| 2018-07-05 14:51:43 | 1) INDICATE THE LEVEL OF ALTERATION ON BOTH SETS OF |
| | PLANS PER THE 2017 FBC-EXISTING SECTION 301.1. |
| | 2) SHT. L-3 - SHOW THE LOCATION OF THE IRRIGATION PUMP, |
| | CONTROLLER AND RAIN SENSOR. ALSO, SHOW THE WATER SOURCE |
| | FOR THE IRRIGATION SYSTEM ON THE PLAN. IF CONNECTED TO |
| | CITY WATER, A REDUCED PRESSURE ZONE BACKFLOW PREVENTION |
| | DEVICE WILL BE REQUIRED ON THE IRRIGATION SYSTEM.CWPB |
| | CROSS-CONNECTION CONTROL MANUAL & WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 3) PLACE A NOTE ON SHT. L-3 THAT IRRIGATION HEADS SHALL |
| | BE PLACED A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE |
| | SIDEWALL. 2017 FBC- PLUMBING SEC.318.1. |
| | 4) SHT. ALS 1.1 - PLUMBING FIXTURE REQUIREMENTS - THE |
| | TOILET FACILITIES ARE NOTED AS "UNISEX." THE TOILET |
| | ROOMS MUST BE DESIGNATED AS "MALE" AND "FEMALE" IN |
| | ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC. 403.2. |
| | 5) SHT. A9.0.2 - SHOW THE CLEAR INSIDE DIMENSIONS ( L X |
| | W ) OF THE ALL THE TOILET ROOMS ON THE PLANS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 6) SHT. A9.0.2. - SHOW THE INSIDE CLEAR DIMENSIONS OF |
| | THE ACCESSIBLE SHOWER IN THE STAFF TOILET ROOM ON THE |
| | PLANS. COMPLY WITH 2017 FBC-ACCESS. SEC.608.2. |
| | 7) SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR |
| | THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY WITH 2017 |
| | FBC-ACCESS. SECS. 608.2.1, 604.3, 606.2 |
| | 8) SHT. A9.0.1 - THE STAFF ROOM SINK SHALL COMPLY WITH |
| | 2017 FBC-ACCESSIBILITY SEC.606.2. |
| | 9) SUBMIT A RAINWATER RISER AND SHOW THE SIZE OF THE |
| | ROOF DRAINS ON SHT. A2.0.1 AND HOW YOU ARRIVED AT THE |
| | ROOF DRAIN SIZE. COMPLY WITH 2017 FBC-PLUMBING |
| | SEC.1106.2. |
| | 10) SHT. A5.0.2 - SUBMIT CALCULATIONS FOR THE SIZING OF |
| | THE INTEGRAL GUTTERS AT THE ROOF EDGE. COMPLY WITH |
| | TABLE 1106.6 OF THE 2017 FBC-PLUMBING. |
| | 11) SHT. A9.0.1 -THE REFRESHMENT CENTER CABINET HEIGHT |
| | SHALL BE A MAXIMUM OF 34 INCHES IN HEIGHT. 2017 |
| | FBC-ACCESS. SEC.902.3. IDENTIFY THE REFRESHMENT CENTER |
| | ON SHT. A9.0.2. |
| | 12) SHT.A9.0.1 - TTHE MAXIMUM HEIGHT OF THE SINK |
| | CABINET IN THE STAFF LOUNGE SHALL BE 34 INCHES MAXIMUM |
| | PER 2017 FBC-ACCESS. SEC.902.3. |
| | 13) SHT. A9.0.2 - DETAILS A, B & C - DETAIL A NOTES THE |
| | TOILET ROOMS AS #104 & #105 BUT THE FLOOR PLAN SHOWS |
| | #118 & 119.THE SAME TYPE OF DISCREPANCY OCCURS ON |
| | DETAILS B & C. CLARIFY. |
| | 14) TOILET ROOM #111 - THE DOOR CANNOT SWING INTO THE |
| | CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2017 |
| | FBC-ACCESS. SEC.603.2.3. |
| | 15) SHT. A9.0.2 - SHOW THE HEIGHT OF THE SHOWER SEAT. |
| | COMPLY WITH 2017 FBC- ACCESS. SECS. 610.3, 610.3.2. |
| | 16) THE GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY |
| | WITH 2017 FBC-ACCESS. SEC.608.3.1 ANSD FIG.608.3.1. |
| | 17) THE LOCATION OF THE SHOWER CONTROLS IN THE STAFF |
| | TOILET SHOWER SHALL COMLY WITH 2017 FBC-ACCESS. |
| | SEC.608.5.1. |
| | 18) THE SHOWER SPRAY UNIT IN THE STAFF TOILET SHOWER |
| | SHALL COMPLY WITH 2017 FBC-ACCESS. SEC.608.6. |
| | 19) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR |
| | FUTURE GRAB BARS IN THE PRIVATE TOILET. SHOW THE TYPE |
| | OF MATERIAL, LENGTH, WIDTH AND HEIGHT OF THE |
| | REINFORCEMENT. 2017 FBC-ACCESS. SECS.604.5, 609.8. |
| | 22) SHT. A10.0.1 - DETAIL #11 - THE SHOWER FLOOR SHALL |
| | BE PITCHED A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN. |
| | 2017 FBC-PLUMBING SEC.417.5.2. |
| | 23) SHT.A10.0.2. - DETAIL #7 - THE MAXIMUM HEIGHT OF |
| | THE CABINET AT THE STAFF LOUNGE SHALL BE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR.2017 FBC-ACCESS. |
| | SEC.902.3. |
| | 24) THE REACH RANGES AT THE CABINETS SHALL COMPLY WITH |
| | 2017 FBC-ACCESS. SEC.308.3.2, |
| | 25) SHT. P2.1 SHOWS ALL THE VENTS THROUGH THE ROOF AND |
| | ALSO LOOPED TOGETHER. WHICH IS IT? CLARIFY. A MINIMUM |
| | OF ONE MMAIN VENT THROUGH THE ROOF IS REQUIRED. 2017 |
| | FBC-PLUMBING SEC.904.1. |
| | 26) SHT. P0.1 - THE SHOWERS ARE SHOWN AS FLOOR DRAINS |
| | WITH TRAP PRIMERS ON THE SANITARY RISERS. REVISE THE |
| | RISER AND CORRECTLY IDENTIFY ALLL THE FIXTURES ON THE |
| | SANITARY RISER.ID |
| | 27) SHT.P0.1 - PLUMBING NOTES - THERE ARE SEVERAL NOTES |
| | THAT REFER TO THE 2010 FBC. CORRECT THE NOTES TO REFER |
| | TO THE 2017 FBC. THIS ALSO OCCURS AT THE WATER HEATER |
| | DETAIL. |
| | 28) THE WATER HEATER TEMPERATURE AND RELIEFF LIINE |
| | SHALL DISCHARGE TO THROUGH AN AIR GAP LOCATED IN THE |
| | SAME ROOM AS THE WATTER HEATER. 2017 FBC-PLUMBING |
| | SEC.504.6 (2) |
| | 29) TEMPERED WATER IS REQUIRED TO THE LAVATORIES IN THE |
| | TOILET ROOMS.2017 FBC-PLUMBING SEC.607.1. TEMPERED |
| | WATER SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070. 2017 |
| | FBC-PLUMBING SEC.607.1.2. |
| | 30 ) HOT WATER IS REQUIRED TO THE STAFF LOUNGE SINK AND |
| | THE MOP SINK. 2017 FBC-PLUMBING SEC. 607.1. |
| | 31) THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| | PIPING FROM THE HOT WATER SOURCE TO THE FIXTURES SHALL |
| | NOT EXCEED 50 FEET.2017 FBC-PLUMBING SEC.607.2. |
| | 32) HOT WATER PIPE SHALL BE INSULATED IN ACCORDANCE |
| | WITH FBC-PLUMBING SEC.607.5. |
| | 33) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER |
| | HEATER DETAIL. |
| | 34) SHOW THE WIDTH OF THE PROPOSED ADAPTABLE SHOWER IN |
| | THE PRIVATE TOILET. |
| | 35) A 30 INCH WIDE MINIMUM BY 48 INCH LONG MINIMUM |
| | CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE |
| | OF THE SHOWER COMPARTMENT. THE SHOWER DOES NOT COMPLY |
| | DUE TO THE LOCATION OF THE WATER CLOSET. 2017 FBC |
| | -ACCESS. SECS. 608.2.2.1 & FIGURE 608.2.2. |
| | 36) A CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48 INCHES |
| | LONG MINIMUM MEAURED FROM THE CONTROL WALL SHALL BE |
| | PROVIDED FOR THE ACCESSIBLE SHOWER IN THE STAFF TOILET. |
| | 2017 FBC _ ACCESS. SEC.608.2.1 & FIGURE 608.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |