| Plan Review Stops For Permit 18051464 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-26 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-26 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2019-03-26 15:39:12 | AIPP SATISFIED PER S.WELTER EMAIL 3/21/19 | | | ROUTED EMAIL TO FILENET | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-04 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-04 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-09-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-28 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-24 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2018-09-28 08:24:36 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051464 | | | REVIEWED: AUGUST 15, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1-8. OK | | | | | | 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS | | | THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO | | | HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS | | | OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD | | | ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED. | | | | | | 8-2. CONTRACTOR STATED THAT THEY WOULD PROVIDE A | | | GEOTECHNICAL REPORT PRIOR FILLING IN HOLE FROM THE FUEL | | | TANK REMOVAL. | | | SUPPLY REPORT, OR INDICATE THAT YOU WOULD LIKE IT TO BE | | | A PROVISO. | | | | | | | | | 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE | | | STRUCTURES. | | | DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF | | | APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE | | | WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK. | | | 9-2. PROVIDE PERMIT NUMBER FOR THE DRIVE THRU CANOPY | | | AND DUMPSTER ENCLOSURE. | | | | | | 10-14. OK | | | | | | 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR | | | INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED | | | SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION. | | | | | | 15-2. PROVISO: | | | TRUSS SHOP DRAWINGS TO BE PROVIDED TO INSPECTOR PRIOR | | | TO INSTALLATION. | | | | | | KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION. | | | PLEASE PROVIDE REQUIREMENTS SET FORTH WATER | | | INFILTRATION. | | | [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL | | | SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE | | | THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED | | | NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG | | | RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION: | | | OH RATIO = OH LENGTH/OH HEIGHT | | | WHERE: | | | OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN | | | OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. | | | OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM | | | THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A | | | DOOR. | | | | | | RESPONSE: THE KAWNEER?S 350 IR SIDE-HINGED DOORS NOA # | | | 15-0622.11 COMPLIES WITH FBC 1709.5.1 EXCEPTION: ?DOOR | | | ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE THE | | | DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER | | | INFILTRATION NEED NOT BE TESTED FOR WATER | | | INFILTRATION.? ACCORDING THE MANUFACUTURER THE KAWNEER | | | DOOR IS DESIGNED TO ACCEPT WATER AND DETER IT BY THE | | | BULB GASKETS ALONG THE PERIMETER FRAMING WHERE IT MEETS | | | THE DOOR. | | | | | | 15-2. I?M LOOKING AT NOA 15-0622.11 NOTE ON SHEET 1 OF | | | 9. | | | IT STATES THAT THESE DOORS ARE NOT APPROVED FOR USE | | | WHERE WATER INFILTRATION RESISTANCE IS REQUIRED. | | | PLEASE PROVIDE REPONSE THAT DOESN?T INCLUDE THE DOORS | | | MEETING REQUIREMENTS FOR WATER INFITRATION, BUT RATHER | | | STATE HOW YOU ARE MEETING THE EXCEPTION REQUIRING THE | | | AREA TO ACCEPT WATER INFILTRATION IN A NONHABITABLE | | | AREA. | | | | | | | | | 16. OK. | | | | | | NEW COMMENT: | | | 17. PLEASE REPLACE NOA 16-0510.28 FOR ROOF VENTS WITH | | | NOA 15-0922.06 FOR ROOF VENTS AS STATED IN COMMENT | | | RESPONSE SHEET DATED SEPTEMBER 18, 2018. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-16 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-13 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2018-08-16 08:55:36 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051464 | | | REVIEWED: AUGUST 15, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SOME OF THE UPLOADED DRAWINGS NAMING DESIGNATIONS | | | DON?T MATCH THE SHEET PROVIDED. PLEASE RE-UPLOAD THE | | | FOLLOWING ARCHITECTURAL DRAWINGS TO PROJECT DOX. | | | A.01, A.02, A.03, A.04, A3.3, A3.4, A5.6 AND A5.7 | | | | | | 2. ALL CIVIL DRAWINGS WERE UPLOADED STARTING WITH THE | | | SAME THREE DIGIT DESIGNATION AS ARCHITECTURAL DWG?S. | | | THIS HAS CAUSED THE ARCHITECTURALS AND CIVIL PLANS TO | | | GET MIXED IN TOGETHER. | | | THE THREE DIGIT PREFIX SHOULD START AT 001 AND 001 | | | SHOULD NOT BE REPEATED. | | | CIVIL PLANS SHOULD HAVE BEEN 001-021 | | | ARCHITECTURAL WOULD START AT 022 | | | TO FIX THIS WITHOUT RELOADING ALL PLANS PLEASE DELETE | | | ALL CIVIL FILES (C1 THRU C21)RELOAD ALL CIVIL PLANS | | | WITH THE FIRST THREE DIGIT AS 000. THIS WILL PUT THEM | | | ALL AT THE TOP OF LIST, AND THE REST OF THE DRAWINGS | | | WILL KEEP CURRENT DESIGNATIONS. | | | | | | 3. SHEET C21 REFERENCES 2014 CODE FOR WIND LOADS. | | | PLEASE UPDATE TO FBC 2017 6 TH EDITION WHEN SUBMITTING | | | FOR SITE LIGHTING PERMIT. | | | | | | 4. [FBC 107.2.5]PLEASE UPLOAD THE SURVEY TO SUPPORTING | | | DOCUMENTS. | | | | | | 5. A UNITY OF TITLE WILL BE NEEDED TO COMBINE THE TWO | | | LOTS TOGETHER. CURRENTLY THERE ARE TWO PCN'S AND TWO | | | ADDRESSES | | | | | | 6. DEMO PERMIT FOR FUEL TANKS NEEDS TO BE CLOSED OUT | | | PRIOR TO PERMIT ISSUANCE. | | | | | | 7. THE STRUCTURAL REPORT IS A MULTI PAGE DOCUMENT. THE | | | FIRST 55 PAGES ARE GOOD, BUT THE REMAINING 35 PAGES | | | DON?T SHOW UP. PLEASE VERIFY THAT ALL 80 PAGES ARE | | | PRESENT IN THE DOCUMENT AND RE-UPLOAD TO PROJECT DOX IF | | | NEEDED. | | | | | | 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS | | | THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO | | | HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS | | | OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD | | | ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED. | | | | | | 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE | | | STRUCTURES. | | | DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF | | | APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE | | | WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK. | | | | | | 10. SHEET A1.1 DETAIL CALL OUTS 2/A7.4 AND 3/A74 APPEAR | | | TO BE FOR SIDE SUPPORT OF THE COILING DOOR, BUT THEY | | | LEAD TO DETAIL OF SCALA SIGNAGE. | | | UPDATE DETQAIL CALLOUTS AND PROVIDE DETAIL THEY WERE | | | INTENDED TO SHOW. | | | IS ANY ADDITIONAL SUPPORT NEEDED FOR THE DOOR AND MOTOR | | | SUPPORTED ABOVE, IF SO PLEASE UPDATE STRUCTURAL TO | | | INCORPORATE. | | | | | | 11. SHEET S0.1 DESIGN AND LOADING. UPDATE THE CODE | | | REFERENCE TO FBC 2017 6 TH EDITION. | | | | | | 12. SHEET S.02 IN WIND DESIGN DATA ? UPDATE THE CODE | | | REFERENCE TO FBC 2017 6 TH EDITION. | | | | | | 13. PROVIDE ROOF DECKING ATTACHMENT/SPACING SCHEDULES | | | FOR THE FLAT ROOF AND THE TOWER ROOF IN APPLICABLE | | | ZONES FROM S0.2 WIND DATA SHEET. SECTIONS AND DETAILS | | | SHOW SHEATHING DIFFERENTLY. UPDATE TO SHOW SHEATHING AS | | | INTENDED. | | | | | | 14. ROOF SUB PERMIT WILL BE REQUIRED(SEE ROOFING REVIEW | | | FOR COMMENTS) | | | | | | 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR | | | INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED | | | SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION. | | | KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION. | | | PLEASE PROVIDE REQUIREMENTS SET FORTH WATER | | | INFILTRATION. | | | [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL | | | SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE | | | THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED | | | NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG | | | RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION: | | | OH RATIO = OH LENGTH/OH HEIGHT | | | WHERE: | | | OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN | | | OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. | | | OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM | | | THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A | | | DOOR. | | | | | | 16. PROVIDE ROOF DRAINAGE CALCULATIONS, OR IN RESPONSE | | | LET ME KNOW WHERE THEY ARE. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-04 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-04 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-10-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-08 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-08 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2018-10-08 07:20:40 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. PAGE E3.0 OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH | | | ASHRSE 90.1 SECTION 8.4.2 PROVIDE RECEPTACLE CONTROL | | | REQUIRED BY ASHREA 90.1: 8.4.2. FBC CE 405.7.1 | | | (RESPONSE LETTER STATES THIS IS NOT REQUIRED PER THE | | | FBC ENERGY, WHICH IS INCORRECT. SEE FBC EC 405.6.1. | | | PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC C405.6.1) | | | 3. E3.1 NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON | | | ROOF. (SHEET M2.0 DOES NOT STATE IF THIS "CONVENIENCE | | | OUTLET" IS GFCI PROTECTED PER CODE. PROVIDE | | | CLARIFICATION AND/OR CORRECTION. NEC 210.8, 210.63) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 9. DIGITAL SIGNATURES ARE CORRUPTED. SEE COMMENTS UNDER | | | SIGNATURE STOP. FS 471/481; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-08-07 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-08-07 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2018-08-07 14:35:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | E0.1 | | | | | | TAP OFF MAIN TO POWER METER AND TO WAC SYSTEM HOW IS | | | THIS GOING TO BE CONNECTED? | | | | | | BUILDING MANAGEMENT SYSTEM TO COMPLY WITH ARTICLE 750 | | | OF THE NEC | | | | | | PAGE E3.0 | | | | | | OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH ASHRSE 90.1 | | | SECTION 8.4.2 | | | PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC CE 405.7.1 | | | | | | E3.1 | | | | | | NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON ROOF. | | | | | | E7.0 | | | | | | LOAD CACLUATION NOT CALCULATED PER 220 OF THE NEC | | | THE ONE SHOWN ON E7.0 SHOWS LIGHTING LOAD OF 2.9KW? | | | | | | FAULT CURRENT CALCULATION REQUIRED FOR ALL SERVICE | | | EQUIPMENT AND DOWN STREAM PANELS | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE TO CONFIRM | | | THE STATED AIC RATING OF THE SERVICE EQUIPMENT AND | | | DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10 | | | | | | PROVIDE ENERGY CALCULATION FOR THE INTERIOR LIGHTING. | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-04 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-04 |
Time |
12:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2018-10-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2018-10-29 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-10-29 12:59:57 | FORMAL ENGINEERING APPROVAL ON 9/27/18 FOR PLANS DATED | | | 8/20/2018. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-30 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-30 |
Time |
06:39 |
Sent To |
|
|
| Notes |
| 2018-07-30 06:40:05 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-11-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-20 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-09-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-09-24 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-27 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2018-07-06 12:57:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A 2.1 - THIS PLAN SHEET IS INDICATED AS LIFE | | | SAFETY PLAN AND DETAILS. | | | | | | BE ADVISED, THIS PLAN INDICATED ACCESSIBILITY DETAILS | | | WITH NO LIFE SAFETY. | | | | | | PLEASE REVIEW AND PROVIDE AN ACCURATE LIFE SAFETY PLAN | | | AND DETAILS. | | | | | | | | | | | | | | | 2) SHEET A 2.1 - THERE ARE INDICATIONS OF THE HARDWARE | | | ON THE MAIN ENTRY DOORS OF MORTISE CYLINDERS. | | | | | | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACIES AND | | | CHAPTER 7, MEANS OF EGRESS: | | | | | | 38.2.2 