Plan Review Details - Permit 18060357
Plan Review Stops For Permit 18060357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-13 Cont ID  
Sent By shill Date 2018-07-13 Time 05:55 Rev Time 0.00
Received By shill Date 2018-07-13 Time 05:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By aclange Date 2018-06-16 Time 17:31 Rev Time 0.00
Received By shill Date 2018-06-16 Time 17:31 Sent To  
Notes
2018-06-16 17:33:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE DOOR TO THE AREA BETWEEN ROOMS 111 AND 109 LACKS
 THE 18" MANEUVERING CLEARANCE REQUIRED BY FBC A FIGURE
 404.2.4.1(A).
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-21 Cont ID  
Sent By jpearson Date 2018-06-21 Time 16:31 Rev Time 0.00
Received By jpearson Date 2018-06-21 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-29 Cont ID  
Sent By pleduc Date 2018-06-29 Time   Rev Time 0.00
Received By pleduc Date 2018-06-29 Time 12:55 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-13 Cont ID  
Sent By shill Date 2018-07-13 Time 05:55 Rev Time 0.00
Received By shill Date 2018-07-02 Time 14:46 Sent To  
Notes
2018-07-03 14:46:26RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-02 Cont ID  
Sent By lmarchan Date 2018-07-02 Time 10:01 Rev Time 0.00
Received By lmarchan Date 2018-06-08 Time 12:48 Sent To  
Notes
2018-06-11 12:48:12B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-09 Cont ID  
Sent By ccole Date 2018-07-09 Time 11:18 Rev Time 0.00
Received By ccole Date 2018-07-09 Time 11:18 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By ccole Date 2018-06-12 Time 11:49 Rev Time 0.00
Received By ccole Date 2018-06-12 Time 11:21 Sent To  
Notes
2018-06-12 11:52:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18060357
 MASTER #17110531
 6/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2014
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD SHALL PROVIDE A RAISED OR INK
 SEAL AND SIGNATURE ON THE PLANS. ELECTRONIC SEALS AND
 SIGNATURES ARE FOR USE ON ELECTRONIC PLANS AND
 DOCUMENTS, COPIED ELECTRONIC SEALS ARE NOT PERMITTED
 PER SECTION 61G15-23.005 FAC.
  
 2) SHOW THE LOCATIONS OF ACCESS PANELS FOR VAV'S 3-2,
 3-3, 3-5, & 3-6 IF THESE UNITS ARE ABOVE HARD CEILINGS-
 SECTION 306.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-14 Cont ID  
Sent By gjohnson Date 2018-06-14 Time 10:09 Rev Time 0.00
Received By gjohnson Date 2018-06-14 Time 10:09 Sent To  
Notes
***NONE***