Plan Review Details - Permit 18050930
Plan Review Stops For Permit 18050930
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-25 Cont ID  
Sent By shill Date 2018-10-25 Time 07:39 Rev Time 0.00
Received By shill Date 2018-10-25 Time 07:39 Sent To  
Notes
2018-10-25 07:40:50PER ARCHITECT, USE WAS ALWAYS DETOX (I-1); NO CHANGE OF
 OCCUPANCY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 14:40 Rev Time 0.00
Received By shill Date 2018-10-06 Time 14:40 Sent To  
Notes
2018-10-06 14:40:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC
 109.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 14:55 Rev Time 0.00
Received By shill Date 2018-08-12 Time 14:55 Sent To  
Notes
2018-08-12 14:56:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC
 109.
  
 3. I WAS UNABLE TO FIND AN OCCUPANCY CLASSIFICATION ON
 THE PLAN, PLEASE REVISE TO INCLUDE.
  
 THIS WAS NOT A COMMENT ON FIRST REVIEW AS PLANS IMPLIED
 R4 AND SHOWED COMPLIANCE FOR R4 WHICH IS SUBJECT TO
 ACCESSIBLITY. A POOL PLAN WAS SUBMITTED WHICH APPEARS
 TO CLAIM EXCEPTIONS UNDER FAIR HOUSING.
  
 PLEASE CORRELATE AND REVISE PLANS ACCORDINGLY.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 09:27 Rev Time 0.00
Received By shill Date 2018-06-29 Time 18:53 Sent To  
Notes
2018-06-30 09:27:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN, FBC
 109.
  
 3. SEE PLUMBING ACCESSIBILITY COMMENTS; APPLICABLE FOR
 BUILDING REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-21 Cont ID  
Sent By jpearson Date 2018-09-21 Time 08:34 Rev Time 0.00
Received By jpearson Date 2018-09-21 Time 08:24 Sent To  
Notes
2018-09-21 08:35:07REVIEWED ONLY SHEET E-1, OTHER SHEET PREVIOUSLY
 APPROVED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By ppetty Date 2018-08-09 Time 13:50 Rev Time 0.00
Received By ppetty Date 2018-08-09 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By jpearson Date 2018-06-25 Time 13:42 Rev Time 0.00
Received By jpearson Date 2018-06-25 Time 12:40 Sent To  
Notes
2018-06-25 13:42:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. CURRENT LOAD CALCULATION DOES NOT
 SHOW ALL LOADS. ADDITIONALLY, THERE IS A DEMAND FACTOR
 OF 50% USED FOR LOAD OVER 10,000 VA WHICH IS A CODE
 VIOLATION. THIS DEMAND FACTOR IS ONLY TO BE USED FOR
 RECEPTACLE OUTLET LOAD, NOT FOR THE ENTIRE LOAD. ANY
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125%. PROVIDE
 LOAD FOR PANEL L-2 AND FOR ENTIRE SERVICE. NEC 215.2,
 220, TABLE 220.44, 408.30
 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-10-19 Cont ID  
Sent By pleduc Date 2018-10-19 Time   Rev Time 0.00
Received By pleduc Date 2018-10-19 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-17 Cont ID  
Sent By J.Walker Date 2018-09-17 Time   Rev Time 0.00
Received By   Date 2018-09-14 Time   Sent To  
Notes
2018-09-17 08:08:42MASTER PLAN PASSED.
 FIRE WILL REQUIRE SHOP DRAWINGS FOR:
 FIRE ALARM SYSTEM
 FIRE SPRINKLER SYSTEM
 LIFE PLAN

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By J.Walker Date 2018-07-12 Time   Rev Time 0.00
Received By   Date 2018-07-11 Time   Sent To  
Notes
2018-07-12 08:43:53MASTER PLAN PASSED
 FIRE WILL REQUIRE SHOP DRAWINGS FOR:
 FIRE ALARM SYSTEM
 FIRE SPRINKLER SYSTEM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By J.Walker Date 2018-05-23 Time   Rev Time 0.30
Received By   Date 2018-05-23 Time   Sent To  
Notes
2018-05-23 09:14:51C-17

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 15:50 Rev Time 0.00
Received By shill Date 2018-11-01 Time 13:31 Sent To  
Notes
2018-11-02 13:32:01ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-30 Cont ID  
Sent By hmoser Date 2018-10-30 Time 13:43 Rev Time 0.00
Received By hmoser Date 2018-10-12 Time 14:37 Sent To  
Notes
2018-10-15 14:38:07C15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 14:40 Rev Time 0.00
Received By shill Date 2018-09-06 Time 15:10 Sent To  
Notes
2018-09-07 15:11:05C07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-16 Cont ID  
Sent By gjohnson Date 2018-08-16 Time 11:54 Rev Time 0.00
Received By gjohnson Date 2018-07-06 Time 15:56 Sent To  
Notes
2018-07-09 15:56:25C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 09:31 Rev Time 0.00
Received By shill Date 2018-05-18 Time 14:08 Sent To  
Notes
2018-05-21 14:08:31C17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 15:46 Rev Time 0.00
Received By shill Date 2018-11-06 Time 15:46 Sent To  
Notes
2018-11-06 15:47:04NO FEES DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 18:27 Rev Time 0.00
Received By shill Date 2018-06-29 Time 18:27 Sent To  
Notes
2018-06-29 18:27:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-10-30 Cont ID  
Sent By hmoser Date 2018-10-30 Time 13:43 Rev Time 0.00
Received By hmoser Date 2018-10-30 Time 11:09 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 15:01 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 15:01 Sent To  
Notes
2018-09-20 15:17:373RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18050930
 9/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OCCUPANCY CLASSIFICATION OF THE FACILITY HAS