MEANS OF EGRESS COMPONENTS. | | | 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE | | | LIMITED | | | TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12. | | | 38.2.2.2 DOORS. | | | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE | | | PERMITTED. | | | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE | | | PERMITTED | | | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. | | | | | | 7.2.1.5.5 KEY-OPERATED LOCKS. | | | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE | | | PERMITTED TO HAVE | | | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT | | | ALL OF THE | | | FOLLOWING CRITERIA ARE MET: | | | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 | | | THROUGH 43 FOR | | | THE SPECIFIC OCCUPANCY. | | | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS | | | THAN 1 IN. | | | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS | | | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: | | | THIS | | | DOOR TO REMAIN UNLOCKED WHEN THE | | | BUILDING IS OCCUPIED. | | | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY | | | DISTINGUISHABLE | | | AS LOCKED. | | | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT | | | INSIDE THE | | | BUILDING WHEN IT IS LOCKED. | | | | | | AND | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | | | | PLEASE REVIEW, CORRECT OR PROVIDE SPECIFIC DETAILS OF | | | COMPLIANCE | | | | | | | | | | | | 3) SHEET A 2.1 - THERE ARE INDICATIONS OF A PANIC BAR | | | ON THE ENTRY DOORS. | | | | | | PER NFPA 101, CHAPTER 7 | | | | | | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. | | | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE | | | EQUIPPED WITH | | | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET | | | ALL OF THE | | | FOLLOWING CRITERIA: | | | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE | | | ACTUATING | | | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF | | | OF THE | | | WIDTH OF THE DOOR LEAF. | | | (2) IT SHALL BE MOUNTED AS FOLLOWS: | | | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. | | | (865 MM), | | | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 | | | IN. (760 MM), | | | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE | | | NOT TO EXCEED | | | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND | | | LATCHES. | | | | | | AND | | | | | | 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT | | | HARDWARE, IN OTHER | | | THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS | | | OTHERWISE PROVIDED | | | IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED WITH ANY | | | LOCKING | | | DEVICE, SET SCREW, OR OTHER ARRANGEMENT THAT PREVENTS | | | THE RELEASE | | | OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING | | | DEVICE. | | | | | | THOUGH PANIC HARDWARE IS NOT REQUIRED FOR THIS | | | OCCUPANCY, IF INSTALLED, IT MUST BE INSTALLED PER THE | | | APPLICABLE CODE. | | | | | | PLEASE REVIEW AND REMOVE THE PANIC BAR OR EXPLAIN WITH | | | SPECIFC DETAILS AND FIRE CODE REFERENCES. | | | | | | | | | | | | 4) SHEET A 2.1 - THERE ARE INDICATIONS OF ELECTROINC | | | LOCKS OR STRIKES WITHIN THE DOOR SCHEDULE. | | | | | | NO DOOR SHALL BE LOCKED AGAINST EGRESS. | | | | | | ALL ACCESS AND/OR EGRESS CONTROL SHALL BE COMPLY WITH | | | THE APPLICABLE REQUIREMENTS FO NFPA 101, CHAPTER 7, | | | MEANS OF EGRESS AND BE SUBMITTED UNDER A SEPARATE SHOP | | | DRAWING PERMIT. | | | | | | PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE | | | OF ACKNOWLEDGEMENT AND COMPLIANCE. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-04 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-11-14 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-30 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-20 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-16 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-06-25 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-04 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-04 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2018-12-04 15:44:44 | IMPACT FEE REVIEW DONE UNDER FOUNDATION PERMIT | | | 18101214, OK PER DBATTLES | | 2018-12-04 