| Plan Review Stops For Permit 18050933 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-25 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-25 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-10-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-06 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-06 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2018-10-06 13:28:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD, | | | PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE | | | APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A | | | COST BREAKDOWN. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-11 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-11 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2018-08-11 16:09:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD, | | | PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE | | | APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A | | | COST BREAKDOWN. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-15 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-15 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2018-06-15 15:17:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. IT APPEARS THAT THIS SITEHAS SEVERAL BUILDINGS; | | | PROVIDE A SITE PLAN WHICH SHOWS WHICH BUILDING IS | | | COVERED UNDER THIS PERMIT, FBC 107. | | | | | | 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD, | | | PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE | | | APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A | | | COST BREAKDOWN. | | | | | | 3. FBC A 236, 1004, REVISE PLAN TO SHOW COMPLIANCE | | | (EXERCISE MACHINES). | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-25 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-25 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-19 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-19 |
Time |
06:41 |
Sent To |
|
|
| Notes |
| 2018-09-19 11:11:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR | | | THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD. | | | CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND | | | NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%. | | | PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO, | | | THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A | | | WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN | | | CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220; | | | WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE | | | LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR | | | PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10 | | | BELOW.)(3RD REVIEW NOT CORRECTED.) | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS, | | | THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE | | | ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2, | | | 310.15(B)(16), 408.30 (NOT CORRECTED.) | | | 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN | | | THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC | | | 220 (NOT CORRECTED,) | | | 12. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 13. LABEL MAINS SHOWING COMPLIANCE WITH NEC 230.2(E)(1) | | | AND 230.71. | | | 14. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN | | | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF | | | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD | | | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS | | | REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-27 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-27 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2018-07-27 14:09:02 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR | | | THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD. | | | CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND | | | NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%. | | | PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO, | | | THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A | | | WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN | | | CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220; | | | WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE | | | LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR | | | PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10 | | | BELOW.) | | | 8. CORRECTED. | | | 9. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS, | | | THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE | | | ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2, | | | 310.15(B)(16), 408.30 | | | 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN | | | THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC | | | 220 | | | 12. RISER SHOWS A THREE PHASE FEED TO TRANSFORMER, BUT | | | IT APPEARS TO BE A SINGLE PHASE TRANSFORMER. PROVIDE | | | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-06-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-12 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-11 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2018-06-12 08:43:47 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. LOAD CALCULATION PROVIDED FOR SUB-PANEL IS A 3 PHASE | | | CALCULATION, BUT THE PANEL IS SINGLE PHASE. PROVIDE | | | CORRECTION. NEC 220; WPB FBC 107.2.1 | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30 | | | 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | | 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. SOME AREAS DO NOT | | | SHOW THE REQUIRED LIGHTING CONTROL. FBC EC C405.2 | | | 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC C405.6.1 | | | 6. EMERGENCY LIGHTS AND EXIT SIGNS ARE SHOWN ON CIRCUIT | | | 20. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR | | | THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD. | | | CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND | | | NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%. | | | PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO, | | | THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A | | | WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN | | | CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220; | | | WPB FBC 107.2.1 | | | 8. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. THE | | | GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5, | | | 422.52 | | | 9. PROVIDE LOCATION OF MAIN SERVICE ON PLAN. WPB FBC | | | 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-11 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2018-05-23 |
