Plan Review Details - Permit 18060448
Plan Review Stops For Permit 18060448
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-23 Cont ID  
Sent By jpearson Date 2018-07-23 Time 10:28 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 10:28 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-03 Cont ID  
Sent By jpearson Date 2018-07-03 Time 10:19 Rev Time 0.00
Received By jpearson Date 2018-07-03 Time 10:19 Sent To M
Notes
2018-07-03 10:19:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. THERE IS A SUBSTANTIAL AMOUNT OF WORK INCLUDED IN
 THIS REVISION, HOWEVER, THE REVISION APPLICATION STATES
 THAT THERE IS NO INCREASE IN VALUE OF WORK. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 (NOT
 PROVIDED)
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By jpearson Date 2018-06-13 Time 11:02 Rev Time 0.00
Received By jpearson Date 2018-06-13 Time 11:01 Sent To M
Notes
2018-06-13 11:01:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO HAVE ADDRESS OF PROJECT. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 2. PLAN IS REQUIRED TO BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. ONLY THE
 SIGNATURE IS PRESENT. PROVIDE PRINTED NAME ALSO. WPB
 FBC 107.2.1
 3. THERE ARE SEVERAL CHANGES TO THIS PLAN FROM THE
 ORIGINAL THAT ARE NOT CLOUDED ON PLAN. PLAN SHOULD
 INDICATE ALL REVISIONS. WPB FBC 107.2.1
 4. PLAN STATES THAT PANEL WILL BE TURNED IN TO THE
 LAUNDRY ROOM, BUT THE ROOM IN QUESTION IS THE STORAGE
 ROOM? IT APPEARS THAT THE PANEL WILL NOT HAVE THE
 CLEARANCE REQUIRED PER NEC 110.26. PROVIDE CORRECTION.
 5. LUTRON PANELS ARE SHOWN APPROXIMATELY 2 FEET FROM
 WATER HEATER. PROVIDE CORRECTION FOR REQUIRED CLEARANCE
 PER NEC 110.26
 6. PROVIDE ACCURATE LOAD CALCULATION. BOTH AIR
 CONDITIONERS ARE CALCULATED AT 4000 VA, BUT MECHANICAL
 PLAN SHOWS ONE AS 4014 VA, AND THE OTHER AS 7176 VA.
 TOTAL VA IS DIVIDED BY 240, BUT THIS IS A SINGLE PHASE
 208 VOLT PANEL, SO 208 SHOULD BE USED FOR CALCULATION.
 NEC 220, 110.4, 300.2
 7. BASED ON AN ACCURATE LOAD CALCULATION USING THE
 PROPER VOLTAGE, IT APPEARS THE PANEL AND FEEDERS WILL
 BE OVERLOADED. PROVIDE CORRECTION. NEC 310.15, 408.30,
 408.36
 8. PLAN SHOWS A RECEPTACLE FOR A TV IN THE SPA TUB
 AREA. THIS RECEPTACLE OUTLET IS NOT PERMITTED PER CODE.
 PROVIDE CORRECTION. NEC 406.9(C)
 9. THERE IS A SUBSTANTIAL AMOUNT OF WORK INCLUDED IN
 THIS REVISION, HOWEVER, THE REVISION APPLICATION STATES
 THAT THERE IS NO INCREASE IN VALUE OF WORK. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 10. ALL RECEPTACLES LOCATED IN BATHROOMS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 11. ALL KITCHEN COUNTER TOP RECEPTACLES REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 12. BREAKER FOR SPA TUB REQUIRES GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 680.43(A)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-18 Time 14:36 Sent To  
Notes
2018-07-19 14:36:43RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-07-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-29 Time 15:54 Sent To  
Notes
2018-07-02 15:54:53RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-11 Time 13:49 Sent To  
Notes
2018-06-12 13:50:15REVISION ROUTED TO JPEARSON

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-07-23 Cont ID  
Sent By ccole Date 2018-07-23 Time 12:38 Rev Time 0.00
Received By ccole Date 2018-07-23 Time 12:38 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-03 Cont ID  
Sent By ccole Date 2018-07-03 Time 16:10 Rev Time 0.00
Received By ccole Date 2018-07-03 Time 15:45 Sent To I
Notes
2018-07-03 16:26:281ST REVIEW FBC-2014 MECHANICAL
 REVISION #18060448
 MASTER PERMIT #17051281
 7/3/18
  
 CODES IN EFFECT:
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 3M DUCT WRAP APPLIED TO THE DRYER EXHAUST DUCT
 IS NOT AN ACCEPTABLE MEANS TO ALLOW THE DUCT TO RUN
 THROUGH THE RETURN PLENUM ABOVE THE CEILING. THE
 MANUFACTURER'S SPECIFICATIONS DO NOT PROVIDE AN
 INSTALLATION METHOD FOR WRAPPING DRYER EXHAUST DUCTS,
 AND THE INSTALLATION INSTRUCTIONS PROVIDED BY THE
 MANUFACTURER ALSO REQUIRE DRYWALL SCREWS TO ATTACH THE
 WRAP TO GREASE OR VENTILATION DUCTS. PLEASE NOTE THAT
 SCREW PENETRATIONS INTO THE EXHAUST DUCT ARE PROHIBITED
 PER SECTION 504.4, AND SCREWS FOR JOINING THE DUCT ARE
 LIMITED TO PNETRATIONS OF 1/8". PLEASE PROVIDE A PLENUM
 RATED ENCLOSURE USING NON COMBUSTIBLE OR PLENUM RATED
 MATERIALS SUCH AS STEEL STUDS AND DRYWALL- SECTION
 602.2..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By ccole Date 2018-06-14 Time 09:12 Rev Time 0.00
Received By ccole Date 2018-06-14 Time 09:12 Sent To I
Notes
2018-06-14 09:23:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060448
 6/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M-1: DRYER EXHAUST DUCTS SHALL NOT EXTEND INTO
 OR RUN THROUGH PLENUMS- SECTION 504.4 FBC M.
  
 2) COPIED ELECTRONIC SEALS AND SIGNATURES ARE NOT
 ACCEPTABLE FOR USE ON PAPER PLAN SUBMITTALS. ELECTRONIC
 SEALS AND SIGNATURES ARE ACCEPTABLE FOR USE ON DIGITAL
 PLAN SUBMITTALS ONLY- SECTION 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  