Plan Review Details - Permit 18051235
Plan Review Stops For Permit 18051235
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-02-28 Cont ID  
Sent By dbattles Date 2019-02-28 Time 11:01 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 11:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 09:21 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 07:03 Sent To  
Notes
2019-02-15 09:26:21BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADVISORY:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 THE FOLLOWING COMMENTS HAVE NOT BEEN ADDRESSED FROM
 PREVIOUS REVIEWS.
  
  
 1. OK.
  
 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL
 INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF
 PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE
 EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR
 OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS.
  2-4. SURVEY NOT PROVIDED.
  
 3-9. OK.
  
 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.)
 FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING
 IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION
 AND ATTACHMNET AS OUTLINED IN R301.1.2.
 10-4. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
 11-15 OK.
  
 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT
 MEET THE DESIGN PRESSURES FOR ZONES 2 & 3.
 16-4. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
  
 17-18. OK.
  
 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS.
  19-3. ONLY PAGE A101 IS SIGNED/SEALED BY ARCHITECT.
 19-4. ONLY ONE SET OF ARCHITECTURAL DRAWINGS PROVIDED.
 ALL OTHER PLAN SHEETS ARE SIGNED AND SEALED. PROVIDE
 SECOND SET OF ARCHITECTURALS, SIGNED AND SEALED.
  
  
 20-21. OK.
  
 22. OK
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 15:28 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 13:18 Sent To  
Notes
2019-01-11 15:37:39BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADVISORY:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 THE FOLLOWING COMMENTS HAVE NOT BEEN ADDRESSED FROM
 PREVIOUS REVIEWS.
  
  
 1. OK.
  
 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL
 INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF
 PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE
 EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR
 OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS.
  2-3. SURVEY NOT PROVIDED.
  
 3-9. OK.
  
 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.)
 FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING
 IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION
 AND ATTACHMNET AS OUTLINED IN R301.1.2.
 10-3. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
 11-15 OK.
  
 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT
 MEET THE DESIGN PRESSURES FOR ZONES 2 & 3.
 16-3. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
  
 17-18. OK.
  
 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS.
  19-3. ONLY PAGE A101 IS SIGNED/SEALED BY ARCHITECT.
  
 20-21. OK.
  
 22. FBC 107, SEPARATE PERMITS ARE REQUIRED; ONE PERMIT
 FOR THE MAIN HOUSE, ONE PERMIT FOR THE GARAGE. PROVIDE
 VALUE FOR EACH.
  22-3 COMMENT NOT ADDRESSED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By dbattles Date 2018-08-22 Time 16:45 Rev Time 0.00
Received By dbattles Date 2018-08-22 Time 13:55 Sent To  
Notes
2018-08-22 16:45:35****CORRECTIONS****
 W.P.B. PERMIT: 18051235
 REVIEWED: AUGUST 22, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK.
  
 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL
 INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF
 PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE
 EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR
 OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS.
  2-2. SURVEY NOT PROVIDED.
  
 3-9. OK.
  
 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.)
 FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING
 IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION
 AND ATTACHMNET AS OUTLINED IN R301.1.2.
 10-2. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
 11-15 OK.
  
 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT
 MEET THE DESIGN PRESSURES FOR ZONES 2 & 3.
 16-2. NO PRODUCT APPROVALS SUBMITTED. SINCE NO COMMENT
 RESPONSE SHEET PROVIDED I DON?T KNOW IF THEY ARE TO BE
 DEFFERED. PROVIDE APPROVALS, OR INDICATE THAT THEY ARE
 TO BE DEFFERED.
  
  
 17-18. OK.
  
 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS.
  19-2. ONLY PAGE A101 IS SIGNED/SEALED BY ARCHITECT.
  
 20-21. OK.
  
 22. FBC 107, SEPARATE PERMITS ARE REQUIRED; ONE PERMIT
 FOR THE MAIN HOUSE, ONE PERMIT FOR THE GARAGE. PROVIDE
 VALUE FOR EACH.
  22-2 COMMENT NOT ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By shill Date 2018-06-28 Time 16:54 Rev Time 0.00
Received By shill Date 2018-06-28 Time 16:54 Sent To  
Notes
2018-06-28 17:04:19****CORRECTIONS****
 W.P.B. PERMIT: 18051235
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. INFO ONLY - [FL. STATUTE 713.13]FILE NOTICE OF
 COMMENCEMENT(N.O.C) WITH THE CLERK OF THE COURT AND
 PROVIDE CERTIFIED COPY TO WPB BUILDING DEPARTMENT PRIOR
 TO SCHEDULING FIRST INSPECTION. THE N.O.C. MUST BE
 SIGNED BY THE OWNER.(REQUIRED FOR VALUE OF $2500 AND
 ABOVE FOR IMPROVEMENTS TO REAL PROPERTY).
  
