| Plan Review Stops For Permit 18050930 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-25 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-25 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2018-10-25 07:40:50 | PER ARCHITECT, USE WAS ALWAYS DETOX (I-1); NO CHANGE OF | | | OCCUPANCY. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-10-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-06 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-06 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2018-10-06 14:40:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC | | | 109. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-12 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-12 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2018-08-12 14:56:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC | | | 109. | | | | | | 3. I WAS UNABLE TO FIND AN OCCUPANCY CLASSIFICATION ON | | | THE PLAN, PLEASE REVISE TO INCLUDE. | | | | | | THIS WAS NOT A COMMENT ON FIRST REVIEW AS PLANS IMPLIED | | | R4 AND SHOWED COMPLIANCE FOR R4 WHICH IS SUBJECT TO | | | ACCESSIBLITY. A POOL PLAN WAS SUBMITTED WHICH APPEARS | | | TO CLAIM EXCEPTIONS UNDER FAIR HOUSING. | | | | | | PLEASE CORRELATE AND REVISE PLANS ACCORDINGLY. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-30 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-29 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2018-06-30 09:27:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC | | | 109. | | | | | | 3. SEE PLUMBING ACCESSIBILITY COMMENTS; APPLICABLE FOR | | | BUILDING REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-09-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-21 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-21 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2018-09-21 08:35:07 | REVIEWED ONLY SHEET E-1, OTHER SHEET PREVIOUSLY | | | APPROVED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-09 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-08-09 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-08-09 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-25 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-25 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2018-06-25 13:42:14 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. CURRENT LOAD CALCULATION DOES NOT | | | SHOW ALL LOADS. ADDITIONALLY, THERE IS A DEMAND FACTOR | | | OF 50% USED FOR LOAD OVER 10,000 VA WHICH IS A CODE | | | VIOLATION. THIS DEMAND FACTOR IS ONLY TO BE USED FOR | | | RECEPTACLE OUTLET LOAD, NOT FOR THE ENTIRE LOAD. ANY | | | CONTINUOUS LOADS SHOULD BE CALCULATED AT 125%. PROVIDE | | | LOAD FOR PANEL L-2 AND FOR ENTIRE SERVICE. NEC 215.2, | | | 220, TABLE 220.44, 408.30 | | | 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-19 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-09-17 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2018-09-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2018-09-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-17 08:08:42 | MASTER PLAN PASSED. | | | FIRE WILL REQUIRE SHOP DRAWINGS FOR: | | | FIRE ALARM SYSTEM | | | FIRE SPRINKLER SYSTEM | | | LIFE PLAN |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2018-07-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2018-07-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-12 08:43:53 | MASTER PLAN PASSED | | | FIRE WILL REQUIRE SHOP DRAWINGS FOR: | | | FIRE ALARM SYSTEM | | | FIRE SPRINKLER SYSTEM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2018-05-23 |
Time |
|
Rev Time |
0.30 |
| Received By |
|
Date |