Time |
|
Rev Time |
0.30 |
| Received By |
pleduc |
Date |
2018-05-22 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-05 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-01 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2018-11-02 13:34:20 | ROUTED TO SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-10-30 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-10-12 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-06 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-06 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-11 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-06 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-15 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-18 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-05 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-02 |
Time |
22:47 |
Sent To |
|
|
| Notes |
| 2018-11-05 07:47:03 | PLAN STAMPED, NO MU NUMBER, $0 DUE | | | STAPED APPLICATION TO FILE COPY | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-15 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-15 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2018-06-15 15:19:51 | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED | | | 561-233-5025 FOR MORE INFORMATION | | | | | | AFTER ALL OTHER PLAN REVIEWS HAVE PASSED, CHECK OUT ONE | | | SET OF PLANS TO TAKE TO PALM BEACH COUNTY. THE PLAN | | | STAMPED BY PALM BEACH COUNTY AND THE RECEIPT SHOWING | | | THAT FEES DUE WERE PAID, IF APPLICABLE, ARE TO BE | | | SUBMITTED TO THE BUILDING DIVISION. | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-10-30 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-10-30 |
Time |
10:51 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-19 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-19 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2018-09-19 17:42:51 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18050933 | | | 7/16/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE 175 CFMS OF OUTDOOR AIR FOR THE EXERCISE ROOM IS | | | INADEQUATE PER TABLE 403.3.1.1 FBC M, AND NEEDS TO BE | | | INCREASED TO 385 CFMS. PER THE TABLE THE OCCUPANT | | | DENSITY FOR 1,429 SF. IS 15 PERSONS. 15 CFMS/ 20 CFMS | | | PER PERSON PLUS 0.6 CFMS/ 1,429 SF. = 385 CFMS. PLEASE | | | CORRECT THE CALCULATION ACCORDINGLY. VERIFY THE | | | EXISTING SYSTEM HAS THE CAPACITY TO CONDITION THE | | | REQUIRED VENTILATION AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-16 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-16 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2018-07-16 14:57:03 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18050933 | | | 7/16/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MP: REFER TO SECTION 601.5(3) FBC M. THE AMOUNT OF | | | RETURN AIR TAKEN FROM ANY ROOM OR SPACE SHALL BE NOT | | | GREATER THAN THE FLOW RATE OF SUPPLY AIR DELIVERED TO | | | SUCH ROOM OR SPACE. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FIRE | | | DAMPERS, AND PROVIDE AN INSTALLATION DETAIL ON THE | | | PLAN- 607.5.2 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-05 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-05 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2018-06-05 16:16:41 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18050933 | | | 6/5/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET MP: THE FRESH AIR CALCULATIONS ARE INDICATING | | | THAT AHU #2 WILL HAVE THE DAMPER ADJUSTED TO BRING IN | | | 1093 CFMS OF OUTDOOR AIR. HOW IS IT POSSIBLE FOR A 3.5 | | | TON SYSTEM TO CONDITION AND DEHUMIDIFY THAT MUCH AIR? | | | PLEASE NOTE THAT THE UNIT ITSELF IS LIMITED TO | | | APPROXIMATELY 1400 CFMS OF SUPPLY AIR, AND TYPICALLY | | | THE RATIO OF FRESH AIR TO SUPPLY AIR IN A SYSTEM RANGES | | | FROM 15- 25% OF THE SUPPLY AIR, OR IN THIS CASE | | | APPROXIMATELY 200-350 CFMS OF FRESH AIR. PLEASE SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE AIR HANDLER | | | VERIFYING THE SYSTEM CAN PROPERLY CONDITION THAT MUCH | | | FRESH AIR- SECTION 403.3.1.1 FBC M. | | | | | | 2) MP: SHOW THE FRESH AIR DUCTS TO THE TWO AIR HANDLERS | | | AND INDICATE HOW THE OUTDOOR AIR WILL BE AUTOMATICALLY | | | CONTROLLED IN COMPLIANCE WITH SECTION C403.2.4.3 FBC EC | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2018-10-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-22 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-22 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2018-09-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-09-28 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-09-28 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2018-09-28 11:20:31 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. HOT WATER IS REQUIRED AT THE SERVICE SINK PER FBC PL | | | 607.1 | | | | | | 2. THE NEW WATER FOUNTAIN AND SERVICE SINK SHALL | | | CONNECT DOWN STREAM OF THE BATHGROOM GROUP. PER FBC PL | | | 912.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-09 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-08 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-13 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-13 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2018-06-13 10:20:07 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.2, 602.4, | | | 602.7 | | | | | | 2. SHT. MP THE WATER ISOMETRIC IS LABELED AS SANITARY | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-18 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-07-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-18 16:53:13 | - CHANGE OF OCCUPANCY FROM RETAIL TO FITNESS/ | | | EXCERCISE. | | | | | | - INTERIOR MODIFICATIONS ONLY. | | | | | | NOTES: | | | | | | * EXISTING TREATMENT FACILITY. | | | | | | * MAX. # OF BEDS PERMITTED = 41 (25 BEDS @ 313 LAKESIDE | | | CT. AND 16 BEDS @ 317 LAKESIDE CT.) | | | | | | * ZONE = GC AND POR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-05-31 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-05-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-31 17:14:39 | - CHANGE OF OCCUPANCY FROM RETAIL TO FITNESS/ | | | EXCERCISE. | | | | | | - INTERIOR MODIFICATIONS ONLY. | | | | | | NOTES: | | | | | | * EXISTING TREATMENT FACILITY. | | | | | | * MAX. # OF BEDS PERMITTED = 41 (25 BEDS @ 313 LAKESIDE | | | CT. AND 16 BEDS @ 317 LAKESIDE CT.) | | | | | | * ZONE = GC AND POR |
|
|