Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-08-11 Cont ID  
Sent By pvalenti Date 2018-08-11 Time 17:11 Rev Time 0.00
Received By pvalenti Date   Time   Sent To I
Notes
2018-08-11 17:30:49****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
  
 1. FBC 107.1 THE SCOPE OF WORK IS NOT CLEAR; THE
 DRAWING SHOWS AREA OF DEMO WORK AND PROPOSED WORK UNDER
 THIS PERMIT APPLICATION.
  
 2. FBC 107.1 THE SUBMITTED WALL DETAIL IS NOT CLEAR AS
 TO THE TOP CONNECTIONS OF WALL. DOES THE WALL GO TO THE
 CEILING? IF THAT IS THE CASE A MECHANICAL PERMIT MAY BE
 REQUIRED FOR AN APPROVED VENTILLATION SYSTEM. IF THE
 WALL DOES NOT CONNECT TO THE CEILING ARE THERE
 CONNECTING BRACES ABOVE AND/OR ARE THERE CONNECTIONS TO
 THE EXISTING STRUCTURAL COLUMNS?
  
 3. FBC 107.1 THE GOVERNMENT CODE SHOWN ON THE PLAN IS
 FROM THE FBC 2010. THIS NEEDS TO BE CHANGED TO THE FBC
 2017.
  
 4. FBC 1016.2 PLEASE LABEL EACH ROOM AREA FOR
 DESIGNATION AND OCCUPANT LOAD/OCCUPANT CLASSIFICATION.
 (THE DIRECTIONAL INDICATORS FOR THE PATH OF EGRESS IN
 AREA LABELED AS UNIT "B" IS IN CONFLICT WITH THIS
 SECTION OF CODE).
  
 5. F.S. 481 DOCUMENTS PREPARED BY AN ARCHITECT AND
 SUBMITTED ON PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 AND DATED ORIGINALS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-13 Cont ID  
Sent By cthroop Date 2018-07-13 Time 15:10 Rev Time 0.00
Received By cthroop Date 2018-07-13 Time 15:10 Sent To FIRE
Notes
2018-07-13 15:14:45BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY LOCATION OF BUILDING ENTRANCE AND EXIT.
 PROVIDE EXIT PATH OF TRAVEL ON PLANS.
 2. IDENTIFY LOCATION OF EXIT SIGNS. WALL CANNOT BLOCK
 LINE OF SIGHT TO EXIT SIGNS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-13 Cont ID  
Sent By cthroop Date 2018-07-13 Time 13:34 Rev Time 0.00
Received By cthroop Date 2018-07-13 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-02 Cont ID  
Sent By cthroop Date 2018-06-02 Time 10:50 Rev Time 0.00
Received By cthroop Date 2018-06-02 Time 10:49 Sent To  
Notes
2018-06-02 10:53:12BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED WALL.
 IDENTIFY ANY EASEMENTS/SETBACKS.
 2. PROVIDE DETAIL OF WALL CONSTRUCTION.
 3. DESIGNER TO PRINT NAME AND SIGN PLAN.
 4. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-08-06 Cont ID  
Sent By J.Walker Date 2018-08-06 Time   Rev Time 0.00
Received By   Date 2018-08-06 Time   Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-07-25 Cont ID  
Sent By J.Walker Date 2018-07-25 Time   Rev Time 0.00
Received By   Date 2018-07-25 Time   Sent To B
Notes
2018-07-25 12:55:27COMMENTS FROM 7/19/2018 NOT ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By J.Walker Date 2018-07-19 Time   Rev Time 0.00
Received By   Date 2018-07-19 Time   Sent To B
Notes
2018-07-19 16:35:04FIRE WILL REQUIRE A DETAILED INTERIOR FLOOR PLAN
 MEANS OF EGRESS AND LIFE SAFETY PLAN NFPA CHAPTER 7
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-11 Cont ID  
Sent By pvalenti Date 2018-08-11 Time 17:31 Rev Time 0.00
Received By pvalenti Date 2018-08-01 Time 11:12 Sent To I
Notes
2018-08-02 11:12:32RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-27 Cont ID  
Sent By cpuell Date 2018-07-27 Time 14:43 Rev Time 0.00
Received By cpuell Date 2018-07-02 Time 14:38 Sent To I
Notes
2018-07-13 15:50:037/13 ON SH DESK
  
2018-07-03 14:38:16RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-02 Cont ID  
Sent By cthroop Date 2018-06-02 Time 10:53 Rev Time 0.00
Received By cthroop Date 2018-05-25 Time 10:46 Sent To I
Notes
2018-05-30 10:46:27ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status N Date 2018-07-13 Cont ID  
Sent By shill Date 2018-07-13 Time 15:03 Rev Time 0.00
Received By shill Date 2018-07-13 Time 15:03 Sent To  
Notes
2018-07-13 15:03:21SEE ZONING REVIEW; NOT REQUIRED FOR INTERIOR
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-10 Cont ID  
Sent By mcruz Date 2018-07-10 Time 13:56 Rev Time 0.00
Received By mcruz Date 2018-07-10 Time 13:50 Sent To B
Notes
2018-07-10 13:56:47ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) IT APPEARS YOUR DRAWING ON THE SURVEY FOR THE
 PROPOSED WALL IS INTERIOR WORK. IF THAT IS THE CASE,
 AND NO EXTERIOR WORK IS PROPOSED, THEN A ZONING REVIEW
 IS NOT REQUIRED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 14:17 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 13:57 Sent To B
Notes
2018-05-31 14:17:17ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE SURVEY OF PROPERTY.
 2) PROVIDE LOCATION, HEIGHT AND LENGTH OF WALL ON
 SURVEY.
 3) CLARIFY PURPOSE OF WALL. IS IT A RETENTION WALL? IS
 IS DECORATIVE?
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]