND THE MOP SINK SHALL BE INCLUDED
 IN THE GREASE TRAP SIZING CALCULATIONS. PER FBC PL
 1003.3.1
  
 3. SHT. P2.1, P3.1 THE FLOOR PLAN SHOWS A SINK NEXT TO
 THE REACH IN FREEZER #007 IT DOES NOT SHOW UP ON THE
 ISOMETRIC DRAWINGS THE SINK SHALL CONNECT TO THE GREASE
 SYSTEM. PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE GREASE TRAP. PER WPB AMEND
 TO FBC 107.2.1
  
 5. PLEASE EXPAND THE ISOMETRIC DRAWING THEY ARE TO
 CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB AMEND
 TO FBC 107.2.1
  
 6. PLEASE PROVIDE STORM DRAIN ISOMETRIC DRAWING
 INCLUDING SQFT DRAINED. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status N Date 2019-04-30 Cont ID  
Sent By gjohnson Date 2019-04-30 Time 10:03 Rev Time 0.00
Received By gjohnson Date 2019-04-30 Time 10:03 Sent To  
Notes
2019-04-30 10:19:16GREASE INTERCEPTOR: NOT APPROVED UNDER THIS PERMIT.
  
 SEPARATE PERMIT AND PLANS WITH MANUFACTURE SIZING
 CALCULATIONS REQUIRED FOR INSTILLATION OF GREASE
 INTERCEPTOR.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 13:25 Rev Time 0.00
Received By gjohnson Date 2018-12-11 Time 13:25 Sent To  
Notes
2018-12-11 15:31:022ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. C.6 SHOWS A 750 GAL. CONCRETE GREASE
 INTERCEPTOR SHT. P5.1 SHOWS A GB2 35-50 GAL.
 INTERCEPTOR PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE SCHIER GB2 SHALL BE INSTALLED INDOORS ONLY. PER
 MANUFACTURE SPECIFICATIONS PLEASE CLARIFY ON PLUMBING
 FLOOR PLAN THE LOCATION.
  
 3. SHT. P5.1 THE MANUFACTURE SPECIFICATIONS SHOWN ON
 PLAN DO NOT MATCH SPECIFICATION FROM SCHIER FOR A GB2
 PLEASE CLARIFY.
  
 4. PROVIDE SIZING CALCULATIONS FROM SCHIER TO INCLUDE
 THE SINGLE COMPARTMENT SINK NEXT TO WALK IN FREEZER,
 FLOOR DRAIN, MOP SINK AND THREE COMP SINK. THE MIN SIZE
 OF THE GREASE INTERCEPTOR SHALL BE 750GAL OR A
 HYDROMACHANICAL EQUIVALENT PER WPB UTILITIES DEPT YOU
 CAN CONTACT JEFFERY ODOMS AT 822-2172 WITH QUESTIONS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2019-05-21 Time   Rev Time 0.00
Received By ahansen Date 2019-05-21 Time 14:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2019-04-25 Time   Rev Time 0.00
Received By ahansen Date 2019-04-25 Time 13:44 Sent To  
Notes
2019-04-25 13:44:33 
 - REPEAT ISSUE: PLEASE NOTE THAT A SEPARATE LANDSCAPING
 PERMIT IS REQUIRED FOR THE LANDSCAPING ASSOCIATED WITH
 THE CONCESSION BUILDING AND ANY OTHER AREAS AFFECTED BY
 THE CONSTRUCTION RELATED TO THE SUBJECT BUILDING
 PERMIT. AS STATED IN PREVIOUS REVIEWS, THE LANDSCAPING
 PERMIT (AND ANY OTHER NEEDED PERMITS) HAVE TO BE
 SUBMITTED PRIOR TO ZONING'S APPROVAL OF THE CONCESSION
 STAND BUILDING PERMIT. WHILE THE LATEST RESPONSE BY THE
 APPLICANT STATES "NOTED, THE CONTRACTOR SHALL ACQUIRE A
 SEPARATE LANDSCAPE PERMIT AS REQUIRED", TO DATE NO
 LANDSCAPING PERMIT HAS BEEN SUBMITTED, HENCE ZONING
 CANNOT APPROVE THE CONCESSION STAND BUILDING PERMIT.
  
 - CITY STAFF HAD PREVIOUSLY COMMENTED THAT CONSTRUCTION
 OF ANY SIDEWALK, DRIVEWAY, OR PAVED AREA WITHIN THE
 SCOPE OF WORK WOULD REQUIRE A SEPARATE PAVING PERMIT.
 SHEETS C.4 AND C.5 OF THE PAVING, GRADING, AND DRAINAGE
 PLANS SUBMITTED WITH THIS APPLICATION SHOW AREAS
 IDENTIFIED FOR "PROPOSED CONCRETE" AND "PROPOSED
 SIDEWALK". AGAIN, THIS WORK REQUIRES SUBMITTAL OF A
 SEPARATE PAVING PERMIT PRIOR TO ZONING'S APPROVAL OF
 THE CONCESSION STAND BUILDING PERMIT.
  
