Plan Review Details - Permit 18050931
Plan Review Stops For Permit 18050931
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-25 Cont ID  
Sent By shill Date 2018-10-25 Time 07:19 Rev Time 0.00
Received By shill Date 2018-10-25 Time 07:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 13:32 Rev Time 0.00
Received By shill Date 2018-10-06 Time 13:32 Sent To  
Notes
2018-10-06 13:32:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE
 APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A
 COST BREAKDOWN.
  
 THIS CAN BE SENT VIA EMAIL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 15:40 Rev Time 0.00
Received By shill Date 2018-08-11 Time 15:40 Sent To  
Notes
2018-08-11 15:41:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE
 APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A
 COST BREAKDOWN.
  
 THIS CAN BE SENT VIA EMAIL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 15:05 Rev Time 0.00
Received By shill Date 2018-06-15 Time 15:02 Sent To  
Notes
2018-06-15 15:08:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. IT APPEARS THAT THIS SITEHAS SEVERAL BUILDINGS;
 PROVIDE A SITE PLAN WHICH SHOWS WHICH BUILDING IS
 COVERED UNDER THIS PERMIT, FBC 107.
  
 2. VALUE IS TO INCLUDE ALL LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING/ARCHITECTURE DESIGN FEES. VALUE
 APPEARS TOO LOW. PROVIDE A COPY OF THE CONTRACT AND A
 COST BREAKDOWN.
  
 3. BREAKROOM SINK IS TO COMPLY WITH FBC A 606; PROVIDE
 A DETAIL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-10-23 Cont ID  
Sent By jpearson Date 2018-10-23 Time 09:15 Rev Time 0.00
Received By jpearson Date 2018-10-23 Time 09:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-09-19 Cont ID  
Sent By jpearson Date 2018-09-19 Time 11:39 Rev Time 0.00
Received By jpearson Date 2018-09-19 Time 06:40 Sent To  
Notes
2018-09-19 11:39:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR
 THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD.
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND
 NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%.
 PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO,
 THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A
 WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN
 CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220;
 WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE
 LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR
 PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10
 BELOW.)(3RD REVIEW NOT CORRECTED.)
 8. CORRECTED.
 9. CORRECTED.
 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS,
 THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE
 ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2,
 310.15(B)(16), 408.30 (NOT CORRECTED.)
 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN
 THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC
 220 (NOT CORRECTED,)
 12. CORRECTED.
  
 NEW COMMENT:
  
 13. LABEL MAINS SHOWING COMPLIANCE WITH NEC 230.2(E)(1)
 AND 230.71.
 14. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By jpearson Date 2018-07-27 Time 15:59 Rev Time 0.00
Received By jpearson Date 2018-07-27 Time 10:49 Sent To  
Notes
2018-07-27 15:59:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR
 THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD.
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND
 NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%.
 PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO,
 THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A
 WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN
 CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220;
 WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE
 LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR
 PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10
 BELOW.)
 8. CORRECTED.
 9. CORRECTED.
  
 NEW COMMENT:
  
 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS,
 THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE
 ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2,
 310.15(B)(16), 408.30
 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN
 THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC
 220
 12. RISER SHOWS A THREE PHASE FEED TO TRANSFORMER, BUT
 IT APPEARS TO BE A SINGLE PHASE TRANSFORMER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-11 Cont ID  
Sent By jpearson Date 2018-06-11 Time 17:03 Rev Time 0.00
Received By jpearson Date 2018-06-11 Time 15:29 Sent To  
Notes
2018-06-11 17:03:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION PROVIDED FOR SUB-PANEL IS A 3 PHASE
 CALCULATION, BUT THE PANEL IS SINGLE PHASE. PROVIDE
 CORRECTION. NEC 220; WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 6. EMERGENCY LIGHTS AND EXIT SIGNS ARE SHOWN ON CIRCUIT
 20. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR
 THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD.
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND
 NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%.
 PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO,
 THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A
 WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN
 CALCULATION. MAKE SURE TO INCLUDE ALL LOADS.NEC 220;
 WPB FBC 107.2.1
 8. PROVIDE LOCATION OF ELECTRICAL PANELS AND MAIN
 SERVICE ON PLAN. WPB FBC 107.2.1
 9. THE GFCI DEVICE FOR DRINKING FOUNTAIN MUST BE
 READILY ACCESSIBLE. PROVIDE CORRECTION. NEC 422.5,
 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By pleduc Date 2018-07-10 Time   Rev Time 0.00
Received By pleduc Date 2018-07-10 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By J.Walker Date 2018-05-23 Time   Rev Time 0.30
Received By pleduc Date 2018-05-22 Time 10:42 Sent To  
Notes
2018-05-23 09:10:40C-14

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 15:44 Rev Time 0.00
Received By shill Date 2018-11-01 Time 13:35 Sent To  
Notes
2018-11-02 13:36:02ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-10-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-12 Time 14:16 Sent To  
Notes
2018-10-16 14:16:30C06

