| 2018-06-20 15:18:34 | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS |
| | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| | G2413.4.2. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS |
| | WHICH MODEL REGULATOR IS BEING INSTALLED AND THE |
| | ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE |
| | THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1, |
| | 2017 FBC-RES. SEC. G2421.1. |
| | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | 6) THE PLANS REFER TO AN EXISTING GAS METER. THERE ARE |
| | NO RECORDS ON FILE WITH THE CITY FOR A GAS PERMIT FOR |
| | THIS ADDRESS. ANY PREVIOUS GAS INSTALLATION SHALL BE |
| | PERMITTED. WPB AMEND. TO FBC SEC. 105.1. |
| | 7) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | 10) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET |
| | OF THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBCR SEC. G2420.4. |
| | 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL |
| | GAS SEC. 411.1.3.2. |
| | 13) THE GAS PERMIT APPLICATION HAS THE ELECTRICAL |
| | CONTRACTOR'S LICENSE NUMBER ON IT. AN ELECTRICAL |
| | CONTRACTOR CANNOT INSTALL GAS UNLESS HE IS LICENSED IN |
| | THAT CATEGORY. AN ELECTRICAL CONTRACTOR'S LICENSE DOES |
| | NOT ALLOW YOU TO INSTALL GAS PIPING. FL. STATUTE |
| | 489.505 |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |