Plan Review Details - Permit 18060195
Plan Review Stops For Permit 18060195
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By rmcdouga Date 2018-07-05 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2018-07-05 Time 13:28 Sent To I
Notes
2018-07-05 13:30:56FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By rmcdouga Date 2018-06-26 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2018-06-26 Time 14:32 Sent To I
Notes
2018-06-26 14:58:21FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By rmcdouga Date 2018-07-05 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2018-07-05 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By rmcdouga Date 2018-06-26 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2018-06-26 Time 15:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-26 Cont ID  
Sent By tklarge Date 2018-06-26 Time 05:45 Rev Time 0.00
Received By tklarge Date 2018-06-26 Time 05:40 Sent To  
Notes
2018-06-26 05:45:39THERE IS NO GAS ASSOCIATED WITH THIS POOL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-05 Cont ID  
Sent By rmcdouga Date 2018-07-05 Time 13:45 Rev Time 0.00
Received By rmcdouga Date 2018-06-29 Time 15:29 Sent To  
Notes
2018-07-02 15:29:52RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-26 Cont ID  
Sent By rmcdouga Date 2018-06-26 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2018-06-06 Time 10:31 Sent To  
Notes
2018-06-07 10:31:18ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By tklarge Date 2018-07-03 Time 13:24 Rev Time 0.00
Received By tklarge Date 2018-07-03 Time 06:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By tklarge Date 2018-06-26 Time 05:47 Rev Time 0.00
Received By tklarge Date 2018-06-26 Time 05:40 Sent To  
Notes
2018-06-26 05:47:481) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SUBMIT TWO COPIES OF THE POOL PUMP CURVE. IDENTIFY
 ON THE PUMP CURVE THE SPECIFIC CURVE KEY THAT APPLIES
 TO THIS PUMP.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By mcruz Date 2018-06-08 Time 15:42 Rev Time 0.00
Received By mcruz Date 2018-06-08 Time 15:38 Sent To B
Notes
2018-06-08 15:42:55NOTE - POOL EQUIPMENT SHALL BE AT LEAST 6' FROM REAR
 PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]