Plan Review Details - Permit 18051174
Plan Review Stops For Permit 18051174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 12:52 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 12:52 Sent To  
Notes
2019-10-04 16:12:36SOIL REPORT RECEIVED AND ADDED TO RECORD FILE. 10/4/19
 DB
2018-09-12 12:56:49PROVISOS:
  
 A. ENGINEERED TRUSS DRAWINGS REQUIRED AT INSPECTION
 B. SEPARATE PERMITS REQUIRED FOR DEMO, FENCING, WALLS
 C. STAIR ENGINEERING IS TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED TO BUILDING DIVISION FOR REVIEW
 PRIOR TO INSTALLATION.
 D. OWNER TO PROVIDE SOILS REPORT PRIOR TO FOUNDATION
 WORK.
 AS DISCUSSED WITH S.H AND D.B. THE OLD HOUSE NEEDS TO
 BE DEMOED BEFORE THE SOILS REPORT CAN BE DONE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 10:41 Rev Time 0.00
Received By shill Date 2018-06-27 Time 12:07 Sent To  
Notes
2018-06-29 10:42:11****CORRECTIONS****
 W.P.B. PERMIT: 18051174
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 110.9] DETAIL 4-A9 WAS PROVIDED (SITE WALL). I
 WAS UNABLE TO LOCATE PROPOSED LOCATION (C1, A1), PLEASE
 ADVISE WHERE THIS CAN BE FOUND OR ADD TO PLAN. IF IT IS
 NEAR THE PROPERTY LINE, SHOW LOCATION OF FOOTING
 RELATIVE TO THE PROPERTY LINE. TYPICALLY AN ECCENTRIC
 FOOTER IS REQUIRED FOR SITE WALL.
  
 IF A SITE (RETAINING) WALL IS NOT PROPOSED, REVISE C1
 TO SHOW PROPOSED GRADES AND GRADES ON ADJACENT PARCEL
 TO SHOW HOW WATER WILL BE DIRECTED TO DRAIN TO STORM
 DRAIN AT FRONT OF PROPERTY OR SWALE TO THE REAR RATHER
 THAN ADJACENT PARCEL.
  
 2.[FBC R401.3]SITE DRAINAGE TO PROVIDE 2% SLOPE FOR
 IMPERVIOUS SURFACES WITHIN 10' OF THE FOUNDATION.
  
 3.[FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AS REFERENCED ON SHEET S4.
  
 4.[FBC 107] PROVIDE CUT SHEET FOR ICYNENE WITH THE TYPE
 SELECTED TO ESTABLISH THICKNESS NEEDED TO MEET REQUIRED
 R-VALUE.
  
 5.[FBC R302.9.1 & R302.9.2]ADD NOTE TO SHEET A9 THAT
 FINISHES SHALL HAVE A FLAME SPEAD INDEX OF NOT GREATER
 THAN 200 AND SMOKE DEVELOPED INDEX OF NOT GREATER THAN
 400.
  
 6.[FBC R506.2.3]S-1 SHOWS CORRECT VAPOR BARRIER, BUT
 SHEET A9 SHOWS CONFLICTING NUMBERS. PLEASE ADJUST SHEET
 A-9 TO MATCH SHEET S-1.
  
 7.[FBC R506.2.4] ADD NOTE ON SHEET S1 FOR CONTRACTION
 JOINTS TO COMPLY WITH ACI 332 OR APPROVED INDUSTRY
 STANDARD.
  
 8.[R302.6]NOTE ON A-2 CALLS OUT TYPE X DRYWALL ON
 CEILING IN GARAGE. TO AVOID FIELD/INSPECTION ISSUES, IT
 IS SUGGESTED TO CALL OUT TYPE X DRYWALL ON SECTION 1/A9
 TO MATCH.
  
 9.[FBC 107.3.5.3]UPDATE SHEET S4 STRUCTURAL NOTES TO
 REFERENCE FBC 2017 6TH EDITION IN LINE JUST BELOW CODES
 AND STANDARDS.
  
 10.[FBC 107.3.5.3]PROVIDE LINTEL SCHEDULE FOR EACH
 WINDOW/DOOR WHERE LINTEL IS TO BE PROVIDED. THIS IS TO
 ESTABLISH MINIMUM BEARING TO MATCH N.O.A. 17-0821.18.
  
 11.[FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 12.[FBC R302.11]ADD FIREBLOCKING TO DETAIL SHEET A9 ON
 TYPICAL WALL SECTIONS.
  
 13.[FBC R407.2]ADD NOTE THAT THAT STATES HOW STEEL
 COLUMNS WILL MEET PRTECTION REQUIREMENTS IN R407.2
  
 14.[R302.12]UPDATE DRAFTSTOPPING NOTE ON SHEET A8 TO
 SAY R302.12 INSTEAD OF R301.12. ALSO, COPY/PASTE THIS
 NOTE TO SHEET S2 WHERE FLOOR TRUSSES ARE ARE SHOWN IN
 PLAN VIEW.
  
 15.[FBC R311.3 & R311.3.1]EGRESS LANDING SHALL NOT BE
 LESS THAN 1 1/2" LOWER THAN THE TOP OF THRESHOLD.SHOW
 DIMENSION OF LANDING IN RELATIONSHIP TO FINISHED FLOOR
 ON SHEET A8 AND S1.
  
 16.[FBC R310]PROVIDE DETAIL OF HOW DECO RAILS AT EGRESS
 WINDOWS MEET EGRESS REQUIREMENTS.
  
 17.[FBC 107.2.1]PROVIDE NOTICE OF ACCEPTANCE(N.O.A)
 THAT IS NOT EXPIRED FOR N.O.A. 17-1212.2A AND N.O.A.
 17-1212.09.
  
 18. [FBC 107, FBC R 301] THE SHINGLE PRODUCT APPROVAL
 IS OK
 FOR THE FLAT DECK, THE ASSEMBLY PROPOSED AND
 ENGINEERING FOR ZONES 2 & 3, IF APPLICABLE, IS
 REQUIRED.
  
 ALTERNATIVELY, THIS MAY BE PROVIDED AT TIME OF ROOF SUB
 PERMIT APPLICATION UPON REQUEST.
  
 19. [FBC 109], A VALUATION ADJUSTMENT HAS BEEN DONE PER
 ICC TABLES:
 $945,112.55 UNDER AIR (7979 SQ. FT. X 118.45)
 $80,065.00 UNDER ROOF (1675 SQ. FT. X 47.80)
 1,025,177.50 TOTAL EVALUATION
  
