Plan Review Details - Permit 18060327
Plan Review Stops For Permit 18060327
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By shill Date 2018-08-01 Time 08:47 Rev Time 0.00
Received By dbattles Date 2018-08-01 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-03 Cont ID  
Sent By skennedy Date 2018-07-03 Time 09:00 Rev Time 0.00
Received By shill Date 2018-07-03 Time 08:59 Sent To  
Notes
2018-07-03 09:19:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE DATUM ON THE PLAN IS INCORRECT (NGVD29); THIS
 SHOULD BE IN THE SAME DATUM AS THE FLOOD INSURANCE RATE
 MAPS (NAVD88). EITHER CHANGE OR ADD NAVD88 DATUM.
  
 THE DFE SHOULD BE 9' NAVD88.
  
 2. PROVIDE A "CONSTRUCTION DRAWING" ELEVATION
 CERTIFICATE, FBC 107.3.5.3(9). THIS WAS REQUESTED IN
 PLAN REVIEW TWICE BUT NOT PROVIDED; THE "FINISHED
 CONSTRUCTION" ELEVATION CERTIFICATE FOR THE DEMOLISHED
 HOUSE WAS PROVIDED. PLEASE PROVIDE AT THIS TIME. THIS
 SHOULD INCLUDE THE PROPOSED ELEVATIONS AND SHOULD
 CORRELATE WITH THE CONSTRUCTION DRAWINGS.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By skennedy Date 2018-06-26 Time 14:31 Rev Time 0.00
Received By jpearson Date 2018-06-26 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-03 Cont ID  
Sent By cpuell Date 2018-08-03 Time 11:42 Rev Time 0.00
Received By cpuell Date 2018-07-26 Time 11:33 Sent To  
Notes
2018-07-27 11:34:05R30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-07 Time 14:56 Sent To  
Notes
2018-06-08 14:56:56R01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By ccole Date 2018-08-01 Time 09:55 Rev Time 0.00
Received By ccole Date 2018-08-01 Time 09:44 Sent To B
Notes
2018-08-01 10:13:20MECHANICAL PROVISO:
  
 COMPLETE SIGNED AND SEALED ENGINEERING FOR INSTALLATON
 OF THE CONDENSER RACK AND CONDENSETRS SHALL BE ONSITE
 AT TIME OF INSPECTION.
  
 CCOLE- 8/1/18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-11 Cont ID  
Sent By skennedy Date 2018-07-11 Time 11:41 Rev Time 0.00
Received By ccole Date 2018-07-11 Time 07:45 Sent To I
Notes
2018-07-11 11:53:371ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 REVISION #18060327
 MASTER #17100298
 7/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE REMOVE THE PAD MOUNTED CONDENSER
 DETAIL AND REPLACE IT WITH A WALL MOUNTED CONDENSER
 BACKET DETAIL WITH COMPLETE ANCHORING AND FASTENING
 DETAILS. SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE BRACKET WITH APPROVAL STAMP BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 2) M-1: THE PLAN INDICATES FLEX EXHAUST DUCTS ARE TO BE
 INSTALLED FOR THE BATH AND KITCHEN EXHAUST SYSTEMS.
 PLEASE INDICATE THE TYPE OF FLEX DUCTS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN EXHAUST
 HOOD AND EXHAUST DUCT.
  
 3) SUBMIT A REVISED 2ND FLOOR AC PLAN (APPLICABLE ONLY
 IF CHANGES WERE MADE).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-25 Cont ID  
Sent By skennedy Date 2018-06-25 Time 17:25 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 15:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-02 Cont ID  
Sent By awooten Date 2018-08-02 Time   Rev Time 0.00
Received By awooten Date 2018-08-02 Time   Sent To  
Notes
2018-08-02 15:28:16**********************************VERIFIED THAT THERE
 WAS A CONDITIONAL LANDSCAPE APPROVAL SUBMITTED AND
 APPROVED UNDER MASTER PERMIT 17100298 AND THERE IS A
 LANDSCAPING
 PROVISO.*****************************************
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-09 Cont ID  
Sent By awooten Date 2018-07-09 Time 15:40 Rev Time 0.00
Received By awooten Date 2018-07-09 Time 15:23 Sent To M
Notes
2018-07-09 15:40:44*********************************ZONING REVIEW
 FAILED******************************
  
 PROVIDE A SURVEY AND SITE PLAN.
  
 POOL, DRIVEWAY AND FENCES REQUIRE A SEPARATE PERMIT.
  
 PROVIDE SETBACKS FOR MECHANICAL EQUIPMENT. DIMENSION
 THE SETBACKS FOR ALL MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK. WINDOW AIR-CONDITIONING
 UNITS MAY NOT PROJECT MORE THAN 18 INCHES INTO A
 REQUIRED SIDE SETBACK.
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK. PROVIDE THE
 DIMENSIONS OF THE BALCONY OVERHANGS.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  