Plan Review Details - Permit 18060396
Plan Review Stops For Permit 18060396
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2018-06-18 Cont ID  
Sent By jleahy Date 2018-06-18 Time 09:25 Rev Time 0.00
Received By jleahy Date 2018-06-18 Time 09:27 Sent To  
Notes
2018-06-18 09:27:28FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL IS OK BUT THE GENERATOR PAD SUBMITTAL DOES
 NOT SHOW THIS MODEL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By jleahy Date 2018-07-30 Time 14:17 Rev Time 0.00
Received By jleahy Date 2018-07-30 Time 14:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By jleahy Date 2018-06-18 Time 09:27 Rev Time 0.00
Received By jleahy Date 2018-06-18 Time 08:16 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-07 Cont ID  
Sent By tklarge Date 2018-08-07 Time 06:28 Rev Time 0.00
Received By tklarge Date 2018-08-07 Time 06:28 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By tklarge Date 2018-07-27 Time 09:06 Rev Time 0.00
Received By tklarge Date 2018-07-27 Time 08:49 Sent To  
Notes
2018-07-27 09:10:121) CITY RECORDS SHOW A GAS GRILL ALSO CONNECTED TO THIS
 LINE. SHOW THE GAS GRILL ON THE PLAN AND SHOW THE BTU
 LOAD OF THE GRILL. THE BTU LOAD OF THE GAS GRILL SHALL
 BE INCLUDED IN THE TOTAL BTU LOAD ON THIS LINE.
 2) THE LONGEST RUN SHOWN ON THE EXISTING GAS DRAWING IS
 60 FEET TO THE GAS GRILL. THIS DISTANCE SHALL BE USED
 IN THE SIZING OF THIS GAS SYSTEM. 2017 FBC-FUEL GAS
 SEC. 402.4.1.
 3) USING THE 60 FEET DISTANCE COLUMN, THE 1/2 INCH
 GALVANIZED LINE TO THE GENERATOR IS UNDERSIZED PER GAS
 SIZING TABLE 402.4 (4). THE MINIMUM SIZE SHALL BE 3/4
 INCH.
 4) THE 1 INCH PE LINE IS UNDERSIZED FOR A 60 FEET
 DISTANCE AND BTU LOAD PER TABLE 402.4 (21) OF THE 2017
 FBC-FUEL GAS.
  
 NOTE: I HAVE A PLACED A COPY OF THE GAS DRAWING FROM
 CITY RECORDS IN THE PERMIT APPLICATION FILE FOR YOUR
 REVIEW AND REFERENCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By tklarge Date 2018-06-20 Time 12:28 Rev Time 0.00
Received By tklarge Date 2018-06-20 Time 11:25 Sent To I
Notes
2018-06-20 12:16:541) CITY RECORDS SHOW PREVIOUS GAS PERMITS SHOWING AN
 EXISTING GAS STOVE,DRYER AND GAS GRILL WITH A TOTAL
 DEVELOPED LENGTH OF 60 FT. TO THE MOST REMOTE FIXTURE.
 THIS DISTANCE SHALL BE USED IN THE SIZING OF THIS
 SYSTEM.2017 FBC-FUEL GAS SEC.401.3.
 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 3) SUBMIT A LEGIBLE GAS DRAWING WITH LEGIBLE NOTES ON
 IT.
 4) THE GAS SIZING TABLES THAT HAVE BEEN SUBMITTED ARE
 NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT COPIES FROM
 THE CURRENT CODE AND THIS INFO SHALL BE ON THE TABLES.
 WPB AMEND. FBC SEC. 107.2.1.
 5) THE SIZING TABLES SUBMITTED ARE PARTIALLY ILLEGIBLE
 DUE TO BEING ENLARGED. SUBMIT TWO COPIES OF LEGIBLE
 TABLES. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THERE IS AN 8 1/2 X 11 COPY OF A SURVEY WITH NOTES
 THAT ARE ILLEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES
 FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 7) THE LOCATION OF THE GENERATOR SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL. 2017 FBC-FUEL GAS
 SEC.616.1.
 8) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH
 NFPA 37.
 NFPA 37
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-07 Cont ID  
Sent By tklarge Date 2018-08-07 Time 06:29 Rev Time 0.00
Received By tklarge Date 2018-08-07 Time 05:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By jleahy Date 2018-07-30 Time 14:17 Rev Time 0.00
Received By jleahy Date 2018-07-19 Time 15:27 Sent To  
Notes
2018-07-20 15:27:40RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By tklarge Date 2018-06-20 Time 12:28 Rev Time 0.00
Received By tklarge Date 2018-06-08 Time 11:27 Sent To  
Notes
2018-06-11 11:27:47ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-08-07 Cont ID  
Sent By tklarge Date 2018-08-07 Time 06:27 Rev Time 0.00
Received By tklarge Date 2018-08-07 Time 05:52 Sent To  
Notes
2018-08-07 06:28:28"P" STOP ENTERED BY MISTAKE. TKL.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-12 Cont ID  
Sent By mcruz Date 2018-06-12 Time 14:53 Rev Time 0.00
Received By mcruz Date 2018-06-12 Time 14:49 Sent To B
Notes
2018-06-12 14:53:55PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST 1'
 FROM SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]