Plan Review Details - Permit 18051411
Plan Review Stops For Permit 18051411
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By shill Date 2018-08-15 Time 07:59 Rev Time 0.00
Received By shill Date 2018-08-14 Time 18:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 15:17 Rev Time 0.00
Received By shill Date 2018-08-09 Time 15:17 Sent To  
Notes
2018-08-09 15:17:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. C5 WIND SPEED IS SHOWN AS 160 MPH (VULT), RISK
 CATEGORY II. ADVISE HOW THIS WAS DETERMINED; IF RISK
 CATEGORY II THIS SHOULD BE A MINIMUM OF 167, AND 179
 FOR RISK CATEGORY III-IV. FBC B 1609.
  
 2ND REVIEW, NOT ADDRESSED. PLEASE REVISE TO A MINIMUM
 OF 167MPH, EXPOSURE C.
  
 2-3. OK
  
 NEW COMMENT: INFORMATIONAL ONLY - A CONTRACT WAS
 PROVIDED. IT APPEARS THAT LANDSCAPING, FENCING WAS
 INCLUDED IN THE VALUE OF THIS PERMIT. BOTH SHOULD BE A
 SEPARATE PERMIT WITH SEPARATE FEES. VALUE HAS BEEN
 ADJUSTED, RESULTING IN A CREDIT.
  
 PLEASE SUBMIT AN APPLICATION FOR EITHER LANDSCAPING OR
 FENCING AT THIS TIME SO THE CREDIT CAN BE TRANSFERRED.
 IF THE PERMIT DOCUMENTS FOR THESE ITEMS ARE NOT YET
 AVAILABLE, A PERMIT APPLICATION NUMBER CAN STILL BE
 GENERATED (WITH A PERMIT APPLICATION) AND WILL BE
 RETAINED AT THE BUILDING DIVISION UNTIL THE TIME THAT
 YOU ARE READY TO PROVIDE PERMIT DOCUMENTS.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 18:12 Rev Time 0.00
Received By shill Date 2018-06-16 Time 18:12 Sent To  
Notes
2018-06-16 18:13:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. C5 WIND SPEED IS SHOWN AS 160 MPH (VULT), RISK
 CATEGORY II. ADVISE HOW THIS WAS DETERMINED; IF RISK
 CATEGORY II THIS SHOULD BE A MINIMUM OF 167, AND 179
 FOR RISK CATEGORY III-IV. FBC B 1609.
  
 2. C5, RISK CATEGORY IS SHOWN AS II. SEE FBC B TABLE
 1604.5, THIS APPEARS TO BE RISK CATEGORY IV ("OTHER
 FACILITIES REQUIRED FOR EMERGENCY RESPONSE").
  
 3. THE STRUCTURAL ENGINEER PROVIDED CALCULATIONS AND
 DESIGN FOR A POLE DESIGNED TO ANSI/TIA 222 G2. THIS IS
 IN CONFLICT WITH THE OTHER ENGINEER'S DESIGN CRITERIA,
 PLEASE CORRELATE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 10:20 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By jpearson Date 2018-06-21 Time 17:16 Rev Time 0.00
Received By jpearson Date 2018-06-21 Time 16:32 Sent To I
Notes
2018-06-21 17:16:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 4. PLAN DOES NOT SHOW ANY FEEDERS OR BRANCH CIRCUITS
 FOR TOWER FROM METER CENTER. WILL THESE BE INSTALLED
 UNDER SEPARATE PERMITS? IS THERE ANY ILLUMINATION TO BE
 PROVIDED FOR THE AREA? PLEASE CLARIFY. WPB FBC 107.2.1
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2018-08-15 Cont ID  
Sent By mGONZALE Date 2018-08-15 Time   Rev Time 1.00
Received By mgonzale Date 2018-08-15 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 15:19 Rev Time 0.00
Received By shill Date 2018-08-09 Time 15:19 Sent To  
Notes
2018-08-09 15:19:41CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By shill Date 2018-06-20 Time 12:15 Rev Time 0.00
Received By shill Date 2018-06-20 Time 12:15 Sent To  
Notes
2018-06-20 12:15:55CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-08-16 Cont ID  
Sent By pleduc Date 2018-08-16 Time   Rev Time 0.00
Received By pleduc Date 2018-08-15 Time 12:11 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By pleduc Date 2018-07-25 Time   Rev Time 0.00
Received By pleduc Date 2018-07-24 Time 10:04 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By pleduc Date 2018-06-07 Time   Rev Time 0.00
Received By pleduc Date 2018-06-05 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-17 Cont ID  
Sent By cpuell Date 2018-08-17 Time 13:41 Rev Time 0.00
Received By cpuell Date 2018-08-13 Time 16:21 Sent To  
Notes
2018-08-14 16:22:12RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 15:19 Rev Time 0.00
Received By shill Date 2018-07-19 Time 15:50 Sent To  
Notes
2018-07-20 15:50:32B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-31 Time 09:58 Sent To  
Notes
2018-06-01 09:59:15B25