 20. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. ENGINEERED TRUSS DRAWINGS REQUIRED AT INSPECTION
 B. SEPARATE PERMITS REQUIRED FOR DEMO, FENCING, WALLS
 SITE WALLS AND POOL.
 C. STAIR ENGINEERING IS TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED TO BUILDING DIVISION FOR REVIEW
 PRIOR TO INSTALLATION.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-10-16 Cont ID  
Sent By jpearson Date 2018-10-16 Time 15:24 Rev Time 0.00
Received By jpearson Date 2018-10-16 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-08-30 Cont ID  
Sent By jpearson Date 2018-08-30 Time 09:18 Rev Time 0.00
Received By jpearson Date 2018-08-30 Time 09:18 Sent To  
Notes
2018-08-30 09:08:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. RISER SHOWS A METER CAN FEEDING A MLO PANEL (PANEL
 A) AND THE GENERATOR TRANSFER SWITCH (MUST BE SERVICE
 RATED. FIRST FLOOR PLAN SHOWS A METER WITH A MAIN
 DISCONNECT ON CORNER OF GARAGE WITH THE PANELS AND
 TRANSFER SWITCH INSIDE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.5; WPB FBC 107.2.1 (PLAN SHOWS A
 METER CAN WITH A CT CAN, WHICH IS NOT TYPICAL IN A
 RESIDENTIAL INSTALLATION. PERHAPS THIS IS A TRANSFER
 SWITCH, SINCE IT SHOWS A CONDUIT FROM THE GENERATOR?
 THE GENERATOR WOULD NOT TIE IN TO A CT CAN. FURTHER
 CLARIFICATION AND/OR CORRECTION NEEDED FOR RISER. FROM
 METER CAN TO FIRST MEANS OF DISCONNECT, THERE WOULD NOT
 BE AN EQUIPMENT GROUNDING CONDUCTOR (EGC). AFTER THE
 FIRST MEANS, THERE SHOULD BE AN EGC IN EACH CONDUIT.)
 6. IF METER FEEDS DIRECTLY TO PANEL A, THIS PANEL IS
 REQUIRED TO HAVE A MAIN BREAKER. PROVIDE CORRECTION.
 PROVIDE INDICATION THAT TRANSFER SWITCH IS SERVICE
 RATED. NEC 110.3, 230.70; FBC RE E3601.6 (COMMENT IS
 RELATED TO COMMENT 5, WITH FURTHER CORRECTION THIS WILL
 PROBABLY BE ADDRESSED.)
 7. CORRECTED.
 8.CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. WITH THE EXCEPTION OF THE CABANA BATH, PLAN DOES
 NOT SHOW THE 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 (POSSIBLY CIRCUITS 18 AND 20 IN PANEL A?, BUT THIS IS
 NOT SHOWN AS BATHROOM GFCI.)
 13. CLOSET LIGHTS ARE SHOWS AS STANDARD RECESS LIGHTS
 OR A CHANDELIER J-BOX. PER CODE: LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (THESE
 LIGHTS ARE STILL SHOWN AS STANDARD RECESS LIGHTS, AND
 SOME ARE SHOWN DIRECTLY OVER THE STORAGE SPACE, WHICH
 IS A VIOLATION FOR MOST TYPES OF LIGHTS. CORRECTION IS
 NEEDED.)
 14. CORRECTED.
 15. CORRECTED.
 16. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE
 ALARM ON EACH STORY OF THE DWELLING. SMOKE ALARMS MUST
 BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1; NFPA 72:29.8.3.4 (SYMBOL USED IS NOT IN LEGEND
 AND APPEARS TO BE A SMOKE ALARM ONLY, AS IT DOES NOT
 HAVE AN "SD" INSIDE THE SYMBOL. A CARBON MONOXIDE ALARM
 IS REQUIRED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. PROVIDE CORRECTION.)
 17. PROVIDE GFCI PROTECTED RECEPTACLE ON BALCONIES. NEC
 210.52(E); FBC RE E3901.7 (BALCONIES THAT CAN BE
 ACCESSED FROM THE INTERIOR OF THE HOME, EVEN IF YOU
 CAN'T WALK OUT ONTO THE BALCONY, MUST HAVE A RECEPTACLE
 OUTLET. THE WEST ELEVATION IS MISSING THIS. PROVIDE
 CORRECTION.)
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. PROVIDE AIC RATING OF SERVICE DISCONNECT, TRANSFER
 SWITCH, AND PANELS. NEC 110.3, 110.9 (NOT SHOWN ON
 PANEL SCHEDULES, MUST BE RATED TO MEET OR EXCEED AIC
 CALCULATION PROVIDED.)
 24. CORRECTED.
  
 NEW COMMENT:
  
