| Plan Review Stops For Permit 18051263 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-11 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-11 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2018-09-11 11:39:02 | PROVISO: | | | SEE ROOF REVIEW FOR ADDITIONAL ITEMS TO SUBMIT WITH | | | ROOFING SUB PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-29 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2018-06-29 17:36:29 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051263 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC R = FBC RESIDENTIAL | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS | | | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT | | | SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED. | | | | | | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET | | | OF PLANS TO TAKE TO THE COUNTY. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | 2. NOTICE OF ACCEPTANCE(N.O.A.) | | | N.O.A. 14-0610.05 IS EXPIRED. PLEASE PROVIDE TWO COPIES | | | OF UPDATED N.O.A. | | | | | | 3. SHEET A-5 REFERENCES N.O.A. NO. 17-1018.05 FOR | | | WINDOWS. PROVIDE N.O.A. FOR WINDOWS AND MULL BAR. | | | HAVE THE DESIGNER OF RECORD MARK THE SELECTED WINDOWS, | | | ATTACHMENT TYPE AND STAMP AS REVIEWED. | | | | | | 4. SUPPLY ROOFING PRODUCT APPROVAL, OR INDICATE ON YOUR | | | COMMENT RESPONSE SHEET THAT THEY WILL BE A SUBMITTAL AT | | | A LATER DATE. | | | | | | 5. [FBC R401.2] DETERMINE UPLIFT THAT THE FOOTER WILL | | | RESIST FOR LIGHT FRAME CONSTRUCTION USING TABLE R401.1. | | | PROVIDE TYPE OF CONNECTOR AT BASE PLATE FOR THE | | | DETERMINED UPLIFT, OR SHOW ON CONNECTOR SCHEDULE HOW | | | THE SST-MST16 MEETS NAILING REQUIRMENTS. | | | | | | 6. [FBC R403.1.4]FOOTER TO HAVE MINIMUM 12" DEPTH BELOW | | | GRADE AND 4" ABOVE GRADE. | | | | | | 7. [FBC R401.3]PROVIDE DRAINAGE FROM FOUNDATION AS | | | OUTLINED IN R401.3 | | | | | | 8. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO | | | BE USED TO MEET REQUIREMNETS OF R703.4 | | | | | | NOTE: | | | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS | | | SUBMITTED AND A COMMENT RESPONSE SHEET. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-10-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-26 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-26 |
Time |
15:04 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-10-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-07 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-07 |
Time |
09:02 |
Sent To |
P |
|
| Notes |
| 2018-10-07 09:02:40 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES | | | NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES | | | WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 (A LOAD CALCULATION SHOULD SHOW | | | ALL LOADS AND THE CORRESPONDING VA FOR THAT LOAD. THIS | | | SHOULD BE COMPLETED IN THE FORMAT PROVIDED IN THE FBC | | | RESIDENTIAL. THE PARTIAL LOAD CALCULATION PROVIDED IS | | | NOT ACCEPTABLE.) | | | 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER | | | PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND | | | DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE. | | | PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, | | | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 (WHAT IS SHOWN ON THE RISER | | | DIAGRAM IS NOT THE SAME AS SHOWN ON PLAN. PROVIDE | | | CORRECTION. RISER DIAGRAM SHOWS A FEED FROM THE METER | | | TO THE INTERIOR PANEL WHICH IS LOCATED IN THE UTILITY. | | | CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR | | | DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE | | | IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE | | | OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. | | | PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6 | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | NEW COMMENT: | | | | | | 7. PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN | | | ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW, | | | IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN | | | FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS | | | REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. THE ADDITIONAL | | | FEE FOR THIS PLAN WILL BE $950.00 . FS 553.80(2)(B) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-08-28 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-08-28 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-08-28 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2018-08-28 10:38:02 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES | | | NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES | | | WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 | | | 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER | | | PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND | | | DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE. | | | PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, | | | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-25 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-22 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2018-06-25 10:31:12 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES | | | NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES | | | WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 | | | 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER | | | PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND | | | DISCONNECT LOCATED OUTSIDE, AND A 125 AMP PANEL INSIDE. | | | PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, | | | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 3. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP | | | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. PLAN | | | ONLY SHOWS THIS IN ONE OF THE BATHROOMS. PROVIDE | | | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE | | | E3703.4, E3901.6 | | | 4. BREAKER FOR WATER HEATER IS SHOWN AS 50 AMP. FOR THE | | | LOAD SPECIFIED OF 4500 WATTS, A BREAKER OF 25 OR 30 | | | AMPS SHOULD BE USED. PROVIDE CORRECTION. NEC 422.13, | | | 240.4; FBC RE E3702.11 | | | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 6. ALL COUNTER TOP RECEPTACLES IN KITCHEN REQUIRE GFCI | | | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE | | | E3902.6 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-18 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-14 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2018-12-18 10:52:24 | ROUTED TO DBATTLES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-10-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-10-25 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2018-10-26 13:11:33 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-10-09 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-10-09 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2018-10-03 13:56:37 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-11 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-07-30 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-25 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2018-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-18 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-18 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2018-12-18 16:13:55 | MU-2018-040826-0000 | | | 12/18/18 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-11 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-11 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2018-09-11 13:25:16 | PENDING ELECTRICAL AND PLUMBING THE PLANS CAN BE | | | CHECKED OUT. | | | SEE BELOW FOR THE MUNICIPAL IMPACT FEE QUESTIONNAIRE | | | FORM REQUIREMENTS. | | | | | | [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. | | | PLEASE PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE | | | FORM TO THE PBC IMPACT FEE OFFICE. THE FORM CAN BE | | | FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION | | | /PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-29 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2018-06-29 11:36:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE, IF APPLICABLE, PROVIDED. | | | | | | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET | | | OF PLANS TO TAKE TO THE COUNTY. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-23 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-08-23 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-08-23 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-06-20 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-06-20 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2018-06-20 15:19:27 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - NEED MANUAL J | | | | | | PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, | | | SIXTH EDITION | | | | | | R403.7.1EQUIPMENT SIZING. | | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT | | | SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE | | | LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING | | | EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR | | | GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR | | | THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS | | | INSTALLED. | | | | | | 2 - NEED ENERGY COMPLIANCE WORKSHEET | | | | | | PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, | | | SIXTH EDITION | | | | | | R101.5.1COMPLIANCE MATERIALS. THE FLORIDA BUILDING | | | COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE, | | | WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR | | | MATERIALS THAT MEET THE INTENT OF THIS CODE. COMMISSION | | | APPROVED CODE COMPLIANCE DEMONSTRATION FORMS CAN BE | | | FOUND IN TABLE R101.5.1. | | | | | | | | | CHRIS MONTELLO | | | 561-805-6673 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-10-09 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-10-09 |
Time |
08:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-06 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-09-06 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2018-09-07 12:55:28 | REVIEW COMPLETED BY JERALD SMITH 0017-P | | 2018-09-06 12:30:35 | 2ND REVIEW: FBC 2017 6TH EDITION | | | PERMIT 18051263 | | | PLUMBING COMMENTS: | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE | | | THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB | | | AMEND TO FBC 107.2.1 | | | A. DETAIL A, AS PREVIOUSLY NOTED PLEASE SHOW FLOOR | | | DRAIN ON SANITARY ISOMETRIC AND FLOOR PLAN; IF NOT | | | REQUIRED THEN PLEASE REMOVE DETAIL. | | | B. DETAIL H, IF WATER HEATER IS EXISTING, PLEASE | | | REMOVE DETAIL. IF NEW WATER HEATER IS REQUIRED THEN A | | | VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER | | | (SHOWN). PER FBC RES P2804.7 | | | 2. SHT. P.1 AND SHEET P.3, FBC RES P3005.4.1 ALLOWS | | | MAXIMUM 6 DFU ON 2" HORIZONTAL FIXTURE BRANCH. DFU LOAD | | | ON THE FIXTURE BRANCH SHOWN ON ISOMETRIC AND FLOOR PLAN | | | CONNECTING KITCHEN SINK/DISHWASHER AND THE WASHING | | | MACHINE FIXTURE DRAINS IS 7 DFU. SIZE OF FIXTURE BRANCH | | | MUST BE INCREASED TO ACCOMMODATE THE DFUS ON THE | | | BRANCH. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-25 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2018-06-25 16:25:56 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE | | | THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB | | | AMEND TO FBC 107.2.1 | | | 2. SHT. P.2 IS THE WATER HEATER BEING REPLACED IF SO A | | | VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER. PER | | | FBC RES P2804.7 | | | 3. SHT. P-2 DETAIL A SHOW FLOOR DRAIN ON SANITARY | | | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 | | | 4. SHT P-2 WHAT IS THE DRY WELL SERVING IS IT THE AC | | | CONDENSATE. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-09-11 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-09-11 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2018-09-11 11:46:42 | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH | | | EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC R = FBC RESIDENTIAL | | | | | | NOA 16-1206.02 PROVIDED, BUT NEED MODIFIED ATTACHMENT | | | PER GENERAL LIMITATION 7. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-08-16 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-08-16 |
Time |
08:50 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-08 |
|
|
Cont ID |
|
| Sent By |
mcurz |
Date |
2018-06-08 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-06-08 |
Time |
16:02 |
Sent To |
PC |
|
| Notes |
| 2018-06-08 16:13:46 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) THE ADDITION EXCEEDS THE ALLOWABLE REAR SETBACK FOR | | | THIS ZONING DISTRICT. STRUCTURE SHOULD BE AT LEAST 10' | | | FROM REAR PROPERTY LINE. | | | | | | NOTE - STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED | | | TO BALCONIES, CORNICES, GUTTERS, EAVES, AND ROOF | | | OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN | | | THREE FEET INTO ANY SETBACK. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|