Plan Review Details - Permit 18051483
Plan Review Stops For Permit 18051483
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-19 Cont ID  
Sent By cthroop Date 2018-10-19 Time 09:38 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-12 Cont ID  
Sent By cthroop Date 2018-09-12 Time 13:03 Rev Time 0.00
Received By cthroop Date 2018-09-12 Time 11:40 Sent To  
Notes
2018-09-12 13:07:34BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PROVIDE SOILS REPORT FROM ACCREDITED LABORATORY.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 3. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 PROPOSED BBQ GRILL. COMBUSTIBLE CEILING ABOVE PROPOSED
 LOCATION. GRILL MAY REQUIRE EXHAUST HOOD.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-06 Cont ID  
Sent By cthroop Date 2018-07-06 Time 09:34 Rev Time 0.00
Received By cthroop Date 2018-07-05 Time 08:54 Sent To  
Notes
2018-07-06 09:58:05BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE STATEMENT OF GOVERNING CODES ON PLANS.
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 2. PROVIDE SOILS REPORT FROM ACCREDITED LABORATORY.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 3. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 IMPACT FEES PAID
 PALM BEACH COUNTY IMPACT FEE OFFICE
 DATE RECEIVED:
 RECEIPT NUMBER:
 TRACKING NUMBER:
 TOTAL AMOUNT:
  
 4. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 5. ROOFING PERMIT REQUIRED.
  
 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 PROPOSED BBQ GRILL. COMBUSTIBLE CEILING ABOVE PROPOSED
 LOCATION. GRILL MAY REQUIRE EXHAUST HOOD.
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTION FOR
 SOLAR PV PANELS THAT ARE TO BE RE-LOCATED. ATTACHMENT
 DETAIL TO METAL ROOF REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By ppetty Date 2018-08-28 Time 13:59 Rev Time 0.00
Received By ppetty Date 2018-08-28 Time 13:59 Sent To  
Notes
2018-08-28 13:59:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-03 Cont ID  
Sent By jpearson Date 2018-07-03 Time 08:40 Rev Time 0.00
Received By jpearson Date 2018-07-02 Time 13:47 Sent To  
Notes
2018-07-03 08:40:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-2, NOTE 10(A) DESCRIBES AFCI PROTECTION BUT
 DOES NOT COVER ALL AREAS REQUIRED PER CODE. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 2. SHEET E-2, NOTE 10(B) DESCRIBES TAMPER RESISTANT
 RECEPTACLES. NOTE STATES THAT RECEPTACLES SHALL BE
 TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION DOES
 NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. NEW MASTER DOES NOT SHOW COMPLIANCE. FBC RE
 R314.3, R315.1; WPB FBC 107.2.1
 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 17:35 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 17:35 Sent To  
Notes
2018-06-29 17:36:22GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-19 Cont ID  
Sent By cthroop Date 2018-10-19 Time 10:44 Rev Time 0.00
Received By cthroop Date 2018-10-05 Time 15:11 Sent To  
Notes
2018-10-10 15:13:59LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-29 Cont ID  
Sent By shill Date 2018-09-29 Time 11:19 Rev Time 0.00
Received By shill Date 2018-08-01 Time 14:37 Sent To  
Notes
2018-08-07 15:47:00R39
2018-08-02 14:37:37LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-06 Cont ID  
Sent By skennedy Date 2018-07-06 Time 16:41 Rev Time 0.00
Received By skennedy Date 2018-05-31 Time 12:03 Sent To  
Notes
2018-06-01 12:04:01R35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 16:03 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 09:34 Sent To  
Notes
2018-10-18 16:04:06ADDITION REMOVED FROM SUBMITTAL.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-06 Cont ID  
Sent By cthroop Date 2018-07-06 Time 09:28 Rev Time 0.00
Received By cthroop Date 2018-07-05 Time 08:54 Sent To  
Notes
2018-07-06 09:31:21BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2018-10-19 Cont ID  
Sent By cthroop Date 2018-10-19 Time 09:20 Rev Time 0.00
Received By cthroop Date 2018-10-19 Time 09:20 Sent To  
Notes
2018-10-19 09:21:06MECHANICAL REMOVED FROM THIS SUBMITTALL PER RICK
 FERRAR. CT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-09-29 Time   Rev Time 0.00
Received By   Date 2018-09-29 Time   Sent To  
Notes
2018-09-29 11:15:012ND REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 2ND REVIEW FBC 2017 EXISTING BUILDING
  
 FAILED
  
 1) PROVIDE A MECHANICAL HVAC PLAN. FBC 107
 2) PROVIDE AN EQUIPMENT SIZING CALCULATION. FBCR403.7
 HEATING AND COOLING EQUIPMENT (MANDATORY).
 FBCR 403.7.1EQUIPMENT SIZING.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-06 Cont ID  
Sent By skennedy Date 2018-07-06 Time 16:40 Rev Time 0.00
Received By skennedy Date 2018-07-06 Time 16:40 Sent To  
Notes
2018-07-06 16:40:541ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FAILED
  