 25. NOW THAT THE ROOMS ARE IDENTIFIED ON THE PLAN, I
 SEE THERE IS A STORAGE AREA (ROOM 103) AND A WORKSHOP
 (ROOM 119). THESE AREAS SHOULD HAVE GFCI PROTECTED
 OUTLETS. NEC 210.8(A)(2); FBC RE E3902.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-29 Cont ID  
Sent By ppetty Date 2018-08-29 Time 09:01 Rev Time 0.00
Received By ppetty Date 2018-08-29 Time 09:01 Sent To  
Notes
2018-08-29 09:01:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. LOAD CALCULATION SHOWS 40,434 WATTS HVAC LOAD, BUT
 THE PANEL SCHEDULES ONLY SHOW THREE SYSTEMS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 215.5, 220; FBC RE
 E3602.2; WPB FBC 107.2.1
 5. RISER SHOWS A METER CAN FEEDING A MLO PANEL (PANEL
 A) AND THE GENERATOR TRANSFER SWITCH (MUST BE SERVICE
 RATED. FIRST FLOOR PLAN SHOWS A METER WITH A MAIN
 DISCONNECT ON CORNER OF GARAGE WITH THE PANELS AND
 TRANSFER SWITCH INSIDE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.5; WPB FBC 107.2.1
 6. IF METER FEEDS DIRECTLY TO PANEL A, THIS PANEL IS
 REQUIRED TO HAVE A MAIN BREAKER. PROVIDE CORRECTION.
 PROVIDE INDICATION THAT TRANSFER SWITCH IS SERVICE
 RATED. NEC 110.3, 230.70; FBC RE E3601.6
 7. SERVICE CONDUCTORS FROM METER CAN TO PANELS IS SHOWN
 AS # 2/0 WIRE TO A 200 AMP PANEL. WIRE SIZES FROM NEC
 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED WHEN
 THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE
 THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE FROM
 METER CAN TO PANELS, RATED FOR THE 200 AMPS SPECIFIED.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
 8. PLAN SHOWS AHU?S BEING FED WITH #6 WIRE ON A 60 AMP
 BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE E3705.4.4
 9. OK
 10. OK
 11. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10
 12. WITH THE EXCEPTION OF THE CABANA BATH, PLAN DOES
 NOT SHOW THE 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 13. CLOSET LIGHTS ARE SHOWS AS STANDARD RECESS LIGHTS
 OR A CHANDELIER J-BOX. PER CODE: LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 14. OK
 15. OK
 16. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE
 ALARM ON EACH STORY OF THE DWELLING. SMOKE ALARMS MUST
 BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1; NFPA 72:29.8.3.4
 17. PROVIDE GFCI PROTECTED RECEPTACLE ON BALCONIES. NEC
 210.52(E); FBC RE E3901.7
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-19 Cont ID  
Sent By jpearson Date 2018-06-19 Time 18:14 Rev Time 0.00
Received By jpearson Date 2018-06-18 Time 07:17 Sent To  
Notes
2018-06-19 18:14:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC SPECIFIED FOR DESIGN ON SHEET A1 DOES NOT
 EXIST. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. THE LOAD CALCULATION FOR THE WHOLE HOUSE SHOWS A
 LOAD OF 4200 WATTS FOR FOUR SMALL APPLIANCE CIRCUITS. A
 MINIMUM OF 1500 WATTS OR EACH SMALL APPLIANCE CIRCUIT
 MUST BE INCLUDED. PROVIDE CORRECTION. NEC 220.52; FBC
 RE E3602.2
 3. WHOLE HOUSE LOAD CALCULATION SHOWS A LOAD FOR
 ELECTRIC RANGE AS 1500 WATTS. AN ELECTRIC RANGE MUST BE
 CALCULATED AT A MINIMUM OF 8000 WATTS AND HAVE A BRANCH
 CIRCUIT WITH A MINIMUM RATING OF 40 AMPERES. PROVIDE
 CORRECTION. NEC 210.21(B)(4); FBC RE E3702.9
 4. LOAD CALCULATION SHOWS 40,434 WATTS HVAC LOAD, BUT
 THE PANEL SCHEDULES ONLY SHOW THREE SYSTEMS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 215.5, 220; FBC RE
 E3602.2; WPB FBC 107.2.1
 5. RISER SHOWS A METER CAN FEEDING A MLO PANEL (PANEL
 A) AND THE GENERATOR TRANSFER SWITCH (MUST BE SERVICE
 RATED. FIRST FLOOR PLAN SHOWS A METER WITH A MAIN
 DISCONNECT ON CORNER OF GARAGE WITH THE PANELS AND
 TRANSFER SWITCH INSIDE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.5; WPB FBC 107.2.1
 6. IF METER FEEDS DIRECTLY TO PANEL A, THIS PANEL IS
 REQUIRED TO HAVE A MAIN BREAKER. PROVIDE CORRECTION.
 PROVIDE INDICATION THAT TRANSFER SWITCH IS SERVICE
 RATED. NEC 110.3, 230.70; FBC RE E3601.6
 7. SERVICE CONDUCTORS FROM METER CAN TO PANELS IS SHOWN
 AS # 2/0 WIRE TO A 200 AMP PANEL. WIRE SIZES FROM NEC
 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED WHEN
 THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE
 THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE FROM
 METER CAN TO PANELS, RATED FOR THE 200 AMPS SPECIFIED.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
 8. PLAN SHOWS AHU?S BEING FED WITH #6 WIRE ON A 60 AMP
 BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE E3705.4.4
 9. BREAKER FOR POOL PUMP AND JACUZZI TUB REQUIRED TO BE
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 680.21(C),
 680.43(A)(3), 680.71; FBC RE E4203.1.3, E4209.1
 10. BE ADVISED THAT THE GENERATOR AND SWIMMING POOL ARE
 NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE
 A BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS
 AND PLAN SUBMITTALS FOR THESE SYSTEMS. WPB FBC 105.1,
 107.2.1
 11. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10
 12. WITH THE EXCEPTION OF THE CABANA BATH, PLAN DOES
 NOT SHOW THE 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 13. CLOSET LIGHTS ARE SHOWS AS STANDARD RECESS LIGHTS
 OR A CHANDELIER J-BOX. PER CODE: LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 14. SOME LIGHTING OVER BATHTUBS OR SHOWERS ARE SHOWS AS
 STANDARD LIGHTS OR A CHANDELIER J-BOX. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. LIGHTING IN BATHTUB OR SHOWER AREAS
 SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE
 CORRECTION. NEC 410.10(D); FBC RE E4003.11
 15. IDENTIFY ROOMS ON ELECTRICAL PLAN. WPB FBC 107.2.1
 16. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. PROVIDE SMOKE
 ALARM ON EACH STORY OF THE DWELLING. SMOKE ALARMS MUST
 BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1; NFPA 72:29.8.3.4
 17. PROVIDE GFCI PROTECTED RECEPTACLE ON BALCONIES. NEC
 210.52(E); FBC RE E3901.7
 18. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.2
 19. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 20. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 21. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 22. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 23. PROVIDE AIC RATING OF SERVICE DISCONNECT, TRANSFER
 SWITCH, AND PANELS. NEC 110.3, 110.9
 24. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-21 Cont ID  
Sent By gjohnson Date 2018-06-21 Time 07:53 Rev Time 0.00
Received By gjohnson Date 2018-06-21 Time 07:53 Sent To  
Notes
2018-06-21 07:54:45GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
  
