Plan Review Details - Permit 18060100
Plan Review Stops For Permit 18060100
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-10-02 Cont ID  
Sent By pvalenti Date 2018-10-02 Time 10:15 Rev Time 0.00
Received By pvalenti Date 2018-10-02 Time 10:15 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 07:36 Rev Time 0.00
Received By shill Date 2018-07-05 Time 07:36 Sent To  
Notes
2018-07-05 07:38:48FOR ADDRESSING, PLEASE CONTAC (PREFERABLY VIA EMAIL)T:
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-24 Cont ID  
Sent By pvalenti Date 2018-09-24 Time 14:08 Rev Time 0.00
Received By pvalenti Date   Time   Sent To I
Notes
2018-09-24 15:00:07 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 UPDATED CORRECTION ITEMS FROM LAST REVIEW:
  
 1. ALREADY APPROVED.
 2. ALREADY APPROVED.
 3. APPROVED. PV. SEE MECHANICAL COMMENTS.
 4. APPROVED. PV. THE ENERGY (EPL) CARD WAS SUBMITTED,
 SEE MECHANICAL COMMENTS.
 5. - 17. ALREADY APPROVED.
 18. APPROVED AS NOTED. PV. THE WINDOW SCHEDULE SHOWS
 THE WINDOWS LABELED "A" TO BE AT A HEIGHT OF 96",
 EXCEEDING THE N.O.A. MAX. HEIGHT OF 76". THE IMAGES OF
 THESE WINDOWS ON PAGES A.4 & A.5 APPEAR TO SHOW A
 DIFFERENT TYPE OF OPENING THAN SINGLE HUNG. THE
 ARCHITECT APPROVED FOR S.G.D.
 19. APPROVED AS NOTED. PV. BE SURE THAT PRIVACY WALL
 FOOTING WILL STAY WITH IN THE PROPERTY LINE, ALSO, THE
 4' HEIGHT OF PRIVACY WALL MUST BE MAINTAINED UP TO 25'
 FROM FRONT PROPERTY LINE.
 20. APPROVED FOR WOOD DECK. PV.
  
 APPROVED PV
  
 NOTES: 1. PROVIDE CORRECT N.O.A. FOR "A" WINDOWS SHOWN
 ON WINDOW SCHEDULE PRIOR TO FIRST INSPECTION.
 2. ALL WORK SUBJECT TO CITY CODES IS SUBJECT TO FIELD
 INSPECTOR'S APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By dbattles Date 2018-08-22 Time 13:11 Rev Time 0.00
Received By dbattles Date 2018-08-22 Time 13:11 Sent To  
Notes
2018-08-22 13:08:481. OK.
  
 2. OK.
  
 3. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 UPDATE PLANS TO SHOW INSULATION VALUES FROM THE ENERGY
 CALCULATIONS.
 3-2. NOT PROVIDED
  
 4. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
 4-2. NOT PROVIDED
  
 5-17 OK.
  
 18. [FBC 107.2.1]N.O.A. FOR WINDOW ONLY COVERS WINDOWS
 UP TO 76" IN HEIGHT (TABLE 1&2). PLEASE PROVIDE N.O.A.
 FOR WINDOWS OVER 76" TALL.
 18-2. NO NEW PRODUCT APPROVAL PROVIDED.
  
 NEW COMMENT:
 19. VERIFY THAT THE FOOTER FOR THE SITE WALL WILL NEED
 TO BE WITHIN PROPERTY LINES.
 IF THE WALL IS TO EXTEND TO THE PROPERTY LINE PROVIDE
 DETAIL TO SHOW ECCENTRIC FOOTER TO KEEP THE FOOTER
 WITHIN PROPERTY LINES, WHILE ALLOWING WALL TO EXTEND TO
 PROPERTY LINE.
  
 20. ROOFING WAS APPROVED, BUT A NEW PRODUCT APPROVAL
 WAS SUBMITTED FOR SYSTEM OVER CONCRETE DECK.
 PLEASE VERIFY THAT THIS DOESN'T APPLY TO THIS PROJECT.
 I BELIEVE ALL ROOF DECK IS TO BE OVER PLYWOOD
 SHEATHING.
  
 18060108(DECK):
 1. OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 09:55 Rev Time 0.00
Received By shill Date 2018-07-05 Time 07:40 Sent To  
Notes
2018-07-05 09:55:11****CORRECTIONS****
 W.P.B. PERMIT: 18060100(HOUSE) AND 18060108(DECK)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC R = FBC RESIDENTIAL
  
 18060100(HOUSE):
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
 1. [FBC R107.2.5]PROVIDE ABSTRACTED SURVEY OF PROPERTY
 TO SHOW WHAT THE BUILD LINE ON SOUTH SIDE OF PROPERTY
 IS. IF THERE IS AN ULTIMATE RIGHT OF WAY THAN ADJUST
 BUILDING TO NOT ENCROACH THAT LINE.
  
 2. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN TO COMPLY
 WITH R401.3.
 SHOW LOWEST FLOOR ELEVATION (NAVD88) AND SHOW GRADE 4"
 BELOW FINISHED FLOOR SLAB FOR STARTING DRAINAGE SLOPES
 [FBC R404.1.6]. USE ELEVATION NUMBERS TO SHOW HOW
 DRAINAGE WORKS. AT WEST SIDE IF YOU CAN'T MAKE PITCH
 REQUIRMENTS, SHOW HOW WATER CAN BE HANDLED ON-SITE
 (PITCH FLAT ROOF TO EAST ONLY, GUTTERS AND UNDERGROUND
 DRAINS CAN BE UTILIZED).
  
 3. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 UPDATE PLANS TO SHOW INSULATION VALUES FROM THE ENERGY
 CALCULATIONS.
  
 4. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
  
 5. [FBC R305]PROVIDE CEILING HEIGHTS FOR ALL ROOMS.
  
 6. [FBC R305]SHEET A.6 TYPICAL WALL SECTION SHOWS
 CEILING HGT. 10'(VERIFY). SHOULD THIS BE 12'(VERIFY)?
 ALSO, SHOW TYPICAL CONNECTION AT FLOOR AND CEILING FOR
 PARTITION WALLS.
  
  
 7. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW OVERHANG WORKS
 ON THE NORTH & SOUTH ROOF, OR RESPOND THAT IT WILL BE
 SUBMITTED WITH TRUSS PACKAGE.
  
 8. [FBC R802.10]THE NOTE ON TOP OF DRAWING SHEET A.8
 STATES THAT TRUSSES ARE SPACED 16" C/C AND THE NOTES TO
 THE RIGHT STATE THEY ARE 24" C/C.
 PLEASE COORDINATE NOTES TO MATCH.
 ALSO, STATE CONNECTOR USED FOR EACH TRUSS AND SHOW X
 BRACING IF APPLICABLE.
  
 9. [FBC R608.8]IF LINTELS ARE BEING USED ABOVE WINDOWS
 AND DOORS, PROVIDE LINTEL SCHEDULE TO SHOW BEARING.
 PROVIDE LINTEL DOCUMENTATION FOR SAFE LOADING WITH
 LINTELS HIGHLIGHTED AND STAMPED APPROVED.
  
 10. [FBC 107.3.5.3]REMOVE NOTES THAT DON'T APPLY FROM
 SHEET A-9. DOES NOTE 18 APPLY TO BLOCK WALL?
  
 11. [FBC 107.3.5.3]TYPICAL COVER PATIO "B" SHOWS
 DRYWALL AND LOOKS THE SAME AS SECTION "A" OTHER NO
 INSULATION. SECTION "B" IS OUTSIDE AREA AND SHOULD SHOW
 MATERIALS THAT WOULD BE APPLIED FOR EXTERIOR TREATMENT,
 AND TRUSS ORIENTATION SHOULD MATCH. PLEASE
  
 12. [FBC R301.1]MARK THE PLAN WITH SECTION CUTS SO I
 CAN TELL WHERE YOU ARE DRAWINGS SECTIONS FROM.
  
 13. [FBC R904]WHAT MATERIALS ARE BEING USED FOR THE
 SOFFIT AND OVERHANG IN TYPICAL WALL SECTION. ADD NOTES
 TO SECTIONS AS APPLICABLE.
  
 14. [FBC R806]SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED.
  
 15. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 NOTICE OF ACCEPTANCE(N.O.A.):
  
 16. [FBC 107.2.1]PLASTPRO PRODUCT APPROVAL DOESN'T
 COMPLY WITH CURRENT CODE EDITION, AND IT DOESN'T COVER
 DOORS 10' HIGH. PLEASE RE-SUBMIT N.O.A. FOR ENTRY DOOR
 THAT MEETS REQUIRMENTS.
  
