Plan Review Details - Permit 18050934
Plan Review Stops For Permit 18050934
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-19 Cont ID  
Sent By shill Date 2018-10-19 Time 06:36 Rev Time 0.00
Received By shill Date 2018-10-19 Time 06:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 07:29 Rev Time 0.00
Received By shill Date 2018-09-27 Time 07:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-13 Cont ID  
Sent By cthroop Date 2018-08-13 Time 09:32 Rev Time 0.00
Received By cthroop Date 2018-08-13 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By cthroop Date 2018-05-29 Time 11:53 Rev Time 0.00
Received By cthroop Date 2018-05-26 Time 08:15 Sent To  
Notes
2018-05-29 12:15:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. THERE ARE MULTIPLE BUILDINGS ON
 THIS SITE. PLEASE IDENTIFY THE CLINICAL BLDG. THAT THIS
 PERMIT IS FOR.
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 2. EITHER PROVIDE NOA'S PER WINDOW AND DOOR SCHEDULE OR
 PROVIDE STATEMENT ON PLANS THAT THE NOA'S WILL BE
 DEFERRED UNTIL A LATER DATE.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-14 Cont ID  
Sent By pleduc Date 2018-09-14 Time   Rev Time 0.00
Received By pleduc Date 2018-09-13 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-11 Cont ID  
Sent By J.Walker Date 2018-07-11 Time   Rev Time 0.30
Received By   Date 2018-07-10 Time   Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By J.Walker Date 2018-05-21 Time   Rev Time 0.30
Received By   Date 2018-05-21 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-19 Cont ID  
Sent By shill Date 2018-10-19 Time 06:36 Rev Time 0.00
Received By shill Date 2018-10-12 Time 14:28 Sent To  
Notes
2018-10-15 14:28:32RESUB ROUTED TO JESMITH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 07:29 Rev Time 0.00
Received By shill Date 2018-09-06 Time 15:06 Sent To  
Notes
2018-09-07 15:06:25B13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 13:24 Rev Time 0.00
Received By gjohnson Date 2018-07-06 Time 15:59 Sent To  
Notes
2018-07-09 15:59:30B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-29 Cont ID  
Sent By cthroop Date 2018-05-29 Time 12:24 Rev Time 0.00
Received By cthroop Date 2018-05-18 Time 13:58 Sent To I
Notes
2018-05-21 13:58:46ROUTED TO FIRE INBOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 11:47 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 11:46 Sent To  
Notes
2018-10-16 11:47:17PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. RE: PLAN SHEET A2; FLUSH CONTROL FOR ADA COMPLIANT
 WATER CLOSET TO BE LOCATED IN ACCORDANCE WITH FBC ACC
 604.6.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 561-805-6715
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-25 Time 07:19 Rev Time 0.00
Received By jesmith Date 2018-09-25 Time 07:19 Sent To  
Notes
2018-09-27 07:21:40FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1. FBC A 604.5, 604.7, PROVIDE DIMENSIONS FOR ADA
 COMPLIANT GRAB BARS AT WATER CLOSET & DIMENSION TO ADA
 CMOPLIANT TOILET PAPER DISPENSERS.
  
 2. PROVIDE NOTE: PROVIDE TEMPERED WATER TO LAVATORY,
 FBC P 416.5.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 561-805-6715
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 13:23 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 10:29 Sent To  
Notes
2018-08-15 13:24:261ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ALTERATION 1 SHALL COMPLY WITH FBC ACC PER FBC
 EX 705.1
  
 2. BY RECONFIGURING THE BATH IT SHALL COMPLY WITH
 REQUIREMENTS FOR FBC ACC CH 6 PLEASE SHOW COMPLIANCE
 WITH FBC ACC 604.2, 604.3.1, 604.4, 604.5.1, 604.5.2,
 604.7, 606.2, 606.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 10:46 Rev Time 0.00
Received By gjohnson Date 2018-08-08 Time 14:14 Sent To  
Notes
2018-08-09 10:53:321ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ALTERATION 1 SHALL COMPLY WITH FBC ACC PER FBC
 EX 705.1
  
 2. BY RECONFIGURING THE BATH IT SHALL COMPLY WITH
 REQUIREMENTS FOR FBC ACC CH 6 PLEASE SHOW COMPLIANCE
 WITH FBC ACC 604.2, 604.3.1, 604.4, 604.5.1, 604.5.2,
 604.7, 606.2, 606.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  