 13. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT,
 SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS
 SYSTEM.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 16:32 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 16:32 Sent To  
Notes
2018-10-12 15:35:08RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-21 Cont ID  
Sent By lmarchan Date 2018-09-21 Time 10:25 Rev Time 0.00
Received By lmarchan Date 2018-08-10 Time 13:55 Sent To  
Notes
2018-08-14 13:55:21R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 10:42 Rev Time 0.00
Received By shill Date 2018-05-24 Time 13:42 Sent To  
Notes
2018-05-25 13:42:37R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 13:00 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 13:00 Sent To  
Notes
2018-09-12 13:04:12CUSTOMER SPOKE TO S.H. AND D.B. ABOUT THE COMMENTS AND
 PLAM BEACH COUNTY HAD NO ADDITIONAL FEES DUE TO
 EXISTING SQ. FOOTAGE EXCEEDING PROPOSED.
 PLANS ARE STAMPED FROM PBC.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 07:44 Rev Time 0.00
Received By shill Date 2018-06-22 Time 09:50 Sent To  
Notes
2018-06-29 07:44:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By cmontell Date 2018-09-20 Time 15:02 Rev Time 0.00
Received By cmontell Date 2018-09-20 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By hmoser Date 2018-06-13 Time 08:56 Rev Time 0.00
Received By hmoser Date 2018-06-12 Time 13:30 Sent To  
Notes
2018-06-13 09:10:56PLAN DENIED
 1) REFER TO SECTION R 403.3.6 AIR HANDLING UNITS
 2017 FLORIDA ENERGY CODE.
 2) REFER TO SECTION M 1503.4 MAKE UP AIR. PROVIDE
 MANUFACTURES SPECIFICATIONS ON KITCHEN HOOD.
  
