Plan Review Details - Permit 18060457
Plan Review Stops For Permit 18060457
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-30 Cont ID  
Sent By rmcdouga Date 2018-06-30 Time 17:54 Rev Time 0.00
Received By shill Date 2018-06-30 Time 17:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 18:40 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 18:40 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By jpearson Date 2018-06-26 Time 18:38 Rev Time 0.00
Received By jpearson Date 2018-06-26 Time 17:57 Sent To  
Notes
2018-06-26 18:38:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON REVISION APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
 2. PLAN SHOWING NEW UNITS IS CALLING OUT CIRCUITS FROM
 PANELS THAT DON'T EXIST ON THE RISER DIAGRAM OR IN THE
 PANEL SCHEDULES. PROVIDE CORRECTIONS. NEC 215.2, 215.5,
 408.4, 408.30; WPB FBC 107.2.1
 3. PROVIDE CORRECTED LOAD CALCULATIONS WITH NEW PANEL
 SCHEDULES. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-02 Cont ID  
Sent By pleduc Date 2018-07-02 Time   Rev Time 0.00
Received By pleduc Date 2018-07-02 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-24 Cont ID  
Sent By shill Date 2018-08-24 Time 16:03 Rev Time 0.00
Received By shill Date 2018-08-22 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-20 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-03 Cont ID  
Sent By shill Date 2018-07-03 Time 12:40 Rev Time 0.00
Received By shill Date 2018-06-19 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 15:39 Rev Time 0.00
Received By ccole Date 2018-08-24 Time 15:39 Sent To  
Notes
2018-08-24 16:03:36MECHANICAL PROVISOS:
 CCOLE- 8/24/18
  
 1) THE KITCHEN HOOD MAKEUP AIR FAN (KSF) SHALL BE IN
 COMPLIANCE WITH SECTION 506.5.1.2 FBC M.
  
 506.5.1.2 IN-LINE FAN LOCATION.
  
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.\
  
 2) COMPLIANCE WITH SECTION 508.1.1 FBC M REQUIRED.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-02 Cont ID  
Sent By ccole Date 2018-08-02 Time 11:34 Rev Time 0.00
Received By ccole Date 2018-08-01 Time 16:50 Sent To  
Notes
2018-08-02 12:04:121ST REVIEW FBC-2017 MECHANICAL
 REVISION #18060457
 MASTER #18020254
 8/2/18
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED STRUCTURAL ENGINEERING FOR TIE DOWN OF
 THE VRF CONDENSERS IS NOT ELECTRONICALLY SIGNED AND
 SEALED BY THE ENGINEER WHO PREPARED THE DRAWING-
 SECTION 61G15-23.005 FAC. A) THE DRAWING DOES NOT
 SPECIFICALLY REFERENCE WHICH ROOFTOP UNITS ARE TO BE
 INSTALLED IN ACCORDANCE WITH THE ENGINEERING. B) THE
 DRAWING DOES NOT INDICATE LATERAL AND UPLIFT PRESSURES
 BASED ON THE DESIGN CRITERIA AND THE DIMENSIONS OF THE
 UNITS. C) THE DESIGN INDICATES THE UNITS NEED TO BE
 STRAPPED TO THE SUPPORT BEAMS WHICH DOES NOT APPEAR TO
 BE COMPATIBLE WITH THE DESIGN OF THE VRF CONDENSERS,
 AND WILL ALSO REQUIRE REMOVAL OF STRAPPING FOR
 SERVICING. PLEASE NOTE THAT COMPLETE WIND LOAD
 ENGINEERING FOR ALL THE ROOFTOP UNITS IS REQUIRED
 INCLUDING THE OAU-1 & 2, THE VRF CONDENSERS, AND THE
 SMOKE CONTROL FANS AND FAN CURBS.
  
 2) THE SUBMITTED NARRATIVE RESPONSE INDICATES
 ADJUSTMENT OF VALUE BASED ON THE ELECTRICAL ONLY.
 PLEASE INCLUDE THE VALUE INCREASE FOR MECHANICAL WHICH
 INCLUDES THE CHANGE TO THE VRF SYSTEMS.
  