 2. [FBC R301]PROVIDE 2 COPIES OF SURVEY THAT WILL
 INDICATE THE UTILITY EASEMENT ON THE SOUTH SIDE OF
 PROPERTY. IF ANY PART OF NEW GARAGE ENCROACHES INTO THE
 EASEMENT THEN MOVE GARAGE LOCATION ACCORDINGLY OR
 OBTAIN EASEMENT CONSENTS FROM EASEMENT HOLDERS.
  
 3. [FBC 107.3.5.3]FINISHED FLOOR ELEVATION NEEDS TO BE
 ESTABLISHED.
  
 4. [FBC R401.3] PROVIDE DRAINAGE PLAN FOR NEW GARAGE
 AND ANY NEW IMPERVIOUS SURFACES TO SHOW COMPLIANCE WITH
 R401.3
 USE ESTABLISHED FINISHED FLOOR ELEVATION OF GARAGE AS
 BASIS OF DESIGN TO SHOW HOW WATER GETS TO THE STREET
 STORM DRAIN.
  
 5. [FBC 107.3.5.3]SHEET A203 AT THE BOTTOM OF PAGE IS
 LABELED NORTH, BUT IT IS SOUTH ELEVATION.
  
 6. [FBC 107.3.5.3]MULTIPLE SHEETS REFER TO SEE
 STRUCTURAL SHEET, BUT THERE IS NO STRUCTURAL SHEET.
 PLEASE PROVIDE STRUCTURAL AS COMMENTS TO FOLLOW ARE
 REQUESTING ADDITIONAL STRUCTURAL INFORMATION.
  
 7. [FBC R401.4]PROVIDE DESIGN CRITERIA FOR NEW GARAGE
 INCLUDING SOIL REPORT, BEARING CAPACITY, WIND DESIGN
 CRITERIA.
  
 8. [FBC R301.2.1]PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS.
  
 9. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 10. [FBC R301.1.2]PROVIDE NOTICE OF APPROVAL(N.O.A.)
 FOR ALL WINDOWS, DOORS AND GARAGE DOORS. IF ANY GLAZING
 IS NON-IMPACT RATED THEM PROVIDE PROPOSED PROTECTION
 AND ATTACHMNET AS OUTLINED IN R301.1.2.
  
 IF ITEMS PROPOSED ARE NOT KNOWN AT THIS TIME, THEY MAY
 BE DEFERRED.
  
 FBC 107, ALL PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGN PROFESIONAL PRIOR TO SUBMITTAL.
 STAMP EACH N.O.A AS REVIEWED, OR PROVIDE ONE REVIEW
 SHEET LISTING ALL PRODUCT APPROVALS REVIEWED AND
 APPROVED.
  
 11. [FBC 107.3.5.3]PROVIDE DETAILS OF HOW NEW OVERHANGS
 AND PORCH ARE CONNECTED TO EXISTING AND HOW THEY MEET
 WIND LOAD DESIGN CRITERIA. CALL OUT EXISTING STEEL
 COLUMNS AND FOOTERS AND DETAIL HOW THEY MEET DESIGN
 CRITERIA FOR UPLIFT AND GRAVITY LOADS. IF APPLICABLE
 PROVIDE PAD DETAILS AND POST CONNECTIONS.
  
 12. [FBC EX807.4]PROVIDE MEANS THAT WERE USED TO
 DETERMINE INTERIOR WALLS TO BE DEMOLISHED ARE NON-LOAD
 BEARING, AND PROVIDE BACK-UP TO SUPPORT FINDINGS.
  
 13. [FBC 107.3.5.3]PROVIDE STRUCTURAL DETAILS OF MAIN
 HOUSE INTERIOR CEILING MODIFICATIONS AS INDICATED ON
 A103.
  
