Plan Review Details - Permit 18060545
Plan Review Stops For Permit 18060545
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-09-27 Cont ID  
Sent By jleahy Date 2018-09-27 Time 16:39 Rev Time 0.00
Received By jleahy Date 2018-09-27 Time 16:39 Sent To  
Notes
2018-09-27 16:40:24DID REVIEW UNDER THE ELECTRICAL PLAN REVIEW FOR SLAB
 JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-09-19 Cont ID  
Sent By rmcdouga Date 2018-09-19 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2018-09-19 Time 16:21 Sent To I
Notes
2018-09-19 16:23:02PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMMENT NOT ADDRESSED. SUBMIT TWO SETS OF GENERATOR
 PAD DETAILS AND GENERATOR ANCHORING DETAILS. FBC-R
 301.1
  
 2) COMMENT NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2018-08-28 Time 07:37 Sent To  
Notes
2018-08-28 07:57:36PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMMENT NOT ADDRESSED. SUBMIT TWO SETS OF GENERATOR
 PAD DETAILS AND GENERATOR ANCHORING DETAILS. FBC-R
 301.1
  
 2) COMMENT NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2018-07-02 Time 18:55 Sent To I
Notes
2018-07-02 19:03:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD DETAILS AND
 GENERATOR ANCHORING DETAILS. FBC-R 301.1
  
 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-27 Cont ID  
Sent By jleahy Date 2018-09-27 Time 16:39 Rev Time 0.00
Received By jleahy Date 2018-09-27 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-28 Cont ID  
Sent By jleahy Date 2018-06-28 Time 17:30 Rev Time 0.00
Received By jleahy Date 2018-06-28 Time 17:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-09-19 Cont ID  
Sent By tklarge Date 2018-09-19 Time 08:07 Rev Time 0.00
Received By tklarge Date 2018-09-18 Time 05:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By tklarge Date 2018-08-28 Time 04:18 Rev Time 0.00
Received By tklarge Date 2018-08-23 Time 05:34 Sent To B
Notes
2018-08-28 04:14:031) THE EXISTING GAS PLAN ON FILE IN THE CITY OF WPB
 RECORDS SHOWS A FUTURE LINE FOR A POOL HEATER WITH A
 BTU LOAD OF 400,000. THIS IS NOT SHOWN ON THE SUBMITTED
 GAS DRAWING. THIS " FUTURE" OUTLET AND BTU LOAD MUST BE
 INCLUDED IN THE TOTAL BTU LOAD OF THE SYSTEM. 2017 FBCR
 SEC. G2412.3, G2412.4, G2412.8.
 2) THE SUBMITTED GAS DRAWING SHOWS THE EXISTING SYSTEM
 TO THE INTERIOR AS BEING A LESS THAN 2 PSI SYSTEM YET
 THE GAS PLAN ON FILE IN THE CITY RECORDS SHOWS THE
 INTERIOR PIPING TO BE A 2 PSI SYSTEM. CLARIFY. NOTE -
 AT A LESS THAN 2 PSI SYSTEM THE INTERIOR PIPING OF CSST
 IS ALL UNDERSIZED FOR A DISTANCE OF 110 FEET AS SHOWN
 ON THE PLAN THE SUBMITTED SIZING TABLE.
 3) THE MINIMUM SIZE SLEEVE FOR THE 3/4 INCH PE PIPE
 SHALL BE 1 1/4 INCHES IN DIAMETER.
 4) THE GAS PLAN ON FILE IN CITY RECORDS SHOWS THE
 EXISTING WATER HEATER AS 100,000 BTU'S BUT THE NEW
 SUBMITTED GAS PLAN SHOWS THE EXISTING WATER HEATER AS
 50,000 BTU'S. CLARIFY.
 5) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING GAS GRILL WITH A BTU LOAD OF 60,000. THIS
 IS NOT SHOWN ON THE EXISTING SYSTEM ON THE SUBMITTED
 GAS DRAWING. CLARIFY.
 6) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 TWO FIREPLACES AT 50,000 BTU'S EACH AND THE SUBMITTED
 GAS PLAN SHOWS ONE EXISTING FIREPLACE AT 90,000 BTU'S .
 CLARIFY.
 NOTE: ACCORDING TO THE GAS PLAN ON FILE IN CITY RECORDS
 THE EXISTING BTU LOAD IS 750,000 AND THE SUBMITTED GAS
 PLAN SHOWS THE EXISTING BTU LOAD AS 240,000. CLARIFY.
 7) THE MINIMUM SIZE SCHEDULE 40 METALLIC PIPE AT THE
 OUTLET OF THE GAS METER SHALL BE 1 INCH. 2017 FBCR
 TABLE G2413.4 (2) .
 8) SHOW THE LOCATION OF THE GAS PIPING TO THE GENERATOR
 ON BOTH COPIES OF THE SURVEY. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) IF THE EXISTING INTERIOR GAS PIPING WILL REMAIN AS A
 2 PSI SYSTEM, PLACE A NOTE ON THE PLAN THAT EXISTING
 REGULATORS ARE LOCATED AT EACH APPLIANCE.
  