12:34:16 | EMAILED IMPACT FEE OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-09-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-28 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-28 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2018-09-28 08:48:25 | COMMENT CARRIED FROM FIRST REVIEW. | | | | | | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-30 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-30 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2018-07-30 06:56:06 | ****CORRECTIONS**** | | | REVISED 8/2/18 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-10-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-18 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-18 |
Time |
08:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-31 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-31 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2018-07-31 16:54:29 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18051464 | | | 7/31/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | AC SYSTEMS- SECTION C403.2.1 FBC-17 EC INCLUDING THE | | | RTU'S AND FAN COIL SYSTEMS. | | | | | | 2) THE COMCHECK ENERGY COMPLIANCE CERTIFICATE, AND THE | | | MECHANICAL PLANS ARE NOT ELECTRONICALLY SIGNED AND | | | SEALED AS REQUIRED BY SECTION 61G15-23.005 FAC. | | | | | | 3) SHEET M1.1: PROVIDE WIND LOAD ENGINEERING FOR TIE | | | DOWN OF THE RTU'S - SECTION 301.15. INCLUDE THE DESIGN | | | CRITERIA IN ACCORDANCE WITH SECTION 1609 FBC B, AND | | | COMPLETE DETAILS FOR ANCHORING THE CURBS TO THE | | | STRUCTURE, AND MOUNTING THE UNITS TO THE CURBS. | | | | | | 4) M1.1: SHOW THE CONDENSATE PIPING RUNS AND DISCARGE | | | LOCATIONS. PLEASE INDICATE THE SIZE OF THE PIPING, AND | | | SHOW HOW THE PIPING WILL BE SUPPORTED ABOVE THE ROOF | | | AND THE TYPE AND SPACING OF THE PIPE SUPPORTS. | | | | | | 5) SUBMIT THE FL. PRODUCT APPROVAL # 16921.1-R3 FOR THE | | | CONDENSER ROOF STAND. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-29 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-29 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-15 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2018-08-15 10:14:24 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THERE IS AN OUTSTANDING PERMIT FOR REMOVAL OF THE | | | OLD FUEL TANKS PERMIT # 18010008 THIS PERMIT SHALL BE | | | FINAL OUT AND CLOSED BEFORE THE BUILDING PERMIT CAN BE | | | ISSUED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2018-09-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-28 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-28 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2018-09-28 08:41:42 | ROOF INSULATION AND ROOFING ATTACHMENT DEFERED UNTIL | | | SUB PERMIT APPLICATION. | | | | | | PROVIDE NOA 15-0922.06 FOR ROOF VENTS AS STATED IN | | | COMMENT RESPONSE SHEET DATED SEPTEMBER 18, 2018. | | | NOA 17-0727.01 TPO ROOFING - CONTRACTOR NEEDS TO CHOOSE | | | WHICH SYSTEM AND PROVIDE FRO ATTACHMENT OF COMPONANTS | | | OF THAT SYSTEM. | | | NOA 14-0708.07 FOR ROOF HATCH IS OK. | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-16 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-16 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2018-08-16 08:57:30 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051464 | | | REVIEWED: AUGUST 15, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. ON PRODUCT APPROVAL TPO ROOFING NOA 17-0727.01 | | | INDICATE WHICH SYSTEM IS BEING USED TO ACHIEVE DESIGN | | | LOAD, OR INDICATE TO DEFER ROOFING SUBMITTAL. | | | | | | 2. PROVIDE PRODUCT APPROVAL AND ATTACHMENT FOR ROOF | | | INSULATION, OR INDICATE THAT IT WILL BE DEFERRED. | | | DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO | | | INSTALLATION. | | | | | | 3. ON PRODUCT APPROVAL FOR ROOF VENTS. VERIFY THE | | | APPROVED APPLICATION WORKS FOR SPANISH TILE. I SEE | | | APPROVAL FOR SHINGLE AND STANDING SEAM. | | | | | | 4. SHOW ROOF FIRE CLASSIFICATION ON ROOFING PLAN | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-04 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-04 