Plan Review Details - Permit 18051464
Plan Review Stops For Permit 18051464
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 15:38 Rev Time 0.00
Received By shill Date 2019-03-26 Time 15:38 Sent To  
Notes
2019-03-26 15:39:12AIPP SATISFIED PER S.WELTER EMAIL 3/21/19
 ROUTED EMAIL TO FILENET
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 08:40 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 08:20 Rev Time 0.00
Received By dbattles Date 2018-09-24 Time 14:05 Sent To  
Notes
2018-09-28 08:24:36****CORRECTIONS****
 W.P.B. PERMIT: 18051464
 REVIEWED: AUGUST 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-8. OK
  
 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS
 THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO
 HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS
 OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD
 ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED.
  
 8-2. CONTRACTOR STATED THAT THEY WOULD PROVIDE A
 GEOTECHNICAL REPORT PRIOR FILLING IN HOLE FROM THE FUEL
 TANK REMOVAL.
 SUPPLY REPORT, OR INDICATE THAT YOU WOULD LIKE IT TO BE
 A PROVISO.
  
  
 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE
 STRUCTURES.
 DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF
 APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE
 WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK.
 9-2. PROVIDE PERMIT NUMBER FOR THE DRIVE THRU CANOPY
 AND DUMPSTER ENCLOSURE.
  
 10-14. OK
  
 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED
 SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION.
  
 15-2. PROVISO:
 TRUSS SHOP DRAWINGS TO BE PROVIDED TO INSPECTOR PRIOR
 TO INSTALLATION.
  
 KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION.
 PLEASE PROVIDE REQUIREMENTS SET FORTH WATER
 INFILTRATION.
 [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL
 SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE
 THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED
 NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG
 RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 RESPONSE: THE KAWNEER?S 350 IR SIDE-HINGED DOORS NOA #
 15-0622.11 COMPLIES WITH FBC 1709.5.1 EXCEPTION: ?DOOR
 ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE THE
 DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER
 INFILTRATION NEED NOT BE TESTED FOR WATER
 INFILTRATION.? ACCORDING THE MANUFACUTURER THE KAWNEER
 DOOR IS DESIGNED TO ACCEPT WATER AND DETER IT BY THE
 BULB GASKETS ALONG THE PERIMETER FRAMING WHERE IT MEETS
 THE DOOR.
  
 15-2. I?M LOOKING AT NOA 15-0622.11 NOTE ON SHEET 1 OF
 9.
 IT STATES THAT THESE DOORS ARE NOT APPROVED FOR USE
 WHERE WATER INFILTRATION RESISTANCE IS REQUIRED.
 PLEASE PROVIDE REPONSE THAT DOESN?T INCLUDE THE DOORS
 MEETING REQUIREMENTS FOR WATER INFITRATION, BUT RATHER
 STATE HOW YOU ARE MEETING THE EXCEPTION REQUIRING THE
 AREA TO ACCEPT WATER INFILTRATION IN A NONHABITABLE
 AREA.
  
  
 16. OK.
  
 NEW COMMENT:
 17. PLEASE REPLACE NOA 16-0510.28 FOR ROOF VENTS WITH
 NOA 15-0922.06 FOR ROOF VENTS AS STATED IN COMMENT
 RESPONSE SHEET DATED SEPTEMBER 18, 2018.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 08:53 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 13:38 Sent To  
Notes
2018-08-16 08:55:36****CORRECTIONS****
 W.P.B. PERMIT: 18051464
 REVIEWED: AUGUST 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SOME OF THE UPLOADED DRAWINGS NAMING DESIGNATIONS
 DON?T MATCH THE SHEET PROVIDED. PLEASE RE-UPLOAD THE
 FOLLOWING ARCHITECTURAL DRAWINGS TO PROJECT DOX.
 A.01, A.02, A.03, A.04, A3.3, A3.4, A5.6 AND A5.7
  
