Plan Review Details - Permit 18051242
Plan Review Stops For Permit 18051242
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 15:16 Rev Time 0.00
Received By shill Date 2018-08-11 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 15:29 Rev Time 0.00
Received By shill Date 2018-06-30 Time 15:22 Sent To  
Notes
2018-06-30 15:30:02PROVISO
 DOORS SHOWN AS "EGRESS STOP" APPEAR TO BE EXITS. IF
 THEY ARE NOT EXITS, AND IF EXIT DISCHARGE DOES NOT LEAD
 TO THE PUBLIC WAY, REVISE PLAN TO SHOW COMPLIANCE WITH
 FBC CHAPTER 10 AND RESUBMIT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 08:05 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 08:05 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-12 Cont ID  
Sent By jpearson Date 2018-07-12 Time 07:17 Rev Time 0.00
Received By jpearson Date 2018-07-11 Time 06:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 15:28 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-04 Cont ID  
Sent By scaldero Date 2018-06-04 Time 13:17 Rev Time 0.00
Received By scaldero Date 2018-06-04 Time 13:08 Sent To  
Notes
2018-06-04 13:16:12PERMIT # 18051242
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS/PROVISO
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 3) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 4) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 5) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-08-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-15 Time 16:14 Sent To  
Notes
2018-08-16 16:14:46RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-23 Time 09:39 Sent To  
Notes
2018-08-11 15:16:51ROUTED TO SAK DESK
  
2018-07-25 09:39:14C28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-12 Cont ID  
Sent By shill Date 2018-07-12 Time 07:21 Rev Time 0.00
Received By shill Date 2018-05-24 Time 10:38 Sent To  
Notes
2018-05-30 10:38:46C01

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-21 Cont ID  
Sent By ccole Date 2018-08-21 Time 11:44 Rev Time 0.00
Received By ccole Date 2018-08-21 Time 11:44 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-13 Cont ID  
Sent By ccole Date 2018-08-13 Time 08:53 Rev Time 0.00
Received By ccole Date 2018-08-13 Time 07:44 Sent To I
Notes
2018-08-13 08:54:352ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18051242
 8/13/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW HAS NOT BEEN
 ADDRSSED. SEE BELOW:
  
 1) SHEET M401: EXHAUST VENTILATION AT A RATE OF 0.25
 CFMS PER SQ. FT. IS REQUIRED FOR THE FITTING ROOMS PER
 TABLE 403.3.1.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By ccole Date 2018-06-22 Time 10:28 Rev Time 0.00
Received By ccole Date 2018-06-22 Time 07:55 Sent To  
Notes
2018-06-22 10:40:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051242
 6/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M401: EXHAUST VENTILATION AT A RATE OF 0.25
 CFMS PER SQ. FT. IS REQUIRED FOR THE FITTING ROOMS PER
 TABLE 403.3.1.1 FBC M.
  
 2) M401: CORRECT KEYED NOTE #1 WHICH IS INDICATING
 EXISTING DUCT SMOKE DETECTOR IN THE RETURN DUCTWORK-
 THE #1 NOTES ON THE PLAN ARE POINTING AT THE DETECTORS
 IN THE SUPPLY DUCTWORK WHICH ARE THE REQUIRED LOCATIONS
 PER SECTION 606.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-07-10 Cont ID  
Sent By gjohnson Date 2018-07-10 Time 08:49 Rev Time 0.00
Received By gjohnson Date 2018-07-10 Time 08:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-02 Cont ID  
Sent By eschneid Date 2018-08-02 Time 16:26 Rev Time 0.25
Received By eschneid Date 2018-08-02 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By eschneid Date 2018-06-12 Time 09:20 Rev Time 0.50
Received By eschneid Date 2018-06-11 Time 15:54 Sent To  
Notes
2018-06-12 09:20:25FAILED
  
 PLEASE PROVIDE EITHER THE PALM BEACH OUTLETS MANAGEMENT
 APPROVAL STAMP ON THE PLANS OR A LETTER FROM THE PALM
 BEACH OUTLETS MANAGEMENT THAT APPROVED THE SPECIFIC
 PLANS SUBMITTED.
  
 ONCE THE PALM BEACH OUTLETS MANAGEMENT APPROVAL IS
 SUBMITTED, THE ZONING REVIEW WILL BE CHANGED TO A
 "PASS".
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  