Plan Review Details - Permit 18060362
Plan Review Stops For Permit 18060362
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By skennedy Date 2018-08-20 Time 09:36 Rev Time 0.00
Received By skennedy Date 2018-08-20 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 07:30 Sent To I
Notes
2018-07-10 07:39:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 1) COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADDRESSED.
 NO PLANS FOR THE GENERATOR PAD WERE SUBMITTED WITH THE
 REQUESTED INFORMATION. SEE COMMENTS BELOW.
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL PLAN.
 SPECIFY THE METHOD OF CRACK CONTROL THAT WILL BE USED (
 FIBERMESH CONCRETE OR 6X6 W1.4X1.4 WELDED WIRE MESH).
 FBC-R506.2.4.2
  
 2) SPECIFY THE TYPE, LOCATIONS AND NUMBER OF ANCHORS
 AND THE REQUIRED EMBED DEPTHS OF THE ANCHORS ON THE
 DRAWINGS. FBC 107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) N/A

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By rmcdouga Date 2018-06-28 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2018-06-28 Time 16:31 Sent To I
Notes
2018-06-28 16:45:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A GENERATOR PAD DETAIL PLAN. SPECIFY THE
 METHOD OF CRACK CONTROL THAT WILL BE USED ( FIBERMESH
 CONCRETE OR 6X6 W1.4X1.4 WELDED WIRE MESH).
 FBC-R506.2.4.2
  
 2) SPECIFY THE TYPE, LOCATIONS AND NUMBER OF ANCHORS
 AND THE REQUIRED EMBED DEPTHS OF THE ANCHORS ON THE
 DRAWINGS. FBC 107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) PROVIDE THE GENERATOR MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS THAT SHOW THE REQUIRED
 GENERATOR PAD DIMENSIONS. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-09 Cont ID  
Sent By jpearson Date 2018-07-09 Time 17:12 Rev Time 0.00
Received By jpearson Date 2018-07-09 Time 17:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-15 Cont ID  
Sent By jpearson Date 2018-06-15 Time 14:35 Rev Time 0.00
Received By jpearson Date 2018-06-15 Time 14:35 Sent To  
Notes
2018-06-15 14:35:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW WHAT THE MANUAL
 TRANSFER SWITCH IS FEEDING. IT APPEARS THAT THE
 TRANSFER SWITCH IS BACK FEEDING THE MAIN PANEL, WHICH
 IS NOT PERMITTED PER CODE. WILL THERE BE A SUB-PANEL
 INSTALLED AND CIRCUITS FOR GENERATOR RELOCATED TO THIS
 PANEL? PROVIDE CLARIFICATION. WPB FBC 107.2.1; NEC
 702.5
 2. LOAD CALCULATION PROVIDED IS NOT A LOAD CALCULATION
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION FOR ITEMS
 THAT WILL BE ON GENERATOR WITH A DESCRIPTION OF THE
 CIRCUITS INVOLVED AND HOW THEY WILL BE FED FROM
 GENERATOR. SEE FBC RESIDENTIAL E3602.2 FOR AN EXAMPLE
 OF WHAT THE LOAD CALCULATION SHOULD INCLUDE. NEC 220,
 702.4(B); FBC RE E3602.2
 3. WHAT IS THE RATING OF THE MANUAL TRANSFER SWITCH?
 PROVIDE SPEC SHEET. NEC 110.3; WPB FBC 107.2.1
 4. EACH PAGE OF ELECTRICAL PLAN IS REQUIRED TO BE
 SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. FS 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 5. PERMIT APPLICATION STATES THIS IS A PORTABLE
 GENERATOR. PROVIDE DETAIL OF HOW THE WIRING FROM THE
 PORTABLE GENERATOR WILL BE CONNECTED TO THE 60 AMP
 DISCONNECT SHOWN. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By jleahy Date 2018-06-14 Time 15:35 Rev Time 0.00
Received By jleahy Date 2018-06-14 Time 15:35 Sent To  
Notes
2018-06-14 15:40:36FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS.THAT WILL BE ON THE GENERATOR NEC 220; FBC RE E
 E3602.2
  
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. FS 481.229; FBC.3.5
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 FBC 107.2.1

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-26 Cont ID  
Sent By tklarge Date 2018-06-26 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-06-26 Time 06:24 Sent To  
Notes
2018-06-26 06:25:01A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-06 Time 14:10 Sent To  
Notes
2018-07-09 14:10:46RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By rmcdouga Date 2018-06-28 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2018-06-08 Time 10:21 Sent To  
Notes
2018-06-11 10:21:15ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-12 Cont ID  
Sent By mcruz Date 2018-06-12 Time 14:07 Rev Time 0.00
Received By mcruz Date 2018-06-12 Time 13:55 Sent To B
Notes
2018-06-12 14:07:12PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST 4'
 FROM REAR PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  