 2. ALL CIVIL DRAWINGS WERE UPLOADED STARTING WITH THE
 SAME THREE DIGIT DESIGNATION AS ARCHITECTURAL DWG?S.
 THIS HAS CAUSED THE ARCHITECTURALS AND CIVIL PLANS TO
 GET MIXED IN TOGETHER.
 THE THREE DIGIT PREFIX SHOULD START AT 001 AND 001
 SHOULD NOT BE REPEATED.
 CIVIL PLANS SHOULD HAVE BEEN 001-021
 ARCHITECTURAL WOULD START AT 022
 TO FIX THIS WITHOUT RELOADING ALL PLANS PLEASE DELETE
 ALL CIVIL FILES (C1 THRU C21)RELOAD ALL CIVIL PLANS
 WITH THE FIRST THREE DIGIT AS 000. THIS WILL PUT THEM
 ALL AT THE TOP OF LIST, AND THE REST OF THE DRAWINGS
 WILL KEEP CURRENT DESIGNATIONS.
  
 3. SHEET C21 REFERENCES 2014 CODE FOR WIND LOADS.
 PLEASE UPDATE TO FBC 2017 6 TH EDITION WHEN SUBMITTING
 FOR SITE LIGHTING PERMIT.
  
 4. [FBC 107.2.5]PLEASE UPLOAD THE SURVEY TO SUPPORTING
 DOCUMENTS.
  
 5. A UNITY OF TITLE WILL BE NEEDED TO COMBINE THE TWO
 LOTS TOGETHER. CURRENTLY THERE ARE TWO PCN'S AND TWO
 ADDRESSES
  
 6. DEMO PERMIT FOR FUEL TANKS NEEDS TO BE CLOSED OUT
 PRIOR TO PERMIT ISSUANCE.
  
 7. THE STRUCTURAL REPORT IS A MULTI PAGE DOCUMENT. THE
 FIRST 55 PAGES ARE GOOD, BUT THE REMAINING 35 PAGES
 DON?T SHOW UP. PLEASE VERIFY THAT ALL 80 PAGES ARE
 PRESENT IN THE DOCUMENT AND RE-UPLOAD TO PROJECT DOX IF
 NEEDED.
  
 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS
 THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO
 HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS
 OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD
 ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED.
  
 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE
 STRUCTURES.
 DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF
 APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE
 WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK.
  
 10. SHEET A1.1 DETAIL CALL OUTS 2/A7.4 AND 3/A74 APPEAR
 TO BE FOR SIDE SUPPORT OF THE COILING DOOR, BUT THEY
 LEAD TO DETAIL OF SCALA SIGNAGE.
 UPDATE DETQAIL CALLOUTS AND PROVIDE DETAIL THEY WERE
 INTENDED TO SHOW.
 IS ANY ADDITIONAL SUPPORT NEEDED FOR THE DOOR AND MOTOR
 SUPPORTED ABOVE, IF SO PLEASE UPDATE STRUCTURAL TO
 INCORPORATE.
  
 11. SHEET S0.1 DESIGN AND LOADING. UPDATE THE CODE
 REFERENCE TO FBC 2017 6 TH EDITION.
  
 12. SHEET S.02 IN WIND DESIGN DATA ? UPDATE THE CODE
 REFERENCE TO FBC 2017 6 TH EDITION.
  
 13. PROVIDE ROOF DECKING ATTACHMENT/SPACING SCHEDULES
 FOR THE FLAT ROOF AND THE TOWER ROOF IN APPLICABLE
 ZONES FROM S0.2 WIND DATA SHEET. SECTIONS AND DETAILS
 SHOW SHEATHING DIFFERENTLY. UPDATE TO SHOW SHEATHING AS
 INTENDED.
  
