| Plan Review Stops For Permit 18051483 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-10-19 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-10-18 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-09-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-09-12 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-09-12 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2018-09-12 13:07:34 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. PROVIDE SOILS REPORT FROM ACCREDITED LABORATORY. | | | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE | | | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND | | | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE | | | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL | | | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY | | | TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 2. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 3. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | | STORIES. ENERGY | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | _ OR _ | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 4. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR | | | PROPOSED BBQ GRILL. COMBUSTIBLE CEILING ABOVE PROPOSED | | | LOCATION. GRILL MAY REQUIRE EXHAUST HOOD. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-06 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-05 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2018-07-06 09:58:05 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE STATEMENT OF GOVERNING CODES ON PLANS. | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | 2. PROVIDE SOILS REPORT FROM ACCREDITED LABORATORY. | | | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE | | | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND | | | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE | | | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL | | | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY | | | TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 3. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | IMPACT FEES PAID | | | PALM BEACH COUNTY IMPACT FEE OFFICE | | | DATE RECEIVED: | | | RECEIPT NUMBER: | | | TRACKING NUMBER: | | | TOTAL AMOUNT: | | | | | | 4. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | | STORIES. ENERGY | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | _ OR _ | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 5. ROOFING PERMIT REQUIRED. | | | | | | 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR | | | PROPOSED BBQ GRILL. COMBUSTIBLE CEILING ABOVE PROPOSED | | | LOCATION. GRILL MAY REQUIRE EXHAUST HOOD. | | | | | | 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTION FOR | | | SOLAR PV PANELS THAT ARE TO BE RE-LOCATED. ATTACHMENT | | | DETAIL TO METAL ROOF REQUIRED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-28 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-08-28 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-08-28 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2018-08-28 13:59:08 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW. | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-03 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-02 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2018-07-03 08:40:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET E-2, NOTE 10(A) DESCRIBES AFCI PROTECTION BUT | | | DOES NOT COVER ALL AREAS REQUIRED PER CODE. ALL BRANCH | | | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND | | | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, | | | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC | | | 210.12; FBC RE E3902.16 | | | 2. SHEET E-2, NOTE 10(B) DESCRIBES TAMPER RESISTANT | | | RECEPTACLES. NOTE STATES THAT RECEPTACLES SHALL BE | | | TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION DOES | | | NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | | CORRECTION. NEC 406.12; FBC RE E4002.14 | | | 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. NEW MASTER DOES NOT SHOW COMPLIANCE. FBC RE | | | R314.3, R315.1; WPB FBC 107.2.1 | | | 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC | | | 210.63; FBC RE E3901.12 | | | 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC | | | 107.3.5; FBC RE E3706.2, E3902 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-29 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-29 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2018-06-29 17:36:22 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | | INSTALLATION OR MODIFICATION OF SYSTEM. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-10-19 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-10-05 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2018-10-10 15:13:59 | LIBRARY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-29 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-01 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2018-08-07 15:47:00 | R39 | | 2018-08-02 14:37:37 | LIBRARY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-06 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-05-31 |
Time |
12:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2018-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-10-18 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-10-18 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2018-10-18 16:04:06 | ADDITION REMOVED FROM SUBMITTAL. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-06 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-05 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2018-07-06 09:31:21 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-10-19 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-10-19 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2018-10-19 09:21:06 | MECHANICAL REMOVED FROM THIS SUBMITTALL PER RICK | | | FERRAR. CT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-09-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2018-09-29 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-29 11:15:01 | 2ND REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 2ND REVIEW FBC 2017 EXISTING BUILDING | | | | | | FAILED | | | | | | 1) PROVIDE A MECHANICAL HVAC PLAN. FBC 107 | | | 2) PROVIDE AN EQUIPMENT SIZING CALCULATION. FBCR403.7 | | | HEATING AND COOLING EQUIPMENT (MANDATORY). | | | FBCR 403.7.1EQUIPMENT SIZING. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-06 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-06 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2018-07-06 16:40:54 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | FAILED | | | | | | 1) PROVIDE A MECHANICAL HVAC PLAN. FBC 107 | | | 2) PROVIDE AN EQUIPMENT SIZING CALCULATION. FBCR403.7 | | | HEATING AND COOLING EQUIPMENT (MANDATORY). | | | FBCR 403.7.1EQUIPMENT SIZING. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-06 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-09-06 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2018-09-07 12:58:49 | REVIEW COMPLETED BY JERALD SMITH 0017-P | | 2018-09-06 15:06:23 | APPROVED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-29 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-29 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2018-06-29 17:35:35 | 1ST REVIEW: FBC 2017 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE WASHING MACHINE AND LAUNDRY TRAY ARE NOT VENTED | | | PLEASE COMPLY WITH FBC PL 901.2.1 | | | | | | 2. THE NOTE ON EXISTING POOL EQUIPMENT STATE RELOCATE | | | EXISTING PLEASE SHOW NEW LOCATION OF EXISTING | | | EQUIPMENT. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. A SEPARATE PERMIT IS REQUIRED FOR GAS AND THE | | | RELOCATION OF THE POOL EQUIPMENT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-06 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-06 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2018-09-06 14:51:15 | APPROVED |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-06 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-05 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2018-07-06 09:34:26 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF COVERING. | | | 2. PROVIDE PRODUCT APPROVALS FOR SELF ADHERED | | | UNDERLAYMENT FOR VALLEY'S. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-10-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-10-17 10:00:56 | INTERIOR MODIFICATIONS, WINDOWS/DOORS AND PLACEMENT OF | | | THE A/C COMPRESSOR UNIT PAD ONLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-08-06 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-08-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-08-06 |
Time |
|
Sent To |
PC |
|
| Notes |
| 2018-08-06 17:19:23 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) NO SURVEY PROVIDED WITH THE PERMIT SUBMITTAL. AN | | | UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED WITH THE PERMIT. PLEASE PROVIDE. [6/8/18 | | | COMMENT NOT ADDRESSED] | | | | | | 2.) WIDTH OF NEW DRIVEWAY SHALL BE NOTATED IN THE PLAN. | | | PLEASE NOTE THAT THE NEW DRIVEWAY CANNOT EXCEED 20 FT. | | | IN WIDTH [ZLDR S.94-312 AND S.94-482(D)]. [6/8/18 | | | COMMENT NOT ADDRESSED] | | | | | | 3.) THE VALUE OF THE CONSTRUCTION ($325,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($143,083.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. [6/8/18 COMMENT NOT | | | ADDRESSED] | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: WALL, | | | DRIVEWAY AND LANDSCAPING. | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: SF7 | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-06-08 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-06-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-08 13:11:04 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) NO SURVEY PROVIDED WITH THE PERMIT SUBMITTAL. AN | | | UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED WITH THE PERMIT. PLEASE PROVIDE. | | | | | | 2.) PLEASE SHOW SETBACK DISTANCE OF THE PROPOSED NEW | | | 5FT. HIGH WALL ALONG THE FRONT PROPERTY LINE TO ENSURE | | | COMPLIANCE WITH THE MINIMUM REQUIREMENTS OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | | | | 3.) SHOW SETBACK DIMENSIONS OF ALL NEW/RELOCATED | | | MECHANICAL EQUIPMENT (I.E. A/C UNIT, POOL EQUIPMENT, | | | ETC.) IN THE PLAN. PLEASE NOTE THAT MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FT. INTO A | | | SETBACK. [ZLDR S.94-305(B)(4)] | | | | | | 4.) SHOW SETBACK AND DIMENSIONS FOR THE PROPOSED NEW | | | DRIVEWAY. PLEASE NOTE THAT THE NEW DRIVEWAY CANNOT | | | EXCEED 20 FT. IN WIDTH, AND MUST BE SETBACK AT LEAST 3 | | | FT. FROM THE SIDE PROPERTY LINE. [ZLDR S.94-312 AND | | | S.94-482(D)] | | | | | | 5.) THE VALUE OF THE CONSTRUCTION ($325,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($143,083.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | 6.) PLAN SHOWS THE REMOVAL OF EXISTING TREES FROM THE | | | PROPERTY. A TREE ALTERATION PERMIT (TAP) IS REQUIRED | | | PRIOR TO THE REMOVAL OF ANY TREES/PALMS ON THE | | | PROPERTY. PLEASE CONTACT THE CITY'S LANDSCAPE PLANNER, | | | RAY CARANCI, AT (561) 822-1462 FOR DETAIL ON THE TAP. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: WALL, | | | DRIVEWAY AND LANDSCAPING. | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: SF7 | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|