 1) PROVIDE A MECHANICAL HVAC PLAN. FBC 107
 2) PROVIDE AN EQUIPMENT SIZING CALCULATION. FBCR403.7
 HEATING AND COOLING EQUIPMENT (MANDATORY).
 FBCR 403.7.1EQUIPMENT SIZING.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 15:06 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 15:05 Sent To  
Notes
2018-09-07 12:58:49REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 15:06:23APPROVED

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 17:28 Sent To  
Notes
2018-06-29 17:35:351ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE AND LAUNDRY TRAY ARE NOT VENTED
 PLEASE COMPLY WITH FBC PL 901.2.1
  
 2. THE NOTE ON EXISTING POOL EQUIPMENT STATE RELOCATE
 EXISTING PLEASE SHOW NEW LOCATION OF EXISTING
 EQUIPMENT. PER WPB AMEND TO FBC 107.2.1
  
 3. A SEPARATE PERMIT IS REQUIRED FOR GAS AND THE
 RELOCATION OF THE POOL EQUIPMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 14:51 Rev Time 0.00
Received By shill Date 2018-09-06 Time 14:50 Sent To  
Notes
2018-09-06 14:51:15APPROVED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-07-06 Cont ID  
Sent By cthroop Date 2018-07-06 Time 09:31 Rev Time 0.00
Received By cthroop Date 2018-07-05 Time 08:55 Sent To  
Notes
2018-07-06 09:34:26BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF COVERING.
 2. PROVIDE PRODUCT APPROVALS FOR SELF ADHERED
 UNDERLAYMENT FOR VALLEY'S.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-17 Cont ID  
Sent By llouie Date 2018-10-17 Time   Rev Time 0.00
Received By llouie Date 2018-10-16 Time   Sent To  
Notes
2018-10-17 10:00:56INTERIOR MODIFICATIONS, WINDOWS/DOORS AND PLACEMENT OF
 THE A/C COMPRESSOR UNIT PAD ONLY.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-06 Cont ID  
Sent By llouie Date 2018-08-06 Time   Rev Time 0.00
Received By llouie Date 2018-08-06 Time   Sent To PC
Notes
2018-08-06 17:19:23** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) NO SURVEY PROVIDED WITH THE PERMIT SUBMITTAL. AN
 UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 REQUIRED WITH THE PERMIT. PLEASE PROVIDE. [6/8/18
 COMMENT NOT ADDRESSED]
  
 2.) WIDTH OF NEW DRIVEWAY SHALL BE NOTATED IN THE PLAN.
 PLEASE NOTE THAT THE NEW DRIVEWAY CANNOT EXCEED 20 FT.
 IN WIDTH [ZLDR S.94-312 AND S.94-482(D)]. [6/8/18
 COMMENT NOT ADDRESSED]
  
 3.) THE VALUE OF THE CONSTRUCTION ($325,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($143,083.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. [6/8/18 COMMENT NOT
 ADDRESSED]
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: WALL,
 DRIVEWAY AND LANDSCAPING.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By llouie Date 2018-06-08 Time   Rev Time  
Received By llouie Date 2018-06-08 Time   Sent To  
Notes
2018-06-08 13:11:04** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) NO SURVEY PROVIDED WITH THE PERMIT SUBMITTAL. AN
 UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 REQUIRED WITH THE PERMIT. PLEASE PROVIDE.
  
 2.) PLEASE SHOW SETBACK DISTANCE OF THE PROPOSED NEW
 5FT. HIGH WALL ALONG THE FRONT PROPERTY LINE TO ENSURE
 COMPLIANCE WITH THE MINIMUM REQUIREMENTS OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 3.) SHOW SETBACK DIMENSIONS OF ALL NEW/RELOCATED
 MECHANICAL EQUIPMENT (I.E. A/C UNIT, POOL EQUIPMENT,
 ETC.) IN THE PLAN. PLEASE NOTE THAT MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FT. INTO A
 SETBACK. [ZLDR S.94-305(B)(4)]
  
 4.) SHOW SETBACK AND DIMENSIONS FOR THE PROPOSED NEW
 DRIVEWAY. PLEASE NOTE THAT THE NEW DRIVEWAY CANNOT
 EXCEED 20 FT. IN WIDTH, AND MUST BE SETBACK AT LEAST 3
 FT. FROM THE SIDE PROPERTY LINE. [ZLDR S.94-312 AND
 S.94-482(D)]
  
 5.) THE VALUE OF THE CONSTRUCTION ($325,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($143,083.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 6.) PLAN SHOWS THE REMOVAL OF EXISTING TREES FROM THE
 PROPERTY. A TREE ALTERATION PERMIT (TAP) IS REQUIRED
 PRIOR TO THE REMOVAL OF ANY TREES/PALMS ON THE
 PROPERTY. PLEASE CONTACT THE CITY'S LANDSCAPE PLANNER,
 RAY CARANCI, AT (561) 822-1462 FOR DETAIL ON THE TAP.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: WALL,
 DRIVEWAY AND LANDSCAPING.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  