 3) PLEASE INDICATE ON THE PLANS THAT ALL FIRE/SMOKE
 DAMPERS AT SHAFT LOCATIONS WILL BE MOTORIZED TO OPERATE
 AUTOMATICALLY IN SEQUENCE WITH THE SMOKE CONTROL
 SYSTEM. PROVIDE AN "M" SYMBOL AT EACH LOCATION.
  
 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR
 THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING
 APPROVAL BY THE ENGINEER OF RECORD. PLEASE NOTE THAT
 WIND LOAD ENGINEERING FOR THE ROOFTOP UNITS MAY BE
 ADDED TO THE LIST IF REQUESTED.
  
 A) SMOKE CONTROL FANS.
 B) FIRE AND FIRE/SMOKE DAMPERS.
 C) BAROMETRIC DAMPERS
 D) DUCT SMOKE DETECTORS
 E) AC ROOF AND DUCT STANDS, WALL BRACKETS
 F) EXHAUST AND OUTSIDE AIR LOUVERS
 G) PIPING INSULATIONS
 H) ACCESS PANELS
 I) GENERATOR
 J) COMMERCIAL CLOTHES DRYERS
 K) COOKING APPLIANCES
 L) DUCT FIRE WRAPPING
 M) FIRESTOPPING AND FIRE CAULKING
  
 5) PLEASE SEE THE PROVISO NOTES UNDER THE MASTER PERMIT
 #18020254. IT IS IMPORTANT THAT THESE REQUIREMENTS ARE
 MET AS SOON AS POSSIBLE TO AVOID CONFLICTS IN THE
 FIELD, AND TO AVOID DELAYS IN CONSTRUCTION, AND FOR CO
 OF THE BUILDING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By ccole Date 2018-06-26 Time 11:23 Rev Time 0.00
Received By ccole Date 2018-06-26 Time 11:23 Sent To  
Notes
2018-06-26 11:24:191ST REVIEW FBC-2017 MECHANICAL
 REVISION #18060457
 MASTER #18020254
 6/26/18
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A REVISED ENERGY COMPLIANCE REPORT
 LISTING THE NEW VRF SYSTEMS- TABLE C403.2.3 (11) FBC
 EC.
  
 2) PROVIDE A REFRIGERANT PIPING RISER DRAWING FOR THE
 NEW SYSTEMS- SECTION 304.1 FBC M.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW ROOF TOP CONDENSERS- SECTION 301.15 FBC M. SUBMIT A
 FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE ROOF
 STANDS.
  
 4) SHEETS M-101, 102, & 103: SHOW THE REFRIGERANT
 PIPING RUNS AND CHASE LOCATIONS- SECTION 1107 FBC M.
  
 5) M-101, 102, 103: SHOW THE LOCATIONS OF ACCESS PANELS
 WHERE VRF UNITS ARE LOCATED ABOVE HARD CEILINGS. PLEASE
 INCLUDE NOTES AND DETAILS FOR CONSTRUCTION OF THE
 PANELS- SECTION 306.1 FBC M.
  
 6) M-102, 103: FIRE DAMPERS FOR O/A DUCTS PENETRATING
 THE CORRIDOR WALLS ARE SHOWN AT MANY LOCATIONS ON THE
 3RD- 9TH FLOORS (M-103), BUT ARE NOT SHOWN ON ANY OF
 THE PENETRATIONS ON THE 2ND FLOOR (M-102)- PLEASE
 CLARIFY.
  
 7) PROVIDE A UL APPROVED FIRESTOPPING ASSEMBLY FOR THE
 REFRIGERANT PIPE AND DUCT PENETRATIONS- SECTION 714 FBC
 B.
  
 8) PLEASE ADJUST THE 0.00 VALUE ON THE REVISION
 APPLICATION TO SHOW ALL ASSOCIATED COSTS WITH THE
 REDESIGN OF THE HVAC SYSTEMS INCLUDING, BUT NOT LIMITED
 TO A) LABOR, MATERIAL, EQUIPMENT TO INSTALL THE
 SYSTEMS. B) DEMOLITION, REMOVAL AND DISPOSAL OF THE
 COOLING TOWERS AND WATER PIPINGS, C) DESIGN FEES. SEE
 SECTION 109.3 WPB.
  