2018-05-23 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-06 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-01 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2018-11-02 13:32:01 | ROUTED TO SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-10-30 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-10-12 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-06 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-06 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-16 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-06 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-30 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-18 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-06 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-06 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2018-11-06 15:47:04 | NO FEES DUE | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-29 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-29 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2018-06-29 18:27:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE, IF APPLICABLE, PROVIDED. | | | | | | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET | | | OF PLANS TO TAKE TO THE COUNTY. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-10-30 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-10-30 |
Time |
11:09 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-09-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-09-20 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-09-20 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2018-09-20 15:17:37 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18050930 | | | 9/20/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE OCCUPANCY CLASSIFICATION OF THE FACILITY HAS | | | CHANGED TO I-1 WHCIH REQUIRES THE CORRIDOR WALL TO BE | | | 1HR. FIRE-RATED PER TABLE 1020.1 FBC B. THIS MAY RESULT | | | IN FIRE DAMPERS HAVING TO BE INSTALLED IN SOME DUCT | | | PENETRATIONS THROUGH THE CORRIDOR WALLS. PLEASE REVISE | | | THE PLANS ACCORDINGLY. | | | | | | 2) SHEET M2: PLEASE MODIFY THE DRYER MAKEUP AIR DETAIL | | | TO SHOW THE DUCT RUN AND OPENING INTO THE LAUNDRY ROOM | | | ACT CEILING. INDICATE THE DUCT AND INLET GRILL SIZES. | | | | | | 3) M1 & M2: PLEASE LIST THE COOLING, HEATING AND CFM | | | SUPPLY CAPACITIES OF THE EXISTING AIR HANDLERS ON THE | | | PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-31 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-31 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-18 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-14 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2018-06-18 16:13:24 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18050930 | | | 6/19/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: THE AMOUNT OF RETURN AIR TAKEN FROM EACH | | | SLEEPING ROOM SHALL NOT BE GREATER THAN THE FLOW RATE | | | OF SUPPLY AIR DELIVERED TO THE SPACE- SECTION 601.5 (3) | | | FBC M | | | | | | 2) M2, LAUNDRY: A) SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE NEW DRYERS, THE EXHAUST DUCT WORK, AND | | | TERMINATION CAP- SECTION 504.1. B) INDICATE HOW MAKEUP | | | AIR IS BEING PROVIDED FOR THE DRYERS AND PROVIDE A | | | CALCULATION- SECTION 504.6. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2018-10-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-22 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-22 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-02 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-01 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-16 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-16 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2018-08-16 11:54:00 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: IN ORDER EXPEDITE THE APPROVAL OF | | | THIS PERMIT I SUGGEST A MEETING WITH THE PLAN REVIEWERS | | | PRIOR TO RESUBMITTING. | | | | | | 1.SHT. A-3 ON THE DETAIL FOR THE ALTERNATE ROLL IN | | | SHOWER IT SHOWS THE WIDTH OF THE SHOWER AT 36" MIN. | | | FIN. PER FBC ACC 608.2.3 THE 36" IS AN EXACT DIMENSION | | | NOT MIN. OR MAX. PLEASE CLARIFY. | | | | | | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.THE | | | SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR | | | SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM | | | MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE | | | SPRUNG TO RETURN TO A LIFTED POSITION. | | | | | | 3. PLEASE SHOW DIMENSIONS FOR THE CLEAR FLOOR SPACE FOR | | | THE TOILETS AND LAVATORY'S. PER FBC ACC 604.3.1, 606.2 | | | | | | 4. PLEASE EXPAND THE SANITARY ISOMETRIC DRAWING IT IS | | | EXTREMELY CONGESTED AND I AM UNABLE TO DO A | | | COMPREHENSIVE REVIEW TO DETERMINE CODE COMPLIANCE. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 5. IT APPEARS THAT THE SANITARY ISOMETRIC IS SHOWING | | | THE TWO SOIL STACKS FROM THE SECOND FLOOR CONNECTING | | | THROUGH THE THE BATHROOM GROUPS ON THE FIRST FLOOR THEY | | | SHALL CONNECT TO THE BUILDING DRAIN SEPARATELY FROM THE | | | BATHROOM GROUP. PER FBC PL 912.1, 704.3 | | | | | | 6.SHT. THE FLOOR PLAN DOES NOT SHOW THE SOIL STACK THAT | | | CONNECTS THE GANG SHOWER, WASHING MACHINES AND THE | | | COMMON BATHROOM ON THE SECOND FLOOR PLEASE CLARIFY . | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 7. I WAS UNABLE TO DETERMINE THE CODE COMPLIANCE OF THE | | | HOT AND COLD WATER ISOMETRIC DRAWING PLEASE EXPAND TO | | | SHOW THE FIRST AND SECOND FLOOR SEPARATELY AND NOT NEXT | | | TO EACH OTHER. . PER WPB AMEND TO FBC 107.2.1 | | | | | | 8. PROVIDE A COMPLETE 1ST AND 2ND FLOOR PLAN SHOWING | | | ALL THE HOT AND COLD WATER PIPING AND ALL THE WATER | | | HEATERS WITH RECIRCULATION SYSTEMS. . PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 9. SHT. P-2 THE 2ND FLOOR FLOOR PLAN SHOWS A 3/4 | | | PRESSURE RELIEF LINE RUNNING TO THE EXTERIOR OF THE | | | BUILDING. THE DISCHARGE PIPING SERVING A PRESSURE | | | RELIEF VALVE, TEMPERATURE RELIEF VALVE OR COMBINATION | | | THEREOF SHALL:DISCHARGE THROUGH AN AIR GAP LOCATED IN | | | THE SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-26 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-26 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2018-06-26 17:56:04 | 1ST REVIEW: FBC 2017 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION\ | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. A5 THE ROLL IN SHOWER SHALL HAVE A 60" MIN | | | OPENING AND COMPLY WITH FBC ACC 608.2.2, 608.2.2.1 | | | 2. THE TRANSFER SHOWER SHALL BE 36"X36" CLEAR INSIDE | | | DIMENSION AND COMPLY WITH FBC ACC 608.2.2 | | | 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE TO FINISHED FLOOR PLAN SNALL SHOW | | | COMPLIANCE WITH FBC ACC 609.4 | | | 4. TOILET PAPER DISPENSER SHALL BE 7" - 9" IN FRONT OF | | | THE TOILET. PER FBC ACC 604.7 | | | 5. SHOW COMPLIANCE WITHFBC ACC 610.3 | | | 6. ON THE SANITARY ISOMETRIC THE VENT FOR THE NEW | | | UNISEX BATHROOM SHALL REVENT INTO THE VENT STACK ABOVE | | | TH FLOOD LEVEL RIM OF THE FIXTURES ON THE SECOND FLOOR | | | IT CANNOT CONNECT TO THE SOIL STACK. PER FBC PL 905.5 | | | 7. THE SHOWERS IN THE SHOWER ROOM ON THE 2ND FLOOR ARE | | | NOT VENTED PER FBC PL 901.2.1 | | | 8. THE SECOND FLOOR SANITARY ISOMETRIC DOES NOT MATCH | | | THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | 9.ON THE SANITARY ISOMETRIC THE LAVATORY IN THE | | | BATHROOM FOR THE DOUBLE SLEEPING ROOM IS NOT VENTED | | | COMPLY WITH FBC PL 901.2.1 | | | 10.SHOW COMPLIANCE WITH FBC PL 504.6 REQUIREMENTS FOR | | | DISCHARGE PIPING. | | | | | | THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE, | | | TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL: | | | | | | | | | 1.NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM. | | | | | | | | | 2.DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM | | | AS THE WATER HEATER. | | | | | | | | | 3.NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF THE | | | VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE AIR | | | GAP. | | | | | | | | | 4SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT TO | | | PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT. | | | | | | | | | 5.DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER | | | HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE | | | OUTDOORS. | | | | | | | | | 6.DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL | | | INJURY OR STRUCTURAL DAMAGE. | | | | | | | | | 7.DISCHARGE TO A TERMINATION POINT THAT IS READILY | | | OBSERVABLE BY THE BUILDING OCCUPANTS. | | | | | | | | | 8.NOT BE TRAPPED. | | | | | | | | | 9.BE INSTALLED SO AS TO FLOW BY GRAVITY. | | | | | | | | | 10.TERMINATE NOT MORE THAN 6 INCHES (152 MM) ABOVE AND | | | NOT LESS THAN TWO TIMES THE DISCHARGE PIPE DIAMETER | | | ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE WASTE | | | RECEPTOR. | | | | | | | | | 11.NOT HAVE A THREADED CONNECTION AT THE END OF SUCH | | | PIPING. | | | | | | | | | 12.NOT HAVE VALVES OR TEE FITTINGS. | | | | | | 11. SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR TEMPERED | | | WATER SUPPLY TO FIXTURES.THE DEVELOPED LENGTH OF HOT OR | | | TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO | | | THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL | | | NOT EXCEED 50 FEET (15 240 MM). RECIRCULATING SYSTEM | | | PIPING AND HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE | | | SOURCES OF HOT OR TEMPERED WATER. | | | | | | 12. TEMPERED WATER REQUIRED AT LAVATORY IN UNISEX | | | BATHROOM PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC | | | HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE | | | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES | | | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR | | | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL | | | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE | | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA | | | B125.3. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-09-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-19 10:48:53 | MAXIMUM NUMBER OF BEDS PERMITTED IN THE GRADTITUDE | | | HOUSE (TREATMENT CENTER) = 41 BEDS: | | | | | | * HIBISCUS HOUSE (313 LAKESIDE CT.) = 9 BEDS | | | * LOTUS HOUSE (317 LAKESIDE CT.) = 26 BEDS | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-07-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-07-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-19 09:10:50 | ** FAILED - 5/31/18 COMMENT NOT ADDRESSED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) CITY RECORDS INDICATE THAT A MAXIMUM NUMBER OF 41 | | | BEDS IS PERMITTED FOR THE COMPLEX (25 BEDS @ 313 | | | LAKESIDE CT. AND 16 BEDS @ 317 LAKESIDE CT.). THIS | | | BUILDING PERMIT INDICATES THAT THE NUMBER OF BEDS | | | EXCEEDS THE 16 BEDS APPROVED FOR 317 LAKESIDE COURT. | | | PLEASE PROVIDE MORE INFORMATION ON WHETHER OR NOT THE | | | NUMBER OF BEDS AT 313 LAKESIDE CT. HAVE BEEN DECREASED, | | | AND IF SO, PLEASE DEMONSTRATE COMPLIANCE THAT THE | | | NUMBER OF BEDS FOR BOTH BUILDINGS WILL NOT EXCEED 41 | | | BEDS. | | | | | | NOTES: | | | | | | * GRATITUDE HOUSE | | | | | | * EXISTING TREATMENT CENTER; MAXIMUM NUMBER OF BEDS 25 | | | (313 LAKESIDE CT.) + 16 BEDS (317 LAKESIDE CT.) TOTAL | | | NUMBER OF BEDS ALLOWED = 41 BEDS | | | | | | * ZONING: GC AND POR | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2018-05-31 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-05-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-31 16:50:53 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | CITY RECORDS INDICATE THAT A MAXIMUM NUMBER OF 41 BEDS | | | IS PERMITTED FOR THE COMPLEX (25 BEDS @ 313 LAKESIDE | | | CT. AND 16 BEDS @ 317 LAKESIDE CT.). THIS BUILDING | | | PERMIT INDICATES THAT THE NUMBER OF BEDS EXCEEDS THE 16 | | | BEDS APPROVED FOR 317 LAKESIDE COURT. PLEASE PROVIDE | | | MORE INFORMATION ON WHETHER OR NOT THE NUMBER OF BEDS | | | AT 313 LAKESIDE CT. HAVE BEEN DECREASED, AND IF SO, | | | PLEASE DEMONSTRATE COMPLIANCE THAT THE NUMBER OF BEDS | | | FOR BOTH BUILDINGS WILL NOT EXCEED 41 BEDS. | | | | | | NOTES: | | | | | | * GRATITUDE HOUSE | | | | | | * EXISTING TREATMENT CENTER; MAXIMUM NUMBER OF BEDS 25 | | | (313 LAKESIDE CT.) + 16 BEDS (317 LAKESIDE CT.) TOTAL | | | NUMBER OF BEDS ALLOWED = 41 BEDS | | | | | | * ZONING: GC AND POR | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|