 14. ROOF SUB PERMIT WILL BE REQUIRED(SEE ROOFING REVIEW
 FOR COMMENTS)
  
 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED
 SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION.
 KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION.
 PLEASE PROVIDE REQUIREMENTS SET FORTH WATER
 INFILTRATION.
 [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL
 SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE
 THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED
 NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG
 RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 16. PROVIDE ROOF DRAINAGE CALCULATIONS, OR IN RESPONSE
 LET ME KNOW WHERE THEY ARE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 12:26 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-08 Cont ID  
Sent By jpearson Date 2018-10-08 Time 08:00 Rev Time 0.00
Received By jpearson Date 2018-10-08 Time 08:00 Sent To  
Notes
2018-10-08 07:20:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PAGE E3.0 OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH
 ASHRSE 90.1 SECTION 8.4.2 PROVIDE RECEPTACLE CONTROL
 REQUIRED BY ASHREA 90.1: 8.4.2. FBC CE 405.7.1
 (RESPONSE LETTER STATES THIS IS NOT REQUIRED PER THE
 FBC ENERGY, WHICH IS INCORRECT. SEE FBC EC 405.6.1.
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1)
 3. E3.1 NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON
 ROOF. (SHEET M2.0 DOES NOT STATE IF THIS "CONVENIENCE
 OUTLET" IS GFCI PROTECTED PER CODE. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 210.8, 210.63)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
  
 NEW COMMENT:
  
 9. DIGITAL SIGNATURES ARE CORRUPTED. SEE COMMENTS UNDER
 SIGNATURE STOP. FS 471/481; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By jleahy Date 2018-08-07 Time 13:04 Rev Time 0.00
Received By jleahy Date 2018-08-07 Time 10:51 Sent To  
Notes
2018-08-07 14:35:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 E0.1
  
 TAP OFF MAIN TO POWER METER AND TO WAC SYSTEM HOW IS
 THIS GOING TO BE CONNECTED?
  
 BUILDING MANAGEMENT SYSTEM TO COMPLY WITH ARTICLE 750
 OF THE NEC
  
 PAGE E3.0
  
 OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH ASHRSE 90.1
 SECTION 8.4.2
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
  
 E3.1
  
 NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON ROOF.
  
 E7.0
  
 LOAD CACLUATION NOT CALCULATED PER 220 OF THE NEC
 THE ONE SHOWN ON E7.0 SHOWS LIGHTING LOAD OF 2.9KW?
  
 FAULT CURRENT CALCULATION REQUIRED FOR ALL SERVICE
 EQUIPMENT AND DOWN STREAM PANELS
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM
 THE STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10
  
 PROVIDE ENERGY CALCULATION FOR THE INTERIOR LIGHTING.
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 12:27 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 12:27 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rrossano Date 2018-10-29 Time   Rev Time 0.00
Received By rrossano Date 2018-10-29 Time   Sent To I
Notes
2018-10-29 12:59:57FORMAL ENGINEERING APPROVAL ON 9/27/18 FOR PLANS DATED
 8/20/2018.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 06:39 Rev Time 0.00
Received By shill Date 2018-07-30 Time 06:39 Sent To  
Notes
2018-07-30 06:40:05CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-11-21 Cont ID  
Sent By pleduc Date 2018-11-20 Time   Rev Time 0.00
Received By pleduc Date 2018-11-20 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By pleduc Date 2018-09-24 Time   Rev Time 0.00
Received By pleduc Date 2018-09-24 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-06 Cont ID  
Sent By pleduc Date 2018-07-06 Time   Rev Time 0.00
Received By pleduc Date 2018-06-27 Time 08:40 Sent To  
Notes
2018-07-06 12:57:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 2.1 - THIS PLAN SHEET IS INDICATED AS LIFE
 SAFETY PLAN AND DETAILS.
  
 BE ADVISED, THIS PLAN INDICATED ACCESSIBILITY DETAILS
 WITH NO LIFE SAFETY.
  
 PLEASE REVIEW AND PROVIDE AN ACCURATE LIFE SAFETY PLAN
 AND DETAILS.
  
