Plan Review Details - Permit 18060557
Plan Review Stops For Permit 18060557
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2018-08-28 Time 18:38 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 06:54 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 06:50 Sent To I
Notes
2018-07-25 06:54:58PENDING PLUMBING APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By rmcdouga Date 2018-07-05 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2018-07-05 Time 14:30 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 06:34 Rev Time 0.00
Received By fgiaquin Date 2018-08-29 Time 17:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-28 Cont ID  
Sent By jleahy Date 2018-06-28 Time 17:31 Rev Time 0.00
Received By jleahy Date 2018-06-28 Time 17:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By tklarge Date 2018-06-28 Time 06:41 Rev Time 0.00
Received By tklarge Date 2018-06-28 Time 06:23 Sent To  
Notes
2018-06-28 06:42:03THERE IS NO GAS ASSOCIATED WITH THIS POOL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2018-08-21 Time 14:09 Sent To  
Notes
2018-08-22 14:10:00RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 06:55 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 09:32 Sent To  
Notes
2018-07-12 09:32:28RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-05 Cont ID  
Sent By rmcdouga Date 2018-07-05 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2018-06-12 Time 12:56 Sent To  
Notes
2018-06-13 12:57:10ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2018-08-30 Time 07:09 Sent To  
Notes
2018-08-30 07:23:5408/30/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 05:00 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 04:43 Sent To I
Notes
2018-07-24 10:57:041) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE HEAT
 PUMP. WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 2) THE HEAT PUMP SHALL COMPLY WITH 2017 FBC- ENERGY
 SEC. R 403.10.5.2ND REQUEST.
 3) SUBMIT TWO COPIES OF AN ENLARGED POOL PUMP CURVE.
 THE PRINTING IS ILLEGIBLE ON THE ONE ON THE PLANS.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS.2ND REQUEST.
 4) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM CCOMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES,
 HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS.CLARIFY. PLEASE IDENTIFY
 THE SOURCE OF THE TDH CALCULATOR FOR VERIFICATION OF
 THE TDH.
 5) SHT. 4 OF 4 - GENERAL NOTES SHEET - VARIOUS NOTES
 REFER TO APSP 7 - 2006 EDITION. THE 2017 FBC REFERENCES
 THE 2013 EDITION. REVISE ALL NOTES TO REFLECT THE 2013
 EDITION. 2ND REQUEST.
 6) VOID OUT OLD PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By tklarge Date 2018-06-28 Time 07:20 Rev Time 0.00
Received By tklarge Date 2018-06-28 Time 06:23 Sent To  
Notes
2018-06-28 06:54:041) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE HEAT
 PUMP. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE HEAT PUMP SHALL COMPLY WITH 2017 FBC- ENERGY
 SEC. R 403.10.5.
 3) IS THE POOL EQUIPPED WITH AN AUTO-FILL? CLARIFY ON
 THE PLANS.
 4) SUBMIT TWO COPIES OF THE AN ENLARGED POOL PUMP
 CURVE. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS.
 5) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER). REVISE SHT. 2 OF 4.
 6) SHT. 4 OF 4 - GENERAL NOTES SHEET - VARIOUS NOTES
 REFER TO APSP 7 - 2006 EDITION. THE 2017 FBC REFERENCES
 THE 2013 EDITION. REVISE ALL NOTES TO REFLECT THE 2013
 EDITION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-15 Cont ID  
Sent By mcruz Date 2018-06-15 Time 16:32 Rev Time 0.00
Received By mcruz Date 2018-06-15 Time 16:28 Sent To B
Notes
***NONE***