 ****NOTE*** - I HAVE PLACED A COPY OF THE ORIGINAL GAS
 PLAN AND SUBSEQUENT REVISIONS IN THE APPLICATION TO BE
 USED AS REFERENCE.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By tklarge Date 2018-07-02 Time 11:25 Rev Time 0.00
Received By tklarge Date 2018-06-27 Time 13:12 Sent To  
Notes
2018-06-27 14:42:1106/27/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 I HAVE PUT IN YOUR PACKAGE A GAS ISOMETIC FROM 2007 FOR
 YOUR REFFREANCE ON THE OLD GAS SYSTEM THAT WAS IN THE
 CITY RECAORD, PLEASE USE THESE FOR REFFREANCE ONLY,
 THEY WILL BE TURNED DOWN IF USED AS RE SUBMITALS.
  
 1. PLEASE LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL
 GAS RES. SEC. G2420.4.
 2. IT APPREARS THE AN EXSISTING GAS AND APPLIANCE ARE
 IN A PREVIOUS GAS SYSTEM, PLEAE LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE 2017 FBC FUEL GAS SECS. 401.8 THROUGH
 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4 (37) OR 2017
 FBC FUEL GAS RES. SEC. G2413.
 3. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. IF THIS IS A NEW METER, PLEASE INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER
 2017 FBC FUEL GAS RES. SEC. G2413.2
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1.
 5. NEED TO SHOW SHUTOFF VALVE ON GAS, 2017 FBC FUEL GAS
 RES. SEC. 404.15, 411.
 6. THE COPY OF THE TABLE 402.4(22) THIS FROM AN
 OUTDATED FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS
 THE 2017 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT
 SIZING TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 7. PLEASE SUBMIT TWO COPIES OF TABLES OF ALL GAS PIPING
 MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 8. YOUR TANK SHOW TO BE MIN OF 10' FROM ANY DOOR OR
 SCREENED WINDOW AND 4? HIGH FENCE ACCORDING TO
 MANUFACTURES INSTALATION MANUAL WHICH WAS NOT
 SUBMITTED, ZOING HAS ISSUES WITH YOUR LOCATION SO
 PLEASE PROVIDE SPEC ON YOUR NEXT REVIEW AND HAVE ON
 SITE FOR FIELD VERIFICATION OF FINAL INSPECTION. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-27 Cont ID  
Sent By jleahy Date 2018-09-27 Time 16:40 Rev Time 0.00
Received By jleahy Date 2018-09-27 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-19 Cont ID  
Sent By rmcdouga Date 2018-09-19 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2018-09-14 Time 09:43 Sent To  
Notes
2018-09-17 09:43:37RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By cpuell Date 2018-08-28 Time 10:15 Rev Time 0.00
Received By cpuell Date 2018-08-14 Time 14:18 Sent To  
Notes
2018-08-15 14:18:24RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2018-06-12 Time 12:53 Sent To  
Notes
2018-06-13 12:53:32ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By mcruz Date 2018-08-22 Time 14:16 Rev Time 0.00
Received By mcruz Date 2018-08-22 Time 14:16 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By mcruz Date 2018-06-15 Time 15:01 Rev Time 0.00
Received By mcruz Date 2018-06-15 Time 14:42 Sent To B
Notes
2018-06-15 15:01:46ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. THE
 GENERATOR MUST BE AT LEAST 6 FEET FROM THE EAST
 PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]