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By eschneid Date 2018-07-26 Time 16:08 Rev Time 0.25
Received By eschneid Date 2018-07-26 Time 16:08 Sent To  
Notes
2018-07-26 16:18:33SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING, WHICH MUST BE INSTALLED AND PASS INSPECTION,
 PRIOR TO THE FINAL INSPECTION PASS FOR THE TOWER.
  
 A. FENCE PERMIT
 B. LANDSCAPE PERMIT
  
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By eschenid Date 2018-06-12 Time 11:11 Rev Time 0.75
Received By eschneid Date 2018-06-12 Time 10:18 Sent To  
Notes
2018-06-12 11:11:51FAILED
  
 1) THE TOWER AND THE ENCLOSURE LOCATION MEET THE
 WIRELESS COMMUNICATION FACILITIES APPROVAL.
  
 2) PLEASE EXPLAIN THE "PROPOSED PARKING" SPACE. THE
 FIRE STATION SITE HAS EXCESS PARKING, SO A SERVICE
 VEHICLE MAY UTILIZE ONE OF THESE SPACES AS THE REQUIRED
 PARKING SPACE FOR THE FACILITY. THE CITY'S WIRELESS
 REGULATIONS STATE, "ONE PARKING SPACE IS REQUIRED FOR
 EACH TOWER DEVELOPMENT AREA. THE SPACE SHALL BE
 PROVIDED WITHIN THE LEASED AREA, OR EQUIPMENT COMPOUND
 OR THE DEVELOPMENT AREA AS DEFINED ON THE SITE PLAN."
 THE PROPOSES PARKING SPACE IS NOT SHOWN WITHIN THE
 LEASED AREA OR THE EQUIPMENT COMPOUND, SO ON THIS SITE
 IT IS PERMITTED IN THE CURRENTLY PROVIDED PARKING
 SPACES. STAFF DOES NOT WISH TO SEE THE ADDITIONAL
 PAVEMENT THAT WOULD BE REQUIRED TO INSTALL A NEW
 PARKING SPACE IN THE LOCATION SHOWN ON THE SITE PLAN.
 ADDITIONALLY, THE PLANS WOULD NEED TO BE REVISED TO
 ACCURATELY DEPICT A CODE COMPLIANT PARKING SPACE. IF
 THE SPACE IS TO BE REMOVED, ZONING STAFF WILL RED-LINE
 THE PLANS TO SHOW IT REMOVED.
  
 3) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING, WHICH MUST BE INSTALLED AND PASS INSPECTION,
 PRIOR TO THE FINAL INSPECTION PASS FOR THE TOWER.
  
 A. FENCE PERMIT
 B. LANDSCAPE PERMIT
 C. IRRIGATION PERMIT
 D. PARKING LOT/STRIPING PERMIT (SUBJECT TO THE
 RESOLUTION OF NO. 2 ABOVE)
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]