  
  
  
 2) SHEET A 2.1 - THERE ARE INDICATIONS OF THE HARDWARE
 ON THE MAIN ENTRY DOORS OF MORTISE CYLINDERS.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACIES AND
 CHAPTER 7, MEANS OF EGRESS:
  
 38.2.2 MEANS OF EGRESS COMPONENTS.
 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE
 LIMITED
 TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12.
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 AND
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE REVIEW, CORRECT OR PROVIDE SPECIFIC DETAILS OF
 COMPLIANCE
  
  
  
 3) SHEET A 2.1 - THERE ARE INDICATIONS OF A PANIC BAR
 ON THE ENTRY DOORS.
  
 PER NFPA 101, CHAPTER 7
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 AND
  
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER
 THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS
 OTHERWISE PROVIDED
 IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED WITH ANY
 LOCKING
 DEVICE, SET SCREW, OR OTHER ARRANGEMENT THAT PREVENTS
 THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
  
 THOUGH PANIC HARDWARE IS NOT REQUIRED FOR THIS
 OCCUPANCY, IF INSTALLED, IT MUST BE INSTALLED PER THE
 APPLICABLE CODE.
  
 PLEASE REVIEW AND REMOVE THE PANIC BAR OR EXPLAIN WITH
 SPECIFC DETAILS AND FIRE CODE REFERENCES.
  
  
  
 4) SHEET A 2.1 - THERE ARE INDICATIONS OF ELECTROINC
 LOCKS OR STRIKES WITHIN THE DOOR SCHEDULE.
  
 NO DOOR SHALL BE LOCKED AGAINST EGRESS.
  
 ALL ACCESS AND/OR EGRESS CONTROL SHALL BE COMPLY WITH
 THE APPLICABLE REQUIREMENTS FO NFPA 101, CHAPTER 7,
 MEANS OF EGRESS AND BE SUBMITTED UNDER A SEPARATE SHOP
 DRAWING PERMIT.
  
 PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 12:27 Rev Time 0.00
Received By jleahy Date 2018-11-14 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By shill Date 2018-10-30 Time 10:50 Rev Time 0.00
Received By shill Date 2018-09-20 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 08:59 Rev Time 0.00
Received By dbattles Date 2018-06-25 Time 10:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 15:07 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 12:34 Sent To  
Notes
2018-12-04 15:44:44IMPACT FEE REVIEW DONE UNDER FOUNDATION PERMIT
 18101214, OK PER DBATTLES
2018-12-04 12:34:16EMAILED IMPACT FEE OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 08:46 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 08:46 Sent To  
Notes
2018-09-28 08:48:25COMMENT CARRIED FROM FIRST REVIEW.
  
 [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 06:54 Rev Time 0.00
Received By shill Date 2018-07-30 Time 06:54 Sent To  
Notes
2018-07-30 06:56:06****CORRECTIONS****
 REVISED 8/2/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By ccole Date 2018-10-18 Time 10:51 Rev Time 0.00
Received By ccole Date 2018-10-18 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By ccole Date 2018-07-31 Time 16:20 Rev Time 0.00
Received By ccole Date 2018-07-31 Time 16:19 Sent To  
Notes
2018-07-31 16:54:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051464
 7/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-17 EC INCLUDING THE
 RTU'S AND FAN COIL SYSTEMS.
  
 2) THE COMCHECK ENERGY COMPLIANCE CERTIFICATE, AND THE
 MECHANICAL PLANS ARE NOT ELECTRONICALLY SIGNED AND
 SEALED AS REQUIRED BY SECTION 61G15-23.005 FAC.
  
 3) SHEET M1.1: PROVIDE WIND LOAD ENGINEERING FOR TIE
 DOWN OF THE RTU'S - SECTION 301.15. INCLUDE THE DESIGN
 CRITERIA IN ACCORDANCE WITH SECTION 1609 FBC B, AND
 COMPLETE DETAILS FOR ANCHORING THE CURBS TO THE
 STRUCTURE, AND MOUNTING THE UNITS TO THE CURBS.
  