  
 ALL OF THE PERMITS REFERENCED ABOVE HAVE TO BE
 SUBMITTED PRIOR TO ZONING'S APPROVAL OF THE CONCESSION
 STAND BUILDING PERMIT

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2019-01-15 Time   Rev Time 0.00
Received By ahansen Date 2019-01-15 Time 15:24 Sent To  
Notes
2019-01-15 15:42:39PLEASE NOTE THAT THESE ARE REPEAT COMMENTS FROM THE
 REVIEW OF THE FIRST SUBMITTAL WHICH WERE NOT ADDRESSED
 IN THIS SUBMITTAL:
  
 - THE EAST AND SOUTH FACADES OF THE EXTERIOR ELEVATION
 PLANS FOR THE CONCESSION STAND BUILDING SHOW EITHER THE
 OXBRIDGE ACADEMY NAME IN LARGE LETTERS OR THE SCHOOL'S
 LOGO. PLEASE NOTE THAT PER THE CITY'S ZONING CODE THE
 SCHOOL'S NAME AND THE LOGO WOULD BE CONSIDERED AS
 SIGNS, WHICH WILL REQUIRE SUBMITTAL OF A SEPARATE SIGN
 PERMIT APPLICATION.
  
 - PLEASE NOTE THAT A SEPARATE LANDSCAPING PERMIT IS
 REQUIRED FOR THE LANDSCAPING ASSOCIATED WITH THE
 CONCESSION BUILDING.
  
 - IT IS NOT CLEAR FROM THE DOCUMENTS SUBMITTED WITH THE
 PERMIT APPLICATION WHETHER THE APPLICANT IS PROPOSING
 AT THIS TIME TO CONSTRUCT THE STORAGE ROOM TO THE WEST
 OF THE CONCESSION STAND/RESTROOM BUILDING, THE
 SIDEWALKS CONNECTING THE DIFFERENT BUILDINGS, THE
 BASEBALL FIELD, OR THE PARKING LOT. PLEASE NOTE THAT
 CONSTRUCTION OF ANY OF THESE REQUIRES A SEPARATE
 BUILDING PERMIT.
  
 - IF THE PROPOSED PARKING LOT IS NOT BEING CONSTRUCTED
 AT THIS TIME, THEN A DEMOLITION PERMIT IS REQUIRED FOR
 THE DEMOLITION WORK SHOW ON SHEET C.3 FOR THE DRIVEWAY
 AREA TO ACCESS THE PARKING LOT.
  
 ALL OF THE PERMITS REFERENCED ABOVE HAVE TO BE
 SUBMITTED PRIOR TO ZONING'S APPROVAL OF THE CONCESSION
 STAND BUILDING PERMIT

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By ahansen Date 2018-06-26 Time   Rev Time 0.00
Received By ahansen Date 2018-06-26 Time 16:15 Sent To  
Notes
2018-06-26 16:23:43COMMENTS BY ALEX HANSEN:
 - THE CONCESSION STAND/RESTROOM BUILDING SHOWN IN THE
 FLOOR PLAN SHEETS INCLUDED IN THE BUILDING PERMIT
 APPLICATION HAS A TOTAL SQUARE FOOTAGE OF 2,121. THIS
 IS ALMOST 100 SQUARE FEET MORE THAN THE 2,027 SQUARE
 FEET SHOWN FOR THIS BUILDING IN THE SITE PLAN APPROVED
 ON MARCH 28, 2018. EITHER THE BUILDING DIMENSIONS IN
 THE BUILDING PLAN DOCUMENTS NEED TO BE REVISED AND MADE
 CONSISTENT WITH THOSE IN THE APPROVED SITE PLAN, OR THE
 APPLICANT NEEDS TO SUBMIT A MAJOR PLANNED DEVELOPMENT
 AMENDMENT APPLICATION TO REVISE THE DIMENSIONS OF THE
 CONCESSION STAND/RESTROOM BUILDING DEPICTED IN THE SITE
 PLAN.
  
 - THE EAST AND SOUTH FACADES OF THE EXTERIOR ELEVATION
 PLANS FOR THE CONCESSION STAND BUILDING SHOW EITHER THE
 OXBRIDGE ACADEMY NAME IN LARGE LETTERS OR THE SCHOOL?S
 LOGO. PLEASE NOTE THAT, PER THE CITY?S ZONING CODE, THE
 SCHOOL?S NAME AND THE LOGO WOULD BE CONSIDERED AS
 SIGNS, WHICH WILL REQUIRE SUBMITTAL OF A SIGN PERMIT
 APPLICATION.
  
 - PLEASE NOTE THAT A SEPARATE LANDSCAPE PERMIT IS
 REQUIRED FOR THE LANDSCAPING ASSOCIATED WITH THE
 CONCESSION BUILDING.
  
 - IT IS NOT CLEAR FROM THE DOCUMENTS SUBMITTED WITH THE
 PERMIT APPLICATION WHETHER THE APPLICANT IS PROPOSING
 AT THIS TIME TO CONSTRUCT THE STORAGE ROOM TO THE WEST
 OF THE CONCESSION STAND/RESTROOM BUILDING, THE
 SIDEWALKS CONNECTING THE DIFFERENT BUILDINGS, THE
 BASEBALL FIELD OR THE PARKING LOT. PLEASE NOTE THAT
 CONSTRUCTION OF ANY OF THESE REQUIRES A SEPARATE
 BUILDING PERMIT.
  
 - IF THE PROPOSED PARKING LOT IS NOT BEING CONSTRUCTED
 AT THIS TIME, THEN A DEMOLITION PERMIT IS REQUIRED FOR
 THE DEMOLITION WORK SHOWN ON SHEET C.3 FOR THE DRIVEWAY
 AREA TO ACCESS THE PARKING LOT.
  


Account Summary | Usage Policy | Privacy Policy