 PLAN REVIEW BY HAROLD MOSER
 HMOSER @ WPB.ORG
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 16:08 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 16:24 Sent To  
Notes
2018-10-16 16:08:443RD REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
  
 1. RE: PLAN SHEET P3; SANITARY ISOMETRIC
 A. KITCHEN 224 SINK: PROVIDE AIR ADMITTANCE VALVE
 CONNECTING ABOVE THE TRAP WEIR OF THE FIXTURE PER FBC
 RES SECTION P3114.
 B. RED LINED ON THE PLAN TO CLARIFY.
 2. RE: PLAN SHEET P3; PLUMBING NOTES
 A. NOTE 11 REGARDING AC CONDENSATE SYSTEM(S); SEE M.2
 MECHANICAL PLAN FOR SIZE AND ROUTING. INSULATE IN
 INTERIOR SPACES.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-11 Cont ID  
Sent By shill Date 2018-09-11 Time 12:31 Rev Time 0.00
Received By jesmith Date 2018-09-11 Time 13:52 Sent To  
Notes
2018-09-11 12:31:322ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051174
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET P3;
 A. SHOW TRAP ON ALL UNDERFLOOR FIXTURE DRAINS, IE.
 BATHTUBS AND SHOWERS, UNLESS FIXTURE IS INTEGRALLY
 TRAPPED, IE. WATER CLOSETS. FBC WPB AMEND 107.2.1, FBC
 RES P3201.2
 B. OVAL SYMBOLS AT END OF HORIZONTAL PIPING FOR WATER
 CLOSETS AND DISHWASHERS ARE CONFUSING. PROVIDE VERTICAL
 EXTENSION AT END OF WATER CLOSET HORIZONTAL AND PLACE
 OVAL SYMBOL AT TOP PER FBC WPB AMEND 107.2.1.
 DISHWASHER IS TO CONNECT TO SINK TAILPIECE ABOVE TRAP,
 NOT DOWNSTREAM OF TRAP PER FBC RES P2717.2
 C. IDENTIFY ALL FIXTURES ON SANITARY ISOMETRIC.
 D. SIZE ALL VENTS, FIXTURE DRAINS, FIXTURE BRANCHES,
 STACKS, BUILDING DRAIN AND BRANCHES OF THE BUILDING
 DRAIN. FBC WPB AMEND 107.2.1
 2. RE: PLAN SHEET P3; PLUMBING NOTES
 A. NOTE 1; CHANGE THE WORDS "ALL APPLICABLE CODES" TO
 "THE 2017 FBC RESIDENTIAL CODE AND CITY OF WEST PALM
 BEACH AMENDMENTS TO 2017 FBC". FBC WPB AMEND 107.2.1
 B. NOTE 11 REQUIRES PLUMBING CONTRACTOR TO PROVIDE
 COMPLETE CONDENSATION SYSTEM. PROVIDE PIPING LAYOUT ON
 FLOOR PLAN AND PIPING RISER DIAGRAM TO INCLUDE SIZING
 AND DISPOSITION OF CLEAR WASTE. PROVIDE TRAP DETAIL AND
 TERMINAL DETAIL, IE. DRYWELL. PROVIDE SPEC FOR
 INSULATION IN THE INDOOR SPACES. FBC WPB AMEND 107.2.1
 C. NOTE 14: THE USE OF AIR CHAMBERS IS NOT AN
 ACCEPTABLE METHOD FOR PREVENTION OF WATER HAMMER;
 PROVIDE WATER HAMMER ARRESTORS IN ACCORDANCE WITH
 MANUFACTURER'S INSTRUCTIONS. FBC RES P903.5
 D. ADD NOTE: SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 2017 FBC RES 2708.4
 E. ADD NOTE: AN ACCESSIBLE TEMPERATURE LIMITING DEVICE
 REQUIRED ON HOT WATER TO BATHTUB VALVE(S) IS REQUIRED.
 2017 FBC RES 2713.3
 3. GROUND FLOOR WASHING MACHINE
 A. P3 SANITARY ISOMETRIC: PROVIDE AAV OR AN INDIVIDUAL
 VENT WASHING MACHINE FIXTURE DRAIN WHICH MAY REVENT TO
 HALF BATH VENT STACK ABOVE FLOOD LEVEL RIM OF THE
