| Plan Review Stops For Permit 18051332 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2018-08-25 19:24:12 | PROVISO - 18" PULL SIDE REQUIRED FOR GATES | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-28 |
Time |
19:20 |
Sent To |
|
|
| Notes |
| 2018-06-29 07:37:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. A1, POSSIBLY OTHER PAGES, SOME REVISION CLOUDS ARE | | | LIGHT, OTHERS DARK, SOME NOT NUMBERED. TYPICALLY NEW | | | UNREVIEWED CLOUDS ARE DARK, OLD PREVIOUSLY REVIEWED | | | CLOUDS ARE LIGHT GREY OR REMOVED. IT APPEARS THAT I | | | SHOULD BE REVIEWING REVISION 3 ONLY, BUT SOME REVISION | | | 3 ARE LIGHT, OTHERS DARK, SOME CLOUDS ARE UNNUMBERED, | | | SO IT IS DIFFICULT TO DETERMINE WHAT HAS CHANGED. FBC | | | 107, PLEASE CLARIFY. | | | | | | 2. SEE PLUMBING ACCESSIBILITY COMMENTS AS THEY ARE | | | APPLICABLE FOR BUILDING REVIEW. | | | | | | 3. GATE AT THE WEST CENTER OF THE BUILDING APPEARS TO | | | LACK THE 18" MANEUVERING CLEARANCE REQUIRED, SEE ANSI | | | 117.1 2009 404.2, TABLE 404.2.3.2, FBC A FIGURE | | | 404.2.4.1(A). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-17 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-17 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2018-08-17 10:58:52 | ITEM CORRECTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-21 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-21 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2018-06-21 15:42:52 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NARRATIVE AND PLAN SHOW MANY ITEMS BEING ADDED, BUT | | | PLAN REVISION APPLICAITON STATES THERE IS NO INCREASE | | | IN VALUE. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE | | | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. | | | FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-08-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-08-06 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-08-06 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-06-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-08 |
Time |
08:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-08-30 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-08-02 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-29 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-12 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-11 |
Time |
17:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-24 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-24 |
Time |
06:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-25 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-25 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2018-06-25 11:57:57 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. ON THE APPROVED SET OF PLANS IT SHOWED WING WALLS | | | NEXT TO WATER FOUNTAIN THE REVISION HAS REMOVED THOSE | | | WALLS THE WATER FOUNTAIN SHALL COMPLY WITH 307.2 . PER | | | FBC ACC 602.1 | | | | | | 2. THE NEW SINK IN THE COVERED PATIO SHALL COMPLY WITH | | | FBC ACC 606.2, 606.3 | | | | | | 3. THE NEW SINK UNDER THE COVERED PATIO APPEARS TO BE | | | OVER 50' FROM THE HOT WATER SOURCE A RECIRCULATION | | | SYSTEM WILL BE REQUIRED FOR THE HOT WATER. PER FBC PL | | | 607.2 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
2018-08-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-08-29 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2018-08-29 09:45:12 | THIS APPROVAL IS GRANTED SUBJECT TO THE FOLLOWING | | | CONDITIONS: | | | | | | 1.) APPLICANT SHALL PROVIDE A REVISED LANDSCAPE PLAN | | | SHOWING SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND | | | UTILIZES ADDED AS SHOWN ON THE SITE PLAN. A NOTE WAS | | | ADDED TO PROVIDE SCREENING AT CONSTRUCTION | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
2018-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-06-15 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2018-06-20 15:36:36 | REQUIRES APPROVAL OF MINOR PD AMENDMENT | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|