Plan Review Details - Permit 18060242
Plan Review Stops For Permit 18060242
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By rmcdouga Date 2018-08-15 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2018-08-15 Time 07:20 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 07:21 Sent To I
Notes
2018-07-25 07:34:51PENDING PLUMBING APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-25 Cont ID  
Sent By rmcdouga Date 2018-06-25 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2018-06-25 Time 18:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By jleahy Date 2018-08-10 Time 07:41 Rev Time 0.00
Received By jleahy Date 2018-08-10 Time 07:40 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-12 Cont ID  
Sent By jleahy Date 2018-06-12 Time 14:29 Rev Time 0.00
Received By jleahy Date 2018-06-12 Time 14:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By tklarge Date 2018-06-25 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-06-25 Time 06:22 Sent To  
Notes
2018-06-25 06:24:50THERE IS NO GAS ASSOCIATED WITH THIS POOL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-15 Cont ID  
Sent By tklarge Date 2018-08-15 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2018-08-06 Time 13:52 Sent To  
Notes
2018-08-07 13:53:04RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2018-07-11 Time 15:00 Sent To  
Notes
2018-07-12 15:00:28RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By rmcdouga Date 2018-06-25 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2018-06-06 Time 10:16 Sent To  
Notes
2018-06-07 10:16:53ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-08 Cont ID  
Sent By tklarge Date 2018-08-08 Time 12:00 Rev Time 0.00
Received By tklarge Date 2018-08-08 Time 11:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 06:01 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 05:28 Sent To  
Notes
2018-07-25 05:57:401) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM CCOMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES,
 HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS.CLARIFY.
 2) INDICATE ON THE PUMP CURVE WHICH KEY CURVE IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SUBMIT TWO COPIES OF AN ENLARGED POOL PUMP CURVE.
 THE PRINTING IS ILLEGIBLE ON THE ONE ON THE PLANS.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS.2ND REQUEST.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By tklarge Date 2018-06-25 Time 08:30 Rev Time 0.00
Received By tklarge Date 2018-06-25 Time 06:19 Sent To  
Notes
2018-06-25 06:58:441) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN COVER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) INDICATE ON THE PUMP CURVE WHICH KEY CURVE IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) GENERAL NOTES PAGE - NOTE #8 - THE INFORMATION IN
 THIS NOTE IS FROM THE 2006 EDITION OF APSP 7. THE 2013
 EDITION IS IN EFFECT FOR THIS POOL. EITHER REVISE THE
 NOTE TO REFLECT THE CURRENT LANGUAGE IN APSP 7 SEC.
 4.4.9 OR DELETE THE NOTE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By mcruz Date 2018-06-08 Time 15:31 Rev Time 0.00
Received By mcruz Date 2018-06-08 Time 15:26 Sent To B
Notes
2018-06-08 15:31:24NOTE - POOL EQUIPMENT SHALL BE AT LEAST 6 FEET FROM
 SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]