 9) PLEASE SEE THE PROVISO NOTES UNDER THE MASTER PERMIT
 #18020254. IT IS IMPORTANT THAT THESE REQUIREMENTS ARE
 MET AS SOON AS POSSIBLE TO AVOID CONFLICTS IN THE
 FIELD, AND TO AVOID DELAYS IN CONSTRUCTION, AND FOR CO
 OF THE BUILDING.
  
 10) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR
 THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING
 APPROVAL BY THE ENGINEER OF RECORD:
  
 A) SMOKE CONTROL FANS.
 B) FIRE AND FIRE/SMOKE DAMPERS.
 C) BAROMETRIC DAMPERS
 D) DUCT SMOKE DETECTORS
 E) AC ROOF AND DUCT STANDS, WALL BRACKETS
 F) EXHAUST AND OUTSIDE AIR LOUVERS
 G) PIPING INSULATIONS
 H) ACCESS PANELS
 I) GENERATOR
 J) COMMERCIAL CLOTHES DRYERS
 K) COOKING APPLIANCES
 L) DUCT FIRE WRAPPING
 M) FIRESTOPPING AND FIRE CAULKING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-07-03 Cont ID  
Sent By gjohnson Date 2018-07-03 Time 12:21 Rev Time 0.00
Received By tklarge Date 2018-07-03 Time 12:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By shill Date 2018-08-24 Time 16:03 Rev Time 0.00
Received By shill Date 2018-08-24 Time 16:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-07-26 Cont ID  
Sent By shill Date 2018-07-26 Time 18:54 Rev Time 0.00
Received By shill Date 2018-07-26 Time 18:54 Sent To  
Notes
2018-07-26 18:55:07SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES, S SHEETS) ARE
 IN ACCORDANCE WITH FS 471, FS 481 AS (A,S,M,E,P). NEW
 SHEETS SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE
 REVIEW.
  
 2. FP SHEETS ARE NOT DIGITALLY SIGNED AND SEALED. I
 HAVE AN ORIGINAL SIGNED AND SEALED SET WHICH CAN SERVE
 AS A "SIGNATURE DOCUMENT". PLEASE SEND A SUBMITTAL FORM
 VIA EMAIL.
  
 3. MEP DRAWINGS SIGNATURE/SEAL DO NOT STATE THAT THEY
 WERE SIGNED BY THE ENGINEER (STATES "SIGNED BY
 DOCUSIGN"). AS DISCUSSED, PLEASE RESOLVE WITH ISSUER
 AND PROVIDE SIGNED AND SEALED PAGES TO ACT AS SIGNATURE
 DOCUMENTS FOR THE ISSUED PERMIT AND FOR THIS REVISION.
  
 FBPE IS IN AGREEMENT THAT THE SEAL APPEARS TO BE
 INCORRECTLY ISSUED. IF YOU DISAGREE, PLEASE HAVE YOUR
 ISSUER CONTACT ME TO DISCUSS.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 17:56 Rev Time 0.00
Received By shill Date 2018-06-30 Time 17:56 Sent To  
Notes
2018-06-30 17:57:48SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES, S SHEETS) ARE
 IN ACCORDANCE WITH FS 471, FS 481 AS (A,S,M,E,P). NEW
 SHEETS SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE
 REVIEW.
  
 2. FP SHEETS ARE NOT DIGITALLY SIGNED AND SEALED. I
 HAVE AN ORIGINAL SIGNED AND SEALED SET WHICH CAN SERVE
 AS A "SIGNATURE DOCUMENT". PLEASE SEND A SUBMITTAL FORM
 VIA EMAIL.
  
 3. MEP DRAWINGS SIGNATURE/SEAL DO NOT STATE THAT THEY
 WERE SIGNED BY THE ENGINEER (STATES "SIGNED BY
 DOCUSIGN"). AS DISCUSSED, PLEASE RESOLVE WITH ISSUER
 AND PROVIDE SIGNED AND SEALED PAGES TO ACT AS SIGNATURE
 DOCUMENTS FOR THE ISSUED PERMIT AND FOR THIS REVISION.
  
 FBPE IS IN AGREEMENT THAT THE SEAL APPEARS TO BE
 INCORRECTLY ISSUED. IF YOU DISAGREE, PLEASE HAVE YOUR
 ISSUER CONTACT ME TO DISCUSS.
  
  
2018-06-26 17:57:39ELECTRICAL SIGNATURES GOOD. JP