| Plan Review Stops For Permit 18060139 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-26 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-25 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-22 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-22 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2018-06-22 14:02:47 | 1) THE SHUTOFF VALVE FOR THE INTERIOR PIPING SHALL BE | | | LOCATED UPSTREAM OF THE PRESSURE REGULATOR PER 2017 | | | FBC-FUEL GAS SEC.409.4. | | | 2) THE PIPE AT THE TEE FOR THE POOL HEATER IS SHOWN AS | | | RIDGID GALVANIZED AND ALSO AS PE. CLARIFY. | | | 3) INDICATE ON THE GAS PLANS WHICH SIZING TABLE IS | | | BEING USED FOR THE LOW PRESSURE SCH. 40 METALLIC PIPE. | | | 4) GAS PLANS ON FILE WITH THE CITY SHOW AN 1 1/4 INCH | | | GALVANIZED LINE AT THE GAS METER OUTLET AND THE | | | SUBMITTED PLANS SHOW AN EXISTING 3/4 INCH LINE. | | | CLARIFY. | | | 5) PLANS ON FILE WITH THE CITY SHOW A BTU LOAD OF | | | 378,000 AND THE SUBMITTED PLANS SHOW AN EXISTING BTU | | | LOAD OF 525,000. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-26 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-26 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-22 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-22 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
|