| 2018-06-20 08:50:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR | | | G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE | | | SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | | AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT | | | BE USED WITH THIS GENERATOR. FBC-R 301.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-23 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-23 |
Time |
06:54 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-06-07 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-06-07 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2018-06-07 06:34:52 | ROUTED TO GENERATOR/POOLS INBOX. | | | | | | VALUE ADJUSTED TO 16500$ | | | | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-26 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-26 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-03 |
Time |
06:00 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-03 |
Time |
05:40 |
Sent To |
|
|
| Notes |
| 2018-06-03 06:00:37 | 1) ) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PRESSURE REGULATORS. THE | | | REGULATORS SHALL BE IN COMPLIANCE WITH 2017 FBCR-SEC. | | | G2421.1, G2421.2 (1-7). IDENTIFY WHICH MODEL REGULATOR | | | IS BEING INSTALLED. | | | 2) THE SHUTOFF VALVE FOR THE EXISTING PIPING INTO THE | | | STRUCTURE SHALL BE LOCATED UPSTREAM (AHEAD) OF THE MP | | | REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4, 2017 | | | FBC-RES. SEC. G2420.4. | | | 3) A REGULATOR IS REQUIRED AT THE EXISTING POOL HEATER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-30 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2018-07-17 14:03:52 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2018-05-30 13:44:34 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-19 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-19 |
Time |
13:04 |
Sent To |
E |
|
| Notes |
| 2018-07-19 13:08:31 | NOTE - GENRATOR SHALL BE AT LEAST 3.5 ' FROM SIDE | | | PROPERTY LINE. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | 561-822-1442 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-05-31 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-05-31 |
Time |
16:01 |
Sent To |
B |
|
| Notes |
| 2018-05-31 16:13:17 | NOTE - SHALL BE AT LEAST 3.5 ' FROM SIDE PROPERTY | | | LINES. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | 561-822-1442 | | | [email protected] |
|
|