Plan Review Details - Permit 18051052
Plan Review Stops For Permit 18051052
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:16 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By jpearson Date 2018-07-12 Time 15:50 Rev Time 0.00
Received By jpearson Date 2018-07-12 Time 15:50 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By jpearson Date 2018-06-15 Time 11:15 Rev Time 0.00
Received By jpearson Date 2018-06-15 Time 08:56 Sent To  
Notes
2018-06-15 11:15:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 2. PROVIDE GFCI PROTECTION FOR RECEPTACLES PER NEC
 210.8
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.
 4. PLAN SHOWS A CHANDELIER IN BATHROOM. BE ADVISED THAT
 NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-,
 OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS,
 OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED
 WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION IF NEEDED, SIZE OF
 CHANDELIER NOT SHOWN. NEC 410.10(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By pleduc Date 2018-05-25 Time   Rev Time 0.00
Received By pleduc Date 2018-05-25 Time 12:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-07-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-10 Time 10:44 Sent To  
Notes
2018-07-12 10:44:34RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:17 Rev Time 0.00
Received By shill Date 2018-05-22 Time 13:51 Sent To  
Notes
2018-05-23 13:51:32B19

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-14 Cont ID  
Sent By gjohnson Date 2018-06-14 Time 13:01 Rev Time 0.00
Received By gjohnson Date 2018-06-14 Time 12:47 Sent To  
Notes
***NONE***