 17. [FBC 107.2.1]N.O.A. FOR GARAGE DOOR DOES NOT COVER
 DOORS WIDER THAN 16'. SHEET A.6 IS CALLING FOR AN 18'
 WIDE DOOR, SO PLEASE PROVIDE N.O.A. TO MEET CRITERIA.
  
 18. [FBC 107.2.1]N.O.A. FOR WINDOW ONLY COVERS WINDOWS
 UP TO 76" IN HEIGHT (TABLE 1&2). PLEASE PROVIDE N.O.A.
 FOR WINDOWS OVER 76" TALL.
  
 GENERAL NOTE FOR N.O.A'S:
 PLEASE HIGHLIGHT ON THE REVIEWED/APPROVED N.O.A'S THE
 APPLICABLE ITEM AND ATTACHMENT OPTIONS FOR THE PRODUCT
 BEING SPECIFIED.
  
  
 18060108(DECK):
 1. [FBC R107.3.5.3]PROVIDE DETAIL FOR BRICK PAVERS, OR
 INDICATE THAT SUBMITTAL WILL BE PROVIDED BY THE
 INSTALLER FOR PERMIT 18060108.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS
 SUBMITTED AND A COMMENT RESPONSE SHEET.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By ppetty Date 2018-08-06 Time 13:48 Rev Time 0.00
Received By ppetty Date 2018-08-06 Time 13:22 Sent To  
Notes
2018-08-06 13:22:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 END OF COMMENTS.
  
  
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By jpearson Date 2018-06-27 Time 10:48 Rev Time 0.00
Received By jpearson Date 2018-06-27 Time 09:19 Sent To  
Notes
2018-06-27 10:48:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3. RISER SHOWS THREE 3/0 CONDUCTORS TO INTERIOR PANEL.
 FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN EQUIPMENT
 GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 4. PROVIDE COMPLETE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS. SEE EXAMPLE IN FBC RESIDENTIAL. SOME ITEMS
 ARE NOT INCLUDED IN PANEL SCHEDULE, SUCH AS DISHWASHER.
 PROVIDE CORRECTIONS. NEC 220; FBC RE E3602.2
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
 10. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 11. LIGHTING IN OUTSIDE AREAS SHALL BE SUITABLE FOR
 DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A); FBC
 RE E4003.9
 12. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 15:40 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 15:40 Sent To  
Notes
2018-08-22 15:43:10GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-02 Cont ID  
Sent By pvalenti Date 2018-10-02 Time 09:03 Rev Time 0.00
Received By pvalenti Date 2018-09-27 Time 11:44 Sent To I
Notes
2018-10-01 11:45:02PVALENTI'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-24 Cont ID  
Sent By pvalenti Date 2018-09-24 Time 17:20 Rev Time 0.00
Received By pvalenti Date 2018-08-30 Time 15:44 Sent To I
Notes
2018-08-31 15:44:45R33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2018-07-19 Time 15:33 Sent To  
Notes
2018-07-20 15:33:47R37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-05 Cont ID  
Sent By hmoser Date 2018-07-05 Time 13:34 Rev Time 0.00
Received By hmoser Date 2018-06-04 Time 12:37 Sent To  
Notes
2018-06-05 12:37:48R36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-02 Cont ID  
Sent By pvalenti Date 2018-10-02 Time 08:57 Rev Time 0.00
Received By pvalenti Date   Time   Sent To  
Notes
2018-10-02 09:02:19NOTES:
 THE CONTRACTOR SUBMITTED THE IMPACT FEE RECEIPT.
 TRACKING NUMBER: MU-2018-033367-0000.
 TOTAL: $8484.59

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 07:38 Rev Time 0.00
Received By shill Date 2018-07-05 Time 07:38 Sent To  
Notes
2018-07-05 07:39:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-09-24 Cont ID  
Sent By pvalenti Date 2018-09-24 Time 15:26 Rev Time 0.00
Received By ccole Date 2018-09-24 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By hmoser Date 2018-08-22 Time 14:42 Rev Time 0.00
Received By hmoser Date 2018-08-22 Time 14:19 Sent To  
Notes
2018-08-22 14:41:52PLAN DENIED
 REFER TO SECTION 1401.3 EQUIPMENT AND APPLIANCE SIZING.
 MISSING ENERGY CALCULATIONS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By hmoser Date 2018-07-05 Time 13:34 Rev Time 0.00
Received By hmoser Date 2018-07-05 Time 11:49 Sent To I
Notes
2018-07-05 13:34:26PLAN DENIED
 1) PROVIDE DUCT SIZE FOR RETURN AIR IN BEDROOM
 PER SECTION M1602.3 BALANCED RETURN AIR.
 2017 RESIDENTIAL CODE
 2) SHOW WHERE DRYER DUCT IS GOING TO TERMINATE
 ON THE PLAN SECTION M1502.4.5 DUCT LENGTH
 2017 RESIDENTIAL CODE.
 3) PLEASE PROVIDE A DETAIL ON THE PLAN SHOWING
 HOW THE DUCT WILL BE INSTALLED ( FLAT ROOF 14 X 14
 DUCT 17 X17 DUCT ON THE OUTSIDE ) SECTION 107
 FBC 2017.
 4) REFER TO SECTION M1401.3 EQUIPMENT AND
 APPLIANCE SIZING.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 15:39 Sent To  
Notes
2018-08-22 15:42:3108/22/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By gjohnson Date 2018-06-26 Time 09:24 Rev Time 0.00
Received By gjohnson Date 2018-06-26 Time 08:51 Sent To  
Notes
2018-06-26 09:43:361ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-2 IT APPEARS TO BE ALOT OF THE DETAILS THAT
 WON'T BE USED ON THIS JOB PLEASE REMOVE OR MARK NOT
 USED ALL DETAILS THAT DON'T APPLY TO THIS JOB. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. P-2 DETAIL I PLEASE SHOW LOCATION AND PIPING
 FOR THE DRY WELL. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. P-2 DETAIL A FLOOR DRAIN NOT SHOWN ON SANITARY
 ISOMETRIC OR FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 4. SHT. P-2 DETAIL H WHAT PIPING IS GOING TO BE ON THE
 ROOF PLEASE CLARIFY. . PER WPB AMEND TO FBC 107.2.1
  
 5. A CLEAN OUT IS REQUIRED AT EACH BUILDING DRAIN THAT
 EXITS THE BUILDING PER FBC RES P3005.2.3 , P3005.2.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 10:04 Rev Time 0.00
Received By shill Date 2018-07-05 Time 10:04 Sent To  
Notes
2018-07-05 10:04:36FLAT ROOF PRODUCT APPROVAL & CALCULATIONS PROVIDED
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-18 Cont ID  
Sent By awooten Date 2018-09-18 Time   Rev Time 0.00
Received By awooten Date 2018-09-18 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-31 Cont ID  
Sent By awooten Date 2018-07-31 Time 16:47 Rev Time 0.00
Received By awooten Date 2018-07-30 Time 16:49 Sent To  
Notes
2018-07-31 16:47:13************************************ZONING REVIEW
 FAILED*****************************
  
 THE SETBACK FROM THE REAR PROPERTY LINE (THE PROPERTY
 LINE ACROSS FROM PROPERTY LINE ON S OLIVE) SHOULD BE
 10.2 FEET.
  
 PLEASE MAKE SURE THAT THE SETBACKS LISTED ON THE SURVEY
 AND THE SITE PLAN ARE CONSISTENT.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By awooten Date 2018-06-12 Time   Rev Time  
Received By awooten Date 2018-06-12 Time   Sent To  
Notes
2018-06-12 11:26:30********************************************ZONING
 REVIEW FOR HOUSE FAILED********************************
 *******************
  
 THE ZONING OF THE PROPERTY IS SF-7.
  
 PROVIDE THE FRONT YARD SETBACK ON THE SITE PLAN.
 (ACCORDING TO CURRENT CODE OLIVE IS THE FRONT YARD, THE
 LESSER LENGTH.)
  
 THE REAR SETBACK IS 10.7 FEET.
  
 DECKS REQUIRE A SEPARATE PERMIT.
  
 PROVIDE THE SETBACK FOR THE A/C
  
 *SECTION 94-305. (B)(4) MECHANICAL EQUIPMENT.
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK. WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
 DRIVEWAY REQUIRES A SEPARATE PERMIT.
  
 WALLS AND FENCES REQUIRE A SEPARATE PERMIT.
  
 A SEPARATE LANDSCAPE AND IRRIGATION PERMIT IS REQUIRED
 TO SHOW:
  
 *RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  