| 2018-06-13 11:01:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN IS REQUIRED TO HAVE ADDRESS OF PROJECT. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 2. PLAN IS REQUIRED TO BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. ONLY THE |
| | SIGNATURE IS PRESENT. PROVIDE PRINTED NAME ALSO. WPB |
| | FBC 107.2.1 |
| | 3. THERE ARE SEVERAL CHANGES TO THIS PLAN FROM THE |
| | ORIGINAL THAT ARE NOT CLOUDED ON PLAN. PLAN SHOULD |
| | INDICATE ALL REVISIONS. WPB FBC 107.2.1 |
| | 4. PLAN STATES THAT PANEL WILL BE TURNED IN TO THE |
| | LAUNDRY ROOM, BUT THE ROOM IN QUESTION IS THE STORAGE |
| | ROOM? IT APPEARS THAT THE PANEL WILL NOT HAVE THE |
| | CLEARANCE REQUIRED PER NEC 110.26. PROVIDE CORRECTION. |
| | 5. LUTRON PANELS ARE SHOWN APPROXIMATELY 2 FEET FROM |
| | WATER HEATER. PROVIDE CORRECTION FOR REQUIRED CLEARANCE |
| | PER NEC 110.26 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION. BOTH AIR |
| | CONDITIONERS ARE CALCULATED AT 4000 VA, BUT MECHANICAL |
| | PLAN SHOWS ONE AS 4014 VA, AND THE OTHER AS 7176 VA. |
| | TOTAL VA IS DIVIDED BY 240, BUT THIS IS A SINGLE PHASE |
| | 208 VOLT PANEL, SO 208 SHOULD BE USED FOR CALCULATION. |
| | NEC 220, 110.4, 300.2 |
| | 7. BASED ON AN ACCURATE LOAD CALCULATION USING THE |
| | PROPER VOLTAGE, IT APPEARS THE PANEL AND FEEDERS WILL |
| | BE OVERLOADED. PROVIDE CORRECTION. NEC 310.15, 408.30, |
| | 408.36 |
| | 8. PLAN SHOWS A RECEPTACLE FOR A TV IN THE SPA TUB |
| | AREA. THIS RECEPTACLE OUTLET IS NOT PERMITTED PER CODE. |
| | PROVIDE CORRECTION. NEC 406.9(C) |
| | 9. THERE IS A SUBSTANTIAL AMOUNT OF WORK INCLUDED IN |
| | THIS REVISION, HOWEVER, THE REVISION APPLICATION STATES |
| | THAT THERE IS NO INCREASE IN VALUE OF WORK. PROVIDE |
| | COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, |
| | TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| | 10. ALL RECEPTACLES LOCATED IN BATHROOMS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 11. ALL KITCHEN COUNTER TOP RECEPTACLES REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 12. BREAKER FOR SPA TUB REQUIRES GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 680.43(A)(3) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |