| Plan Review Stops For Permit 18051242 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-11 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-11 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-30 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-30 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2018-06-30 15:30:02 | PROVISO | | | DOORS SHOWN AS "EGRESS STOP" APPEAR TO BE EXITS. IF | | | THEY ARE NOT EXITS, AND IF EXIT DISCHARGE DOES NOT LEAD | | | TO THE PUBLIC WAY, REVISE PLAN TO SHOW COMPLIANCE WITH | | | FBC CHAPTER 10 AND RESUBMIT. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-21 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-21 |
Time |
08:05 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-12 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-11 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-07-31 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-07-31 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-06-04 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-06-04 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-06-04 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2018-06-04 13:16:12 | PERMIT # 18051242 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED WITH COMMENTS/PROVISO | | | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) | | | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND | | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | | 500 NORTH DIXIE HIGHWAY. | | | | | | 3) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN | | | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE | | | MAINTAINED AT ALL TIMES. | | | | | | 4) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO | | | THE FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | 5) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT | | | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED | | | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE | | | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM | | | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD | | | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY | | | BE NEEDED. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-08-15 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2018-08-16 16:14:46 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-08-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-07-23 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2018-08-11 15:16:51 | ROUTED TO SAK DESK | | | | | 2018-07-25 09:39:14 | C28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-12 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-24 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-21 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-21 |
Time |
11:44 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-13 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-13 |
Time |
07:44 |
Sent To |
I |
|
| Notes |
| 2018-08-13 08:54:35 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18051242 | | | 8/13/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW HAS NOT BEEN | | | ADDRSSED. SEE BELOW: | | | | | | 1) SHEET M401: EXHAUST VENTILATION AT A RATE OF 0.25 | | | CFMS PER SQ. FT. IS REQUIRED FOR THE FITTING ROOMS PER | | | TABLE 403.3.1.1 FBC M. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-22 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-22 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2018-06-22 10:40:57 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18051242 | | | 6/22/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M401: EXHAUST VENTILATION AT A RATE OF 0.25 | | | CFMS PER SQ. FT. IS REQUIRED FOR THE FITTING ROOMS PER | | | TABLE 403.3.1.1 FBC M. | | | | | | 2) M401: CORRECT KEYED NOTE #1 WHICH IS INDICATING | | | EXISTING DUCT SMOKE DETECTOR IN THE RETURN DUCTWORK- | | | THE #1 NOTES ON THE PLAN ARE POINTING AT THE DETECTORS | | | IN THE SUPPLY DUCTWORK WHICH ARE THE REQUIRED LOCATIONS | | | PER SECTION 606.2.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-07-10 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-10 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-02 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2018-08-02 |
Time |
16:26 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2018-08-02 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-12 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2018-06-12 |
Time |
09:20 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2018-06-11 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2018-06-12 09:20:25 | FAILED | | | | | | PLEASE PROVIDE EITHER THE PALM BEACH OUTLETS MANAGEMENT | | | APPROVAL STAMP ON THE PLANS OR A LETTER FROM THE PALM | | | BEACH OUTLETS MANAGEMENT THAT APPROVED THE SPECIFIC | | | PLANS SUBMITTED. | | | | | | ONCE THE PALM BEACH OUTLETS MANAGEMENT APPROVAL IS | | | SUBMITTED, THE ZONING REVIEW WILL BE CHANGED TO A | | | "PASS". | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] | | | | | | |
|
|