| Plan Review Stops For Permit 18060327 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-01 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-01 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-03 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-03 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-03 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2018-07-03 09:19:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE DATUM ON THE PLAN IS INCORRECT (NGVD29); THIS | | | SHOULD BE IN THE SAME DATUM AS THE FLOOD INSURANCE RATE | | | MAPS (NAVD88). EITHER CHANGE OR ADD NAVD88 DATUM. | | | | | | THE DFE SHOULD BE 9' NAVD88. | | | | | | 2. PROVIDE A "CONSTRUCTION DRAWING" ELEVATION | | | CERTIFICATE, FBC 107.3.5.3(9). THIS WAS REQUESTED IN | | | PLAN REVIEW TWICE BUT NOT PROVIDED; THE "FINISHED | | | CONSTRUCTION" ELEVATION CERTIFICATE FOR THE DEMOLISHED | | | HOUSE WAS PROVIDED. PLEASE PROVIDE AT THIS TIME. THIS | | | SHOULD INCLUDE THE PROPOSED ELEVATIONS AND SHOULD | | | CORRELATE WITH THE CONSTRUCTION DRAWINGS. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-06-26 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-06-26 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-26 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-08-03 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-07-26 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-07-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-07 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-01 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-01 |
Time |
09:44 |
Sent To |
B |
|
| Notes |
| 2018-08-01 10:13:20 | MECHANICAL PROVISO: | | | | | | COMPLETE SIGNED AND SEALED ENGINEERING FOR INSTALLATON | | | OF THE CONDENSER RACK AND CONDENSETRS SHALL BE ONSITE | | | AT TIME OF INSPECTION. | | | | | | CCOLE- 8/1/18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-11 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-11 |
Time |
07:45 |
Sent To |
I |
|
| Notes |
| 2018-07-11 11:53:37 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | REVISION #18060327 | | | MASTER #17100298 | | | 7/11/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: PLEASE REMOVE THE PAD MOUNTED CONDENSER | | | DETAIL AND REPLACE IT WITH A WALL MOUNTED CONDENSER | | | BACKET DETAIL WITH COMPLETE ANCHORING AND FASTENING | | | DETAILS. SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE | | | NOA FOR THE BRACKET WITH APPROVAL STAMP BY THE DESIGN | | | PROFESSIONAL OF RECORD. | | | | | | 2) M-1: THE PLAN INDICATES FLEX EXHAUST DUCTS ARE TO BE | | | INSTALLED FOR THE BATH AND KITCHEN EXHAUST SYSTEMS. | | | PLEASE INDICATE THE TYPE OF FLEX DUCTS AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN EXHAUST | | | HOOD AND EXHAUST DUCT. | | | | | | 3) SUBMIT A REVISED 2ND FLOOR AC PLAN (APPLICABLE ONLY | | | IF CHANGES WERE MADE). | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-06-25 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-25 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-02 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-08-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-08-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-08-02 15:28:16 | **********************************VERIFIED THAT THERE | | | WAS A CONDITIONAL LANDSCAPE APPROVAL SUBMITTED AND | | | APPROVED UNDER MASTER PERMIT 17100298 AND THERE IS A | | | LANDSCAPING | | | PROVISO.***************************************** | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-09 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-07-09 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-07-09 |
Time |
15:23 |
Sent To |
M |
|
| Notes |
| 2018-07-09 15:40:44 | *********************************ZONING REVIEW | | | FAILED****************************** | | | | | | PROVIDE A SURVEY AND SITE PLAN. | | | | | | POOL, DRIVEWAY AND FENCES REQUIRE A SEPARATE PERMIT. | | | | | | PROVIDE SETBACKS FOR MECHANICAL EQUIPMENT. DIMENSION | | | THE SETBACKS FOR ALL MECHANICAL EQUIPMENT. MECHANICAL | | | EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. WINDOW AIR-CONDITIONING | | | UNITS MAY NOT PROJECT MORE THAN 18 INCHES INTO A | | | REQUIRED SIDE SETBACK. | | | STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING | | | BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES, | | | AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER | | | THAN THREE FEET INTO ANY SETBACK. PROVIDE THE | | | DIMENSIONS OF THE BALCONY OVERHANGS. | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | GROSS LOT SQUARE FOOTAGE MINUS | | | BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | |
|
|