 FIXTURES. FBC RES P3101.2.1
 B. P1 FLOOR PLAN: THE WASHING MACHINE ON THE FIRST
 FLOOR SHALL CONNECT DOWN STREAM OF THE HALF BATHROOM
 GROUP. PER FBC RES P3108.1. COORDINATE WITH SANITARY
 ISOMETRIC ON P3.
 4. BATH(S)209/210:
 A. P3 SANITARY ISOMETRIC; URINAL IS A WALL DISCHARGE
 FIXTURE. IT CANNOT CONNECT HORIZONTALLY TO HORIZONTAL
 FIXTURE BRANCH. PROVIDE AAV OR AN INDIVIDUAL VENT ABOVE
 VERTICAL WASTE PIPE WHICH MAY REVENT TO BATH VENT STACK
 ABOVE FLOOD LEVEL RIM OF THE FIXTURES. FBC RES
 P3101.2.1
 B. P1 SECOND FLOOR PLAN IS CONFUSING. HORIZONTAL
 DRAINAGE BRANCH TO 210 BT AND SHOWER IS NOT SHOWN;
 HORIZONTAL PIPING FOR 209/210 DOES NOT MATCH ISOMETRIC
 ON P3. FBC WPB AMEND 107.2.1
 5. BATH 228
 A. P3: A FIXTURE IS MISSING ON SANITARY ISOMETRIC.
 PLEASE CLARIFY. FBC WPB AMEND 107.2.1
 B. P1: BATHTUB AND WATER CLOSET FIXTURE DRAINS SHOWN
 CONNECTING TO EACH OTHER BEFORE CONNECTING TO(WET)VENT.
 MUST CONNECT INDEPENDENTLY TO VENT FBC RES 3108.1;
 FIXTURE DRAIN LENGTH TRAP TO VENT TO BE IN ACCORDANCE
 WITH FBC RES TABLE P3105.1.
 C. P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT
 MATCH. PLEASE CLARIFY.
 6. LAUNDRY RM 202: P1 SECOND FLOOR PLAN IS CONFUSING.
 HORIZONTAL FIXTURE DRAIN FROM WASHING MACHINE SOIL
 STACK TO IS NOT SHOWN; DOES NOT MATCH ISOMETRIC ON P3.
 PLEASE CLARIFY. FBC WPB AMEND 107.2.1
 7. CABANA BATH 123: P1 AND P3; HORIZONTAL FIXTURE DRAIN
 FROM OUTDOOR KITCHEN SINK MUST CONNECT DOWNSTREAM FROM
 CABANA BATH WET VENT, NOT AT THE JUNCTION. FBC RES
 P3108.1
 8. HER BATH 217: P1 PLAN VIEW PIPING AND P3 SANITARY
 ISOMETRIC DO NOT MATCH. HORIZONTAL PIPING FROM LAV AND
 SHOWER TO SOIL STACK NOT SHOWN ON P1. PLEASE CLARIFY;
 NOTE THAT PIPING IN ACCORDANCE WITH THE DRAINAGE FLOW
 SHOWN ON P3 MEETS THE REQUIREMENTS OF
 P3108.1(HORIZONTAL WET VENTING)WITHOUT THE NEED OF THE
 INDIVIDUAL VENTS SHOWN AT THE WATER CLOSET AND BATHTUB.
 9. HALF BATH RM 120/WORKSHOP 119 SINK: WORKSHOP SINK TO
 CONNECT DOWNSTREAM OF HALF BATH. FBC RES P3108.1. SHOW
 ON P1 AND P3. FBC WPB AMEND 107.2.1
 10. KITCHEN 224 SINK: NOTE LOCATION OF WASTE STACK FROM
 BELOW AND SHOW ANY UNDERFLOOR HORIZONTAL PIPING
 REQUIRED ON SECOND FLOOR PLAN P1. P1 AND P3 TO MATCH.
 FBC WPB AMEND 107.2.1
 P1 PLAN VIEW PIPING AND P3 SANITARY ISOMETRIC DO NOT
 MATCH. PLEASE CLARIFY.
 11. RE; P2 WATER DISTRIBUTION PLAN. SHOW BRANCH PIPING
 IN 1ST FLOOR CEILING TO RISERS TO SECOND FLOOR. PLEASE
 SIZE ALL RUNOUTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By gjohnson Date 2018-06-20 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2018-06-20 Time 15:34 Sent To  
Notes
2018-06-20 17:11:391ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. E3 THE WASHING MACHINE ON THE FIRST FLOOR SHALL
 CONNECT DOWN STREAM OF THE HALF BATHROOM GROUP. PER FBC
 RES P3108.4
  
