Plan Review Details - Permit 18051164
Plan Review Stops For Permit 18051164
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By cthroop Date 2018-07-30 Time 12:48 Rev Time 0.00
Received By cthroop Date 2018-07-30 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 12:13 Rev Time 0.00
Received By shill Date 2018-06-16 Time 12:13 Sent To  
Notes
2018-06-16 12:15:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. FBC 1609, THE SPECIFICATION IS FOR "3/8 TEC SCREWS".
 SPECIFY MINIMUM EMBEDMENT OR LENGTH AND FASTENING
 PATTERN.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By fgiaquin Date 2018-07-19 Time 06:10 Rev Time 0.00
Received By fgiaquin Date 2018-07-19 Time 05:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By fgiaquin Date 2018-06-14 Time 05:40 Rev Time 0.00
Received By fgiaquin Date 2018-06-14 Time 05:22 Sent To B
Notes
2018-06-14 05:39:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER.FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. DISCONNECT REQUIRED WITHIN SIGHT OF SIGNS. NEC
 600.6A(1)
  
 3. DUE TO THE DISCONNECT REQUIREMENTS OF NEC 600.6A(1)
 AN ELECTRICAL SUB-PERMIT CANNOT BE ISSUED TO A
 CONTRACTOR HOLDING AN ES LICENSE. A CONTRACTOR WITH AN
 ER OR EC LICENSE MUST APPLY FOR THE PERMIT AND PERFORM
 THE NECESSARY WORK. PLEASE SEE SCOPE OF WORK FOR ES
 LICENSE.
  
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN
 CONTRACTORS, SPECIALTY ELECTRICAL CONTRACTORS, (#2 SIGN
 SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION
 INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE
 FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR,
 SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE
 LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE
 THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE
 LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A
 CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE
 ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN
 DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE
 INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH
 REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO
 HUNDRED FIFTY (250) VOLTS MAXIMUM.
  
 4. VALUE OF WORK TOO LOW, PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-15 Cont ID  
Sent By cpuell Date 2018-08-15 Time 14:54 Rev Time 0.00
Received By cpuell Date 2018-08-09 Time 13:29 Sent To  
Notes
2018-08-10 13:30:03RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By cthroop Date 2018-07-30 Time 12:48 Rev Time 0.00
Received By cthroop Date 2018-07-12 Time 13:35 Sent To I
Notes
2018-07-30 10:48:217/30 TO CT DESK
  
2018-07-17 14:38:49TO LAURA MARCHANT FROM ZONING 7/17
2018-07-13 13:36:10RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By aaponte Date 2018-06-16 Time 12:15 Rev Time 0.00
Received By shill Date 2018-05-24 Time 10:52 Sent To Z
Notes
2018-05-24 16:22:34TO LMARCHANT FOR ROUTING
2018-05-24 10:52:40ROUTED TO AAPONTE

Review Stop Z ZONING
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By elevesqu Date 2018-08-15 Time 13:56 Rev Time 0.00
Received By elevesqu Date 2018-08-15 Time 13:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-17 Cont ID  
Sent By elevesqu Date 2018-07-17 Time 14:38 Rev Time 0.00
Received By elevesqu Date 2018-07-17 Time 14:36 Sent To E
Notes
2018-07-17 14:38:12GARAGE SIGNAGE EXCEEDS ALLOWABLE 60% OF GARAGE
 ENTRANCE. PLEASE REVISE TO MEET SIZE REQUIREMENT.
  
 CALL LIZ LEVESQUE, URBAN DESIGN PLANNER WITH ANY
 QUESTIONS 561 822 1426

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By shill Date 2018-06-16 Time 12:15 Rev Time 0.00
Received By aaponte Date 2018-05-24 Time 16:15 Sent To E
Notes
2018-05-24 16:21:471. PLEASE IDENTIFY IN ONE PLAN THE LOCATION OF ALL THE
 SIGNS.
 2.STAFF RECOMMENDS THE SIGN NEXT TO THE RESIDENTIAL
 ENTRANCE TO BE LOWER. AT THE HEIGHT OF THE ADJACENT
 CANOPIES.
 3. PLEASE PROVIDE DIMENSIONS OF SIGN AT THE TOP OF
 PODIUM LEVEL.
 4. PLEASE INDICATE THE RESIDENTIAL ENTRANCE FRONTAGE
 DIMENSIONS FOR EACH OF THE SIGNS. THE MAXIMUM WIDTH
 ALLOWED FOR THE SIGN IS BASED ON THE FRONTAGE.
 5. PLEASE PROVIDE DIMENSIONS OF THE PARKING GARAGE
 ENTRANCE. THE WIDTH OF THE SIGN IS BASED ON THE WIDTH
 OF THE FRONTAGE.
 FOR ADDITIONAL INFORMAITON PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.