Plan Review Details - Permit 18051302
Plan Review Stops For Permit 18051302
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By hmoser Date 2018-06-20 Time 09:00 Rev Time 0.00
Received By hmoser Date 2018-06-15 Time 12:55 Sent To  
Notes
2018-06-18 12:55:33RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-05 Cont ID  
Sent By hmoser Date 2018-06-05 Time 09:25 Rev Time 0.00
Received By hmoser Date 2018-05-29 Time 15:32 Sent To  
Notes
2018-05-30 15:32:48MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By hmoser Date 2018-06-20 Time 08:59 Rev Time 0.00
Received By hmoser Date 2018-06-20 Time 08:59 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By hmoser Date 2018-06-05 Time 09:25 Rev Time 0.00
Received By hmoser Date 2018-06-05 Time 09:11 Sent To I
Notes
2018-06-05 09:25:13PLAN DENIED
 1) REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING.
 ENERGY CALCULATIONS REQUIRED 2017 RESIDENTIAL CODE
 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DELTA
 SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE
 DESIGN. CITY OF WEST PALM BEACH AMENDMENTS 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676