 2. THE KITCHEN SINK IN ROOM 115 SHALL BE VENTED BY AN
 AAV OR THE VENT SHALL RUN UP TO SECOND FLOOR ABOVE
 FLOOD LEVEL RIM OF THE FIXTURES BEFORE REVENTING INTO
 THE VENT STACK. PER FBC RES P3101.2.1
  
 3. THE HALF BATHROOM #120 SHALL BE VENTED SEPARATELY
 FROM THE UPSTAIRS KITCHEN AND CONNECT TO THE HORIZONTAL
 BUILDING DRAIN NOT THE SOIL STACK. PER FBC RES
 P3101.2.1 , P3108.4
  
 4. THE SINK IN THE WORK SHOP SHALL CONNECT TO THE
 BUILDING DRAIN DOWN STREAM OF THE HALF BATHROOM.
 P3108.4
  
 5. PLEASE PROVIDE PLUMBING FLOOR PLAN INCLUDING WATER
 AND SANITARY TO DETERMINE CODE COMPLIANCE OF PLUMBING
 SYSTEM DESIGN. PER WPB AMEND TO FBC 107.2.1
  
 6. UNDER WORK DESCRIPTION ON PERMIT APPLICATION IT
 STATES A 14X 35 FIBERGLASS POOL PROVIDE PLANS OR REMOVE
 FROM WORK DESCRIPTION. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 12:57 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 12:56 Sent To  
Notes
2018-09-12 12:59:17PRODUCT APPROVALS WERE SUBMITTED AND APPROVED.
 THE ROOFING SUB CONTRACTOR WILL SUPPLY ENGINEERING FOR
 ROOF ZONES AND MODIFIED NAILING AS NEEDED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 07:43 Rev Time 0.00
Received By shill Date 2018-06-22 Time 09:52 Sent To  
Notes
2018-06-29 07:43:54SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By mcruz Date 2018-08-21 Time 16:52 Rev Time 0.00
Received By mcruz Date 2018-08-21 Time 16:43 Sent To PC
Notes
2018-08-21 16:43:36PASSED WITH PROVISOS: OVERHANG SHALL NOT ENCROACH MORE
 THAN 3' INTO A SETBACK. A/C PAD SHALL BE AT LEAST 6'
 FRONT SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-14 Cont ID  
Sent By avann Date 2018-06-14 Time 16:16 Rev Time 0.00
Received By mcruz Date 2018-06-14 Time 16:15 Sent To PC
Notes
2018-06-14 16:16:47PASSED WITH PROVISOS: OVERHANG SHALL NOT ENCROACH MORE
 THAN 3' INTO A SETBACK. A/C PAD SHLL BE AT LEAST 6'
 FROMT SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]