Plan Review Details - Permit 18051487
Plan Review Stops For Permit 18051487
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By spalmer Date 2018-07-26 Time 12:24 Rev Time 0.00
Received By spalmer Date 2018-07-26 Time 12:24 Sent To  
Notes
2018-07-26 12:25:08SEE PLAN REVIEW ON 18051486

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By tklarge Date 2018-06-21 Time 06:48 Rev Time 0.00
Received By tklarge Date 2018-06-21 Time 06:10 Sent To  
Notes
2018-06-21 06:46:311) THE EXISTING GAS PLANS ON FILE IN THE CITY HAVE THE
 FOLLOWING INFORMATION FOR THE EXISTING BTU LOAD:
 A) WATER HEATER - 55,000 BTU'S
 B) GAS DRYER - 35,000 BTU'S
 C) BBQ - 40,000 BTU'S
 D) POOL HEATER - 400,000 BTU'S
 THESE VALUES SHALL BE USED FOR THE EXISTING BTU LOAD ON
 YOUR PLANS.
 2) THE TOTAL BTU LOAD WILL BE 850,000 BTU'S. THE GAS
 METER SHALL BE CHECKED TO ENSURE THAT IT WILL HANDLE
 THE TOTAL BTU LOAD OF THE SYSTEM. CONTACT THE GAS
 PURVEYOR FOR FURTHER DIRECTION. THIS WILL BE CHECKED BY
 THE FIELD INSPECTOR AT FINAL INSPECTION.
 3) SUBMIT TWO COPIES OF THE INSTALLATION INTRUCTIONS
 FOR THE REGULATOR.WPB AMEND. TO FBC SEC. 107.2.1.
 4) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER 2017
 FBC-GAS SEC.410.1. THE REGULATOR SPECS DO NOT SHOW
 THIS.
 5) INDICATE ON THE REGULATOR SPECS THE MODEL BEING
 INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 7) THE EXISTING GAS PLANS ON FILE IN THE CITY SSHOW AN
 1 1/2 INCH GALVANIZED LINE FROM THE METER OUTLET AND A
 1 INCH GALVANIZED LINE TO THE INTERIOR AND YOUR PLAN
 SHOWS A 3/4 INCH LINE AT BOTH POINTS. CLARIFY.
 8) INDICATE ON THE PLANS THE SIZING TABLE FOR THE LOW
 PRESSURE SIDE FOR THE GENERATOR.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-21 Cont ID  
Sent By tklarge Date 2018-06-21 Time 06:48 Rev Time 0.00
Received By tklarge Date 2018-06-21 Time 06:10 Sent To  
Notes
***NONE***