Plan Review Details - Permit 18060316
| Plan Review Stops For Permit 18060316 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-08-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-02 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-02 |
Time |
17:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-26 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-01 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2018-08-01 17:20:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FS471, THE PLANS SUBMITTED ARE NOT SIGNED, SEALED, | | | DATED ORIGINALS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-30 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-30 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-08-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-08-02 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-08-02 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2018-08-02 16:18:34 | PROVISO!!!! | | | | | | NEED TO SUBMIT NEW PLANS SHOWING COMPLIANCE WITH THE | | | ELECTRICAL PLAN REVIEW DATED 7/26/18 BEFORE FINAL. | | | | | | JAKE LEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-26 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-26 |
Time |
13:10 |
Sent To |
B |
|
| Notes |
| 2018-07-26 13:10:23 | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH | | | CODE. NEC 210.8, 215.5, 408.4 | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30 | | | 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE | | | INCLUDING ALL LOADS. NEC 220 | | | 4. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS. | | | NEC 110.3, 110.9 | | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 7. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER | | | CODE. NEC 210.64 | | | 8. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. PLANS SUBMITTED SHOULD MEET THIS | | | REQUIREMENT AND NEED TO BE LEGIBLE. WPB FBC 107.2.1.3, | | | 107.1 | | | | | | NEW COMMENT | | | | | | 9. PLAN IS REQUIRED TO BE SIGNED/SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. WPB FBC 107.1; FS 481 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-12 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-12 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2018-07-12 13:43:06 | BE ADVISED THAT A COURTESY REVIEW HAS BEEN PERFORMED | | | WITH THE DIGITAL PLANS THAT WERE EMAILED TO ME. | | | CORRECTIONS FOR COMMENTS BELOW SHOULD BE SUBMITTED WITH | | | PLANS THAT ARE DRAWN TO SCALE AND LEGIBLE, | | | SIGNED/SEALED BY THE DESIGN PROFESSIONAL RESPONSIBLE | | | FOR THE DESIGN. WPB FBC 107.1 | | | SEE BELOW FOR REVIEW: | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH | | | CODE. NEC 210.8, 215.5, 408.4 | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30 | | | 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE | | | INCLUDING ALL LOADS. NEC 220 | | | 4. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS. | | | NEC 110.3, 110.9 | | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 7. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER | | | CODE. NEC 210.64 | | | 8. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. PLANS SUBMITTED SHOULD MEET THIS | | | REQUIREMENT AND NEED TO BE LEGIBLE. WPB FBC 107.2.1.3, | | | 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-29 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-29 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2018-06-29 13:55:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW PER THE | | | FOLLOWING: QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. WPB FBC 107.2.1.3 | | | | | | A COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO | | | THE SUBMISSION OF PLANS NOT COMPLIANT WITH THE ABOVE. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2018-07-09 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2018-07-09 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2018-07-09 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-01 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-12 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-07-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-06-07 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
Hansen |
Date |
2018-07-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
ahansen |
Date |
2018-07-19 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
| Sent By |
ahansen |
Date |
2018-06-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
ahansen |
Date |
2018-06-15 |
Time |
10:17 |
Sent To |
I |
|
| Notes |
| 2018-06-15 10:21:18 | - THE ADDRESS AND PCN INCLUDED IN THE PERMIT | | | APPLICATION DO NOT CORRESPOND TO THE LOCATION OF THE | | | PROJECT. | | | - SINCE THERE IS A LANDSCAPING COMPONENT TO THIS | | | PROJECT, A SEPARATE LANDSCAPE PERMIT IS REQUIRED | | | - SINCE THERE IS A FENCE INCLUDED IN THIS PROJECT, A | | | SEPARATE BUILDING PERMIT FOR THE FENCE IS REQUIRED. | | | | | | ALEX HANSEN, CITY COMPREHENSIVE PLANNER (561-822-463) |
|
|
|