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2018-11-13 15:26:26 | 11/13/18 HARD COPY OF SURVEY IN LIBRARY. LEM |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2018-09-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-24 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-24 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2018-09-24 15:12:17 | 001-022 C-SHEETS - OK | | | 023 SURVEY - NO DIGITAL SIGNATURE AND NO IMPRESSION OF | | | SEAL ON THE SURVEY. | | | 024-029 L-SHEETS - OK | | | 030-074 A-SHEETS - OK | | | 075-089 S-SHEETS - OK | | | 090-094 M-SHEETS - OK | | | 095-100 P-SHEETS - OK | | | 101-112 E-SHEETS - NO DIGITAL SIGNATURE |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-08-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-14 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-08-14 17:29:05 | PLUMBING PAGES ARE NOT DIGITALLY SIGNED PER FAC | | | 61G15-23.003 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-30 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-30 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2018-07-30 07:08:13 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) DIGITAL | | | SIGNATURE STATUS ARE AS FOLLOWS: | | | | | | ARCHTECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND | | | SEALED. IT APPEARS THAT THE ARCHITECT (JAMES LALLI, RA) | | | HAS A DIGITAL SEAL AS THERE IS AN IMAGE OF THE DIGITAL | | | SEAL ON THE A SHEETS. | | | | | | STRUCTURAL SHEETS OK; DIGITALLY SIGNED & SEALED BY | | | DAVID A. BALMA, PE. SHEETS SUBMITTED NEXT REVIEW CYCLE | | | NEED VERIFICATION. | | | | | | MECHANICAL, PLUMBING SHEETS ARE NOT DIGITALLY SIGNED & | | | SEALED; DOES STEVEN J. VAZ, PE HAVE A DIGITAL SEAL? IF | | | YES, PLEASE HAVE HIM SEND A SAMPLE S&S PAGE VIA EMAIL | | | TO [email protected]. IF NO, PLEASE CONTACT ME REGARDING | | | HOW TO RESOLVE AFTER REVIEWS HAVE PASSED. | | | | | | ELECTRICAL DIGITALLY SIGNED AND SEALED PAGES HAVE AN | | | ERROR (CORRUPTED SIGNATURE, ADAM R. MUELLER, PE). THIS | | | MAY HAVE RESULTED DUE TO SOMEONE OPENING THE FILE AND | | | SAVING. AFTER ELECTRICAL REVIEW AND CHANGES MADE TO | | | PLAN PAGES ACCORDINGLY, PLEASE S&S AND SEND A SAMPLE | | | PAGE TO ME VIA EMAIL FOR SIGNATURE VERIFICATION, | | | [email protected]. | | | | | | 2. ENERGY CALCS (SUPPORTING DOCUMENTS FOLDER) ARE NOT | | | DIGITALLY SIGNED AND SEALED. | | | | | | 3. GEOTECHNICAL REPORT (SUPPORTING DOCUMENTS) IS NOT | | | DIGITALLY SIGNED AND SEALED. | | | | | | 4. STRUCTURAL CALCS (SUPPORTING DOCUMENTS) NOT | | | DIGITALLY SIGNED AND SEALED. | | | | | | IF A DESIGN PROFESSIONAL DOES NOT HAVE A DIGITAL SEAL, | | | A PAPER ORIGINAL SIGNED AND SEALED WILL BE REQUIRED | | | PRIOR TO PERMIT ISSUANCE. | | | | | | 5. NO CIVIL PLANS SUBMITTED (BUT WERE REFERRED TO ON | | | STRUCTURAL PAGES), NO SITE PLAN SUBMITTED, SO REVIEWERS | | | WILL NOT BE ABLE TO DO A COMPLETE REVIEW. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-10-02 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2018-10-02 14:54:13 | THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING | | | CONDITIONS: | | | | | | 1.) PRIOR TO THE ISSUANCE OF CERTIFICATE OF OCCUPANCY, | | | AN ACCESS EASEMENT SHALL BE RECORDED ON THE | | | SOUTHWESTERN CORNER OF THE SUBJECT PROPERTY. | | | 2.) APPLICANT SHALL PROVIDE ALL REQUIRED FDOT DRIVEWAY | | | PERMITS. | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-08-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-08-15 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2018-08-15 10:41:29 | THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING | | | CONDITIONS: | | | | | | 1.) AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION | | | WILL BE REQUIRED FROM THE ENGINEERING SERVICES | | | DEPARTMENT. | | | 2.) PRIOR TO THE ISSUANCE OF CERTIFICATE OF OCCUPANCY, | | | AN ACCESS EASEMENT SHALL BE RECORDED ON THE | | | SOUTHWESTERN CORNER OF THE SUBJECT PROPERTY. | | | 3.) APPLICANT SHALL PROVIDE ALL REQUIRED FDOT DRIVEWAY | | | PERMITS. | | | 4.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT ? PLANNING DIVISION. | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] | | | |
|
|