 4) M1.1: SHOW THE CONDENSATE PIPING RUNS AND DISCARGE
 LOCATIONS. PLEASE INDICATE THE SIZE OF THE PIPING, AND
 SHOW HOW THE PIPING WILL BE SUPPORTED ABOVE THE ROOF
 AND THE TYPE AND SPACING OF THE PIPE SUPPORTS.
  
 5) SUBMIT THE FL. PRODUCT APPROVAL # 16921.1-R3 FOR THE
 CONDENSER ROOF STAND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By gjohnson Date 2018-10-29 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2018-10-29 Time 15:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 10:03 Rev Time 0.00
Received By gjohnson Date 2018-08-14 Time 14:32 Sent To  
Notes
2018-08-15 10:14:241ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THERE IS AN OUTSTANDING PERMIT FOR REMOVAL OF THE
 OLD FUEL TANKS PERMIT # 18010008 THIS PERMIT SHALL BE
 FINAL OUT AND CLOSED BEFORE THE BUILDING PERMIT CAN BE
 ISSUED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-09-28 Cont ID  
Sent By dbattles Date 2018-09-28 Time 08:30 Rev Time 0.00
Received By dbattles Date 2018-09-28 Time 08:30 Sent To  
Notes
2018-09-28 08:41:42ROOF INSULATION AND ROOFING ATTACHMENT DEFERED UNTIL
 SUB PERMIT APPLICATION.
  
 PROVIDE NOA 15-0922.06 FOR ROOF VENTS AS STATED IN
 COMMENT RESPONSE SHEET DATED SEPTEMBER 18, 2018.
 NOA 17-0727.01 TPO ROOFING - CONTRACTOR NEEDS TO CHOOSE
 WHICH SYSTEM AND PROVIDE FRO ATTACHMENT OF COMPONANTS
 OF THAT SYSTEM.
 NOA 14-0708.07 FOR ROOF HATCH IS OK.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 08:56 Rev Time 0.00
Received By dbattles Date 2018-08-16 Time 08:55 Sent To  
Notes
2018-08-16 08:57:30****CORRECTIONS****
 W.P.B. PERMIT: 18051464
 REVIEWED: AUGUST 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ON PRODUCT APPROVAL TPO ROOFING NOA 17-0727.01
 INDICATE WHICH SYSTEM IS BEING USED TO ACHIEVE DESIGN
 LOAD, OR INDICATE TO DEFER ROOFING SUBMITTAL.
  
 2. PROVIDE PRODUCT APPROVAL AND ATTACHMENT FOR ROOF
 INSULATION, OR INDICATE THAT IT WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 3. ON PRODUCT APPROVAL FOR ROOF VENTS. VERIFY THE
 APPROVED APPLICATION WORKS FOR SPANISH TILE. I SEE
 APPROVAL FOR SHINGLE AND STANDING SEAM.
  
 4. SHOW ROOF FIRE CLASSIFICATION ON ROOFING PLAN
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 08:41 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 08:09 Sent To  
Notes
2018-11-13 15:26:2611/13/18 HARD COPY OF SURVEY IN LIBRARY. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-09-24 Cont ID  
Sent By dbattles Date 2018-09-24 Time 15:06 Rev Time 0.00
Received By dbattles Date 2018-09-24 Time 14:05 Sent To  
Notes
2018-09-24 15:12:17001-022 C-SHEETS - OK
 023 SURVEY - NO DIGITAL SIGNATURE AND NO IMPRESSION OF
 SEAL ON THE SURVEY.
 024-029 L-SHEETS - OK
 030-074 A-SHEETS - OK
 075-089 S-SHEETS - OK
 090-094 M-SHEETS - OK
 095-100 P-SHEETS - OK
 101-112 E-SHEETS - NO DIGITAL SIGNATURE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-14 Cont ID  
Sent By gjohnson Date 2018-08-14 Time 17:26 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2018-08-14 17:29:05PLUMBING PAGES ARE NOT DIGITALLY SIGNED PER FAC
 61G15-23.003
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 07:08 Rev Time 0.00
Received By shill Date 2018-07-30 Time 06:56 Sent To  
Notes
2018-07-30 07:08:13SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) DIGITAL
 SIGNATURE STATUS ARE AS FOLLOWS:
  
 ARCHTECTURAL SHEETS ARE NOT DIGITALLY SIGNED AND
 SEALED. IT APPEARS THAT THE ARCHITECT (JAMES LALLI, RA)
 HAS A DIGITAL SEAL AS THERE IS AN IMAGE OF THE DIGITAL
 SEAL ON THE A SHEETS.
  