 14. [FBC R602.5]PROVIDE DETAIL OF PROPOSED PARTION AND
 INFILL. LIST MATERIALS, SPACING AND CONNECTIONS.
  
 15. [FBC 107.3.5.3]PROVIDE ROOF PLAN FOR NEW GARAGE TO
 ROOF SLOPE AND SCUPPER LOCATIONS. THE DETAIL ON SHEET
 A501 SHOULD COMPLIMENT THE ROOF PLAN. LABLE CONNECTORS
 TO BE USED IN DETAILS AND SECTIONS PROVIDED.
  
 16. [FBC 107.2.1]PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS. FOR THE FLAT ROOF, INDICATE ASSEMBLY
 PROPOSED AND PROVIDE ENGINEERING IF ASSEMBLY DOES NOT
 MEET THE DESIGN PRESSURES FOR ZONES 2 & 3.
  
 THIS MAY BE DEFERRED UPON REQUEST AND SUBMITTED WITH
 THE ROOF PERMIT APPLICATION PRIOR TO INSTALLATION.
  
 17. [FBC R308.1]SHOWER ENCLOSURES TO COMPLY WITH SAFETY
 GLASS STANDARDS IN FBC R308.1
  
 18. [FBC R702.4.2]PROVIDE TILE BACKER IN SHOWER
 COMPARTMENTS THAT COMPLY WITH TABLE R702.4.2.
  
 19. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS.
  
 20. A PORTION OF THE FIRST PAGE WAS CROSSED OFF; ONLY
 THE ARCHITECT CAN ALTER THE PLAN, FS481.
  
 21. A101 REFERS TO INCORRECT GOVERNING CODE; REVISE TO
 FBC 2017 RESIDENTIAL.
  
 22. FBC 107, SEPARATE PERMITS ARE REQUIRED; ONE PERMIT
 FOR THE MAIN HOUSE, ONE PERMIT FOR THE GARAGE. PROVIDE
 VALUE FOR EACH.
  
  
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS
 SUBMITTED.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 10:24 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 07:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 15:43 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 13:17 Sent To  
Notes
2019-01-11 16:18:17ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE EQUIPMENT GROUNDING CONDUCTOR BETWEE MAIN
 PANEL AND GARAGE SUB-PANEL. PER FBC R E3607.3.1
 E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR.
  
 AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN
 SECTION E3908 SHALL BE RUN WITH THE SUPPLY CONDUCTORS
 AND CONNECTED TO THE BUILDING OR STRUCTURE
 DISCONNECTING MEANS AND TO THE GROUNDING ELECTRODE(S).
 THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED FOR
 GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES OR FRAMES
 REQUIRED TO BE GROUNDED OR BONDED. THE EQUIPMENT
 GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH
 SECTION E3908.12. ANY INSTALLED GROUNDED CONDUCTOR
 SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING
 CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). [250.32(B)
 AND TABLE 250.122]
  
 2. PROVIDE AVAILABLE FAULT CURRENT FROM FPL.
 AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 SEPERATE PERMIT REQUIRED FOR DETACHED GARAGE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-14 Cont ID  
Sent By jpearson Date 2018-08-14 Time 16:15 Rev Time 0.00
Received By jpearson Date 2018-08-14 Time 15:17 Sent To  
Notes
2018-08-14 16:15:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
  
 NEW COMMENTS:
  
 5. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 9. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 10. PLAN IS NOT SIGNED BY THE DESIGN PROFESSIONAL. A
 COPY OF THE ENGINEERS SIGNATURE IS NOT ACCEPTABLE. WPB
 FBC 107.1 AND 107.2; SECTION 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By jpearson Date 2018-06-22 Time 11:12 Rev Time 0.00
Received By jpearson Date 2018-06-22 Time 10:21 Sent To  
Notes
2018-06-22 11:12:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By gjohnson Date 2018-06-25 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 14:27 Sent To  
Notes
2018-06-25 14:28:10GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-01-04 Cont ID  
Sent By fmittner Date 2019-01-04 Time 10:24 Rev Time 0.00
Received By fmittner Date 2019-01-04 Time 10:24 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By destabro Date 2018-07-30 Time 15:01 Rev Time 0.00
Received By destabro Date 2018-07-30 Time 15:01 Sent To Z
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By destabro Date 2018-06-12 Time 15:31 Rev Time 0.00
Received By destabro Date 2018-06-12 Time 15:31 Sent To I
Notes
2018-06-12 15:33:566/12/2018 - HISTORIC PRESERVATION BOARD APPROVAL (HPB
 18-07) PER THE FEBRUARY 28, 2018 MEETING. DLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 10:31 Rev Time 0.00
Received By cthroop Date 2019-02-11 Time 11:10 Sent To  
Notes
2019-02-12 11:10:53RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 16:21 Rev Time 0.00
Received By cthroop Date 2018-12-18 Time 14:46 Sent To  
Notes
2018-12-19 14:47:01R38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 08:51 Rev Time 0.00
Received By shill Date 2018-09-04 Time 08:50 Sent To  
Notes
2018-07-18 10:16:33R38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By shill Date 2018-06-28 Time 17:04 Rev Time 0.00
Received By shill Date 2018-05-24 Time 10:12 Sent To  
Notes
2018-05-31 10:12:47R34

