Plan Review Details - Permit 18051275
Plan Review Stops For Permit 18051275
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 18:48 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 18:48 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By jpearson Date 2018-06-27 Time 16:05 Rev Time 0.00
Received By jpearson Date 2018-06-27 Time 16:05 Sent To  
Notes
2018-06-27 16:05:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS CCTV CABLE AND POWER WIRING INSIDE POLE.
 PROVIDE SEPARATION OF WIRING PER NEC 725.136.
 2. PROVIDE CUT SHEET FOR CAMERAS TO CONFIRM LISTING.
 NEC 110.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-18 Time 07:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By cpuell Date 2018-06-28 Time 16:54 Rev Time 0.00
Received By cpuell Date 2018-06-05 Time 14:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-06-27 Cont ID  
Sent By jpearson Date 2018-06-27 Time 16:06 Rev Time 0.00
Received By jpearson Date 2018-06-27 Time 16:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By eschneid Date 2018-07-26 Time 14:56 Rev Time 0.25
Received By eschneid Date 2018-07-26 Time 14:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By eschenid Date 2018-06-28 Time 11:56 Rev Time 0.50
Received By eschneid Date 2018-06-28 Time 11:56 Sent To  
Notes
2018-06-28 14:59:18FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE ADDRESS FOR THIS PERMIT IS 429 59TH STREET. THE
 WORK SHOWN ON SHEET E-2 IS PHYSICALLY BEING DONE ON THE
 PROPERTY HAVING THE ADDRESS OF 6000 N. FLAGLER DRIVE
 AND WITHIN RIVIERA BEACH (CONNECTION TO THE BUILDING).
 PLEASE VERIFY WITH THE CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DIVISION THAT SEPARATE PERMITS
 FOR EACH PARCEL ARE NOT REQUIRED AND ENSURE THAT THE
 WORK WITHIN RIVIERA BEACH IS PERMITTED THROUGH THEM.
  
 2) SHEET E-2 SHOWS CONDUIT INSTALLED THOUGH THE
 LANDSCAPE BUFFER. THERE ARE EXISTING AND PROPOSED TREES
 IN THIS BUFFER. PROVIDE VERIFICATION ON THE APPROVED
 LANDSCAPE PLAN THAT THE CONDUIT LOCATIONS WILL NOT
 INTERFERE WITH THE EXISTING OR PROPOSED TREES AND THEIR
 ROOT SYSTEMS.
  
 3) SHEET E-3 SHOWS CONDUIT INSTALLED THOUGH THE
 LANDSCAPE LANDSCAPE ISLANDS. THERE ARE EXISTING AND
 PROPOSED TREES IN THESE LANDSCAPE ISLANDS. PROVIDE
 VERIFICATION ON THE APPROVED LANDSCAPE PLAN THAT THE
 CONDUIT LOCATIONS WILL NOT INTERFERE WITH THE EXISTING
 OR PROPOSED TREES AND THEIR ROOT SYSTEMS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  
  
  