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 13:32 Rev Time 0.00
Received By shill Date 2018-09-06 Time 15:02 Sent To  
Notes
2018-09-07 15:02:12C24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 15:41 Rev Time 0.00
Received By shill Date 2018-07-06 Time 15:21 Sent To  
Notes
2018-07-09 15:21:12C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 15:09 Rev Time 0.00
Received By shill Date 2018-05-18 Time 14:00 Sent To  
Notes
2018-05-21 14:01:08C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 15:44 Rev Time 0.00
Received By shill Date 2018-11-06 Time 15:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 15:55 Rev Time 0.00
Received By shill Date 2018-08-11 Time 15:54 Sent To  
Notes
2018-08-11 15:55:09IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 15:09 Rev Time 0.00
Received By shill Date 2018-06-15 Time 15:02 Sent To  
Notes
2018-06-15 15:10:20IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED
 561-233-5025 FOR MORE INFORMATION
  
 AFTER ALL OTHER PLAN REVIEWS HAVE PASSED, CHECK OUT ONE
 SET OF PLANS TO TAKE TO PALM BEACH COUNTY. THE PLAN
 STAMPED BY PALM BEACH COUNTY AND THE RECEIPT SHOWING
 THAT FEES DUE WERE PAID, IF APPLICABLE, ARE TO BE
 SUBMITTED TO THE BUILDING DIVISION.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-10-25 Cont ID  
Sent By ccole Date 2018-10-25 Time 09:05 Rev Time 0.00
Received By ccole Date 2018-10-25 Time 07:20 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 07:25 Rev Time 0.00
Received By ccole Date 2018-09-19 Time 17:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-16 Cont ID  
Sent By ccole Date 2018-07-16 Time 14:05 Rev Time 0.00
Received By ccole Date 2018-07-16 Time 13:55 Sent To  
Notes
2018-07-16 14:08:412ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050931
 7/16/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MP: REFER TO SECTION 601.5(3) FBC M. THE AMOUNT OF
 RETURN AIR TAKEN FROM ANY ROOM OR SPACE SHALL BE NOT
 GREATER THAN THE FLOW RATE OF SUPPLY AIR DELIVERED TO
 SUCH ROOM OR SPACE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-04 Cont ID  
Sent By ccole Date 2018-06-04 Time 17:24 Rev Time 0.00
Received By ccole Date 2018-06-04 Time 17:24 Sent To  
Notes
2018-06-04 17:36:331ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE OUTSIDE AIR DUCTS TO THE AHU'S AND HOW THE
 AIR IS BEING AUTOMATICALLY CONTROLLED PER SECTION
 C403.2.4.3 FBC EC.
  
 2) PLEASE LABEL THE AHU'S AS EXISTING ON THE PLAN AND
 PROVIDE EQUIPMENT SCHEDULES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-10-22 Cont ID  
Sent By gjohnson Date 2018-10-22 Time 10:10 Rev Time 0.00
Received By gjohnson Date 2018-10-22 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-09-26 Cont ID  
Sent By tklarge Date 2018-09-26 Time 13:18 Rev Time 0.00
Received By tklarge Date 2018-09-26 Time 10:16 Sent To  
Notes
2018-09-26 13:07:231) SUBMIT TWO SIGNED AND SEALED COPIES OF THE LETTER
 FROM THE ARCHITECT OF RECORD STATING THAT SEPARATE
 SANITARY FACILITIES ARE LOCATED IN THE ORCHID BULDING
 WING WITHIN 500 FEET OF THE LAVENDER BUILDING PER THE
 NOTE UNDER THE "UNISEX RESTROOM" HEADING ON SHT. A1.
 2) SHT. A1 NOTES THIS SPACE HAS 16 OCCUPANTS. A SERVICE
 SINK AND A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE
 PER THE 2017 FBC-PLUMBING TABLE 403.1
 3) TEMPERED WATER IS REQUIRED AT THE STAFF TOILET
 LAVATORY. 2017 FBC-PLUMBING SEC.416.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 11:05 Rev Time 0.00
Received By gjohnson Date 2018-08-09 Time 11:05 Sent To  
Notes
2018-08-09 11:07:56PROVIDE TWO COPY'S OF LETTER FROM ARCHITECT THAT IS
 LISTED ON SHT. A-1 UNDER UNISEX BATHROOM.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 10:39 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 09:08 Sent To  
Notes
2018-06-13 10:45:091ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3
  
 2. A BACKFLOW DEVISE IS REQUIRED ON THE ICE MACHINE FOR
 THE REFRIGERATOR. PER FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By llouie Date 2018-07-19 Time   Rev Time 0.00
Received By llouie Date 2018-07-19 Time   Sent To  
Notes
2018-07-19 08:28:45CHANGE OF OCCUPANCY FROM DAYCARE USE (NO LONGER IN
 OPERATION) TO ADMINSTRATIVE OFFICE.
  
 NOTE:
  
 * EXISTING TREATMENT FACILITY.
  
 * MAX. NUMBER OF BED PERMITTED = 41 BEDS (25 BEDS @ 313
 LAKESIDE CT. AND 16 BEDS @ 317 LAKESIDE CT.)
  
 * ZONE: GC AND POR
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-31 Cont ID  
Sent By LL Date 2018-05-31 Time   Rev Time  
Received By llouie Date 2018-05-31 Time   Sent To  
Notes
2018-05-31 17:05:06CHANGE OF OCCUPANCY FROM DAYCARE USE (NO LONGER IN
 OPERATION) TO ADMINSTRATIVE OFFICE.
  
 NOTE:
  
 * EXISTING TREATMENT FACILITY.
  
 * MAX. NUMBER OF BED PERMITTED = 41 BEDS (25 BEDS @ 313
 LAKESIDE CT. AND 16 BEDS @ 317 LAKESIDE CT.)
  
 * ZONE: GC AND POR
  