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 09:33 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 15:39 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 13:18 Sent To  
Notes
2019-01-11 15:42:54MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN PROFESSIONAL SHALL SIGN AND SEAL PLAN.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 SEPERATE PERMIT REQUIRED FOR DETACHED GARAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By cmontell Date 2018-08-06 Time 15:03 Rev Time 0.00
Received By cmontell Date 2018-08-06 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By cmontell Date 2018-06-20 Time 14:52 Rev Time 0.00
Received By cmontell Date 2018-06-20 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 10:26 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 07:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 16:19 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 13:18 Sent To  
Notes
2019-01-11 16:21:41PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN PROFESSIONAL SHALL SIGN AND SEAL PLAN.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 2. SEPERATE PERMIT REQUIRED FOR DETACHED GARAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-02 Cont ID  
Sent By jesmith Date 2018-10-02 Time 14:29 Rev Time 0.00
Received By jesmith Date 2018-09-04 Time 08:46 Sent To  
Notes
2018-09-04 08:46:262ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.3(12)
  
 2. PROVIDE NOTE: THE VALVES FOR THE STACKABLE WASHING
 MACHINE SHALL BE ACCESSIBLE. PER FBC RES P2903.9.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By gjohnson Date 2018-06-25 Time 14:09 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 09:28 Sent To  
Notes
2018-06-25 14:27:171ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.3(12)
  
 2. THE VALVES FOR THE STACKABLE WASHING MACHINE SHALL
 BE ACCESSIBLE. PER FBC RES P2903.9.3
  
 3. THE TANKLESS HEATER SHALL BE MOUNTED A MINIMUM OF 4'
 FROM ANY OPENINGS IN THE BUILDING. ANSI Z223.1 NFPA 54
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status N Date 2019-02-28 Cont ID  
Sent By dbattles Date 2019-02-28 Time 11:01 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 11:01 Sent To  
Notes
2019-02-28 11:05:01NO ROOFING ON PLANS FOR THE MAIN HOUSE RENOVATIONS.
 THE GARAGE (19020474) WILL HAVE ROOFING SUB PERMIT.
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 10:28 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 07:04 Sent To  
Notes
2019-02-15 10:30:28BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2019-01-11 Cont ID  
Sent By cthroop Date 2019-01-11 Time 15:28 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 13:17 Sent To  
Notes
2019-01-11 15:28:34PLEASE SEE COMMENTS UNDER BLDG. REVIEW. CT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 08:49 Rev Time 0.00
Received By shill Date 2018-09-04 Time 08:48 Sent To  
Notes
2018-09-04 08:49:44NO ROOF INFORMATION PROVIDED; SEE BUILDING REVIEW
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By shill Date 2018-06-28 Time 17:04 Rev Time 0.00
Received By shill Date 2018-06-28 Time 17:04 Sent To  
Notes
2018-06-28 17:05:12NO ROOF INFORMATION PROVIDED; SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-04 Cont ID  
Sent By fmittner Date 2019-01-04 Time 10:24 Rev Time 0.00
Received By fmittner Date 2019-01-04 Time 10:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By destabro Date 2018-07-30 Time 15:02 Rev Time 0.00
Received By destabro Date 2018-07-30 Time 15:02 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-12 Cont ID  
Sent By destabro Date 2018-06-12 Time 15:31 Rev Time 0.00
Received By destabro Date 2018-06-12 Time 15:31 Sent To HIST
Notes
***NONE***