Plan Review Details - Permit 18051263
Plan Review Stops For Permit 18051263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-11 Cont ID  
Sent By dbattles Date 2018-09-11 Time 11:37 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 11:37 Sent To  
Notes
2018-09-11 11:39:02PROVISO:
 SEE ROOF REVIEW FOR ADDITIONAL ITEMS TO SUBMIT WITH
 ROOFING SUB PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 17:35 Rev Time 0.00
Received By shill Date 2018-06-29 Time 17:35 Sent To  
Notes
2018-06-29 17:36:29****CORRECTIONS****
 W.P.B. PERMIT: 18051263
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC R = FBC RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT
 SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
 2. NOTICE OF ACCEPTANCE(N.O.A.)
 N.O.A. 14-0610.05 IS EXPIRED. PLEASE PROVIDE TWO COPIES
 OF UPDATED N.O.A.
  
 3. SHEET A-5 REFERENCES N.O.A. NO. 17-1018.05 FOR
 WINDOWS. PROVIDE N.O.A. FOR WINDOWS AND MULL BAR.
 HAVE THE DESIGNER OF RECORD MARK THE SELECTED WINDOWS,
 ATTACHMENT TYPE AND STAMP AS REVIEWED.
  
 4. SUPPLY ROOFING PRODUCT APPROVAL, OR INDICATE ON YOUR
 COMMENT RESPONSE SHEET THAT THEY WILL BE A SUBMITTAL AT
 A LATER DATE.
  
 5. [FBC R401.2] DETERMINE UPLIFT THAT THE FOOTER WILL
 RESIST FOR LIGHT FRAME CONSTRUCTION USING TABLE R401.1.
 PROVIDE TYPE OF CONNECTOR AT BASE PLATE FOR THE
 DETERMINED UPLIFT, OR SHOW ON CONNECTOR SCHEDULE HOW
 THE SST-MST16 MEETS NAILING REQUIRMENTS.
  
 6. [FBC R403.1.4]FOOTER TO HAVE MINIMUM 12" DEPTH BELOW
 GRADE AND 4" ABOVE GRADE.
  
 7. [FBC R401.3]PROVIDE DRAINAGE FROM FOUNDATION AS
 OUTLINED IN R401.3
  
 8. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS
 SUBMITTED AND A COMMENT RESPONSE SHEET.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-10-26 Cont ID  
Sent By jpearson Date 2018-10-26 Time 15:28 Rev Time 0.00
Received By jpearson Date 2018-10-26 Time 15:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-10-07 Cont ID  
Sent By jpearson Date 2018-10-07 Time 09:02 Rev Time 0.00
Received By jpearson Date 2018-10-07 Time 09:02 Sent To P
Notes
2018-10-07 09:02:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES
 NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES
 WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220,
 408.30; FBC RE E3602.2 (A LOAD CALCULATION SHOULD SHOW
 ALL LOADS AND THE CORRESPONDING VA FOR THAT LOAD. THIS
 SHOULD BE COMPLETED IN THE FORMAT PROVIDED IN THE FBC
 RESIDENTIAL. THE PARTIAL LOAD CALCULATION PROVIDED IS
 NOT ACCEPTABLE.)
 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER
 PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND
 DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (WHAT IS SHOWN ON THE RISER
 DIAGRAM IS NOT THE SAME AS SHOWN ON PLAN. PROVIDE
 CORRECTION. RISER DIAGRAM SHOWS A FEED FROM THE METER
 TO THE INTERIOR PANEL WHICH IS LOCATED IN THE UTILITY.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6
 3. OK
 4. OK
 5. OK
 6. OK
  
 NEW COMMENT:
  
 7. PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN
 ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW,
 IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN
 FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. THE ADDITIONAL
 FEE FOR THIS PLAN WILL BE $950.00 . FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By ppetty Date 2018-08-28 Time 10:38 Rev Time 0.00
Received By ppetty Date 2018-08-28 Time 10:38 Sent To  
Notes
2018-08-28 10:38:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES
 NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES
 WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER
 PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND
 DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. OK
 4. OK
 5. OK
 6. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By jpearson Date 2018-06-25 Time 10:31 Rev Time 0.00
Received By jpearson Date 2018-06-22 Time 13:35 Sent To  
Notes
2018-06-25 10:31:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES
 NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES
 WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER
 PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND
 DISCONNECT LOCATED OUTSIDE, AND A 125 AMP PANEL INSIDE.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. PLAN
 ONLY SHOWS THIS IN ONE OF THE BATHROOMS. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 4. BREAKER FOR WATER HEATER IS SHOWN AS 50 AMP. FOR THE
 LOAD SPECIFIED OF 4500 WATTS, A BREAKER OF 25 OR 30
 AMPS SHOULD BE USED. PROVIDE CORRECTION. NEC 422.13,
 240.4; FBC RE E3702.11
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. ALL COUNTER TOP RECEPTACLES IN KITCHEN REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-12-18 Cont ID  
Sent By dbattles Date 2018-12-18 Time 16:14 Rev Time 0.00
Received By dbattles Date 2018-12-14 Time 10:52 Sent To  
Notes
2018-12-18 10:52:24ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-10-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-25 Time 13:11 Sent To  
Notes
2018-10-26 13:11:33RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-09 Cont ID  
Sent By jesmith Date 2018-10-09 Time 08:43 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 08:43 Sent To  
Notes
2018-10-03 13:56:37RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-11 Cont ID  
Sent By dbattles Date 2018-09-11 Time 11:39 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 14:36 Sent To  
Notes
2018-07-31 14:36:29R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 17:36 Rev Time 0.00
Received By shill Date 2018-05-25 Time 10:17 Sent To  
Notes
2018-05-30 10:18:06R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-18 Cont ID  
Sent By dbattles Date 2018-12-18 Time 16:12 Rev Time 0.00
Received By dbattles Date 2018-12-18 Time 16:12 Sent To  
Notes
2018-12-18 16:13:55MU-2018-040826-0000
 12/18/18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-11 Cont ID  
Sent By dbattles Date 2018-09-11 Time 13:22 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 13:22 Sent To  
Notes
2018-09-11 13:25:16PENDING ELECTRICAL AND PLUMBING THE PLANS CAN BE
 CHECKED OUT.
 SEE BELOW FOR THE MUNICIPAL IMPACT FEE QUESTIONNAIRE
 FORM REQUIREMENTS.
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE.
 PLEASE PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE
 FORM TO THE PBC IMPACT FEE OFFICE. THE FORM CAN BE
 FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION
 /PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 11:33 Rev Time 0.00
Received By shill Date 2018-06-29 Time 11:33 Sent To  
Notes
2018-06-29 11:36:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By cmontell Date 2018-08-23 Time 14:59 Rev Time 0.00
Received By cmontell Date 2018-08-23 Time 14:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By cmontell Date 2018-06-20 Time 15:47 Rev Time 0.00
Received By cmontell Date 2018-06-20 Time 15:11 Sent To  
Notes
2018-06-20 15:19:27MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MANUAL J
  
 PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION,
 SIXTH EDITION
  
 R403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
 2 - NEED ENERGY COMPLIANCE WORKSHEET
  
 PER 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION,
 SIXTH EDITION
  
 R101.5.1COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE,
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE. COMMISSION
 APPROVED CODE COMPLIANCE DEMONSTRATION FORMS CAN BE
 FOUND IN TABLE R101.5.1.
  
  
 CHRIS MONTELLO
 561-805-6673
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-09 Cont ID  
Sent By jesmith Date 2018-10-09 Time 08:42 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 12:30 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 12:30 Sent To  
Notes
2018-09-07 12:55:28REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 12:30:352ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051263
 PLUMBING COMMENTS:
 1ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE
 THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB
 AMEND TO FBC 107.2.1
  A. DETAIL A, AS PREVIOUSLY NOTED PLEASE SHOW FLOOR
 DRAIN ON SANITARY ISOMETRIC AND FLOOR PLAN; IF NOT
 REQUIRED THEN PLEASE REMOVE DETAIL.
  B. DETAIL H, IF WATER HEATER IS EXISTING, PLEASE
 REMOVE DETAIL. IF NEW WATER HEATER IS REQUIRED THEN A
 VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER
 (SHOWN). PER FBC RES P2804.7
 2. SHT. P.1 AND SHEET P.3, FBC RES P3005.4.1 ALLOWS
 MAXIMUM 6 DFU ON 2" HORIZONTAL FIXTURE BRANCH. DFU LOAD
 ON THE FIXTURE BRANCH SHOWN ON ISOMETRIC AND FLOOR PLAN
 CONNECTING KITCHEN SINK/DISHWASHER AND THE WASHING
 MACHINE FIXTURE DRAINS IS 7 DFU. SIZE OF FIXTURE BRANCH
 MUST BE INCREASED TO ACCOMMODATE THE DFUS ON THE
 BRANCH.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By gjohnson Date 2018-06-25 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 16:26 Sent To  
Notes
2018-06-25 16:25:561ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE
 THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB
 AMEND TO FBC 107.2.1
 2. SHT. P.2 IS THE WATER HEATER BEING REPLACED IF SO A
 VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER. PER
 FBC RES P2804.7
 3. SHT. P-2 DETAIL A SHOW FLOOR DRAIN ON SANITARY
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
 4. SHT P-2 WHAT IS THE DRY WELL SERVING IS IT THE AC
 CONDENSATE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By dbattles Date 2018-09-11 Time 11:39 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 11:39 Sent To  
Notes
2018-09-11 11:46:42DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 NOA 16-1206.02 PROVIDED, BUT NEED MODIFIED ATTACHMENT
 PER GENERAL LIMITATION 7.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-16 Cont ID  
Sent By mcruz Date 2018-08-16 Time 09:50 Rev Time 0.00
Received By mcruz Date 2018-08-16 Time 08:50 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By mcurz Date 2018-06-08 Time 16:13 Rev Time 0.00
Received By mcruz Date 2018-06-08 Time 16:02 Sent To PC
Notes
2018-06-08 16:13:46ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) THE ADDITION EXCEEDS THE ALLOWABLE REAR SETBACK FOR
 THIS ZONING DISTRICT. STRUCTURE SHOULD BE AT LEAST 10'
 FROM REAR PROPERTY LINE.
  
 NOTE - STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED
 TO BALCONIES, CORNICES, GUTTERS, EAVES, AND ROOF
 OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN
 THREE FEET INTO ANY SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]