 STRUCTURAL SHEETS OK; DIGITALLY SIGNED & SEALED BY
 DAVID A. BALMA, PE. SHEETS SUBMITTED NEXT REVIEW CYCLE
 NEED VERIFICATION.
  
 MECHANICAL, PLUMBING SHEETS ARE NOT DIGITALLY SIGNED &
 SEALED; DOES STEVEN J. VAZ, PE HAVE A DIGITAL SEAL? IF
 YES, PLEASE HAVE HIM SEND A SAMPLE S&S PAGE VIA EMAIL
 TO [email protected]. IF NO, PLEASE CONTACT ME REGARDING
 HOW TO RESOLVE AFTER REVIEWS HAVE PASSED.
  
 ELECTRICAL DIGITALLY SIGNED AND SEALED PAGES HAVE AN
 ERROR (CORRUPTED SIGNATURE, ADAM R. MUELLER, PE). THIS
 MAY HAVE RESULTED DUE TO SOMEONE OPENING THE FILE AND
 SAVING. AFTER ELECTRICAL REVIEW AND CHANGES MADE TO
 PLAN PAGES ACCORDINGLY, PLEASE S&S AND SEND A SAMPLE
 PAGE TO ME VIA EMAIL FOR SIGNATURE VERIFICATION,
 [email protected].
  
 2. ENERGY CALCS (SUPPORTING DOCUMENTS FOLDER) ARE NOT
 DIGITALLY SIGNED AND SEALED.
  
 3. GEOTECHNICAL REPORT (SUPPORTING DOCUMENTS) IS NOT
 DIGITALLY SIGNED AND SEALED.
  
 4. STRUCTURAL CALCS (SUPPORTING DOCUMENTS) NOT
 DIGITALLY SIGNED AND SEALED.
  
 IF A DESIGN PROFESSIONAL DOES NOT HAVE A DIGITAL SEAL,
 A PAPER ORIGINAL SIGNED AND SEALED WILL BE REQUIRED
 PRIOR TO PERMIT ISSUANCE.
  
 5. NO CIVIL PLANS SUBMITTED (BUT WERE REFERRED TO ON
 STRUCTURAL PAGES), NO SITE PLAN SUBMITTED, SO REVIEWERS
 WILL NOT BE ABLE TO DO A COMPLETE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-10-02 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-02 Time 14:53 Sent To  
Notes
2018-10-02 14:54:13THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING
 CONDITIONS:
  
 1.) PRIOR TO THE ISSUANCE OF CERTIFICATE OF OCCUPANCY,
 AN ACCESS EASEMENT SHALL BE RECORDED ON THE
 SOUTHWESTERN CORNER OF THE SUBJECT PROPERTY.
 2.) APPLICANT SHALL PROVIDE ALL REQUIRED FDOT DRIVEWAY
 PERMITS.
  
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-08-15 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-15 Time 10:40 Sent To  
Notes
2018-08-15 10:41:29THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING
 CONDITIONS:
  
 1.) AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION
 WILL BE REQUIRED FROM THE ENGINEERING SERVICES
 DEPARTMENT.
 2.) PRIOR TO THE ISSUANCE OF CERTIFICATE OF OCCUPANCY,
 AN ACCESS EASEMENT SHALL BE RECORDED ON THE
 SOUTHWESTERN CORNER OF THE SUBJECT PROPERTY.
 3.) APPLICANT SHALL PROVIDE ALL REQUIRED FDOT DRIVEWAY
 PERMITS.
 4.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING DIVISION.
  
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]
  