Plan Review Details - Permit 18050978
Plan Review Stops For Permit 18050978
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-26 Cont ID  
Sent By cthroop Date 2018-05-26 Time 10:07 Rev Time 0.00
Received By cthroop Date 2018-05-26 Time 10:02 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By fgiaquin Date 2018-07-25 Time 07:06 Rev Time 0.00
Received By jleahy Date 2018-07-25 Time 06:37 Sent To I
Notes
2018-07-25 07:06:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLE NEEDED IN DINING AREA FOR WALL SPACING.
 210.52A1 NEC
  
 2. RECEPTACLE NEEDED IN MASTER BEDROOM FOR WALL SPACING
 BY FIXED WINDOW 210.52A1 NEC
  
 3. NO RECEPTACLE FOR FRIDGE OR WASHER AND DRYER.
 210.50C NEC
  
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
  
 4. RECEPTACLE REQUIRED ON BALCONY 210.52E3 NEC
  
 5. NO LIGHTS OR SWITCHED RECEPTACLE IN LIVING ROOM.
 210.70A1
  
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 7. SHOW LOCATION OF EXISITNG PANEL AND ANNOTATE IF IT
 IS TO BE REPLACED. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By fgiaquin Date 2018-06-12 Time 06:00 Rev Time 0.00
Received By fgiaquin Date 2018-06-12 Time 05:24 Sent To I
Notes
2018-06-12 06:00:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN SUBMITTED FOR REVIEW, ONLY A
 TYPED "SCOPE OF WORK". PROVIDE ELECTRICAL PLAN FOR
 REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WORK
 (DATA/TV/SPEAKERS ETC.) FBC 105.1
  
 3. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC: 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By jleahy Date 2018-07-26 Time 13:00 Rev Time 0.00
Received By jleahy Date 2018-07-23 Time 11:41 Sent To  
Notes
2018-07-24 11:41:15RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-12 Cont ID  
Sent By fgiaquin Date 2018-06-12 Time 06:05 Rev Time 0.00
Received By fgiaquin Date 2018-05-21 Time 14:02 Sent To  
Notes
2018-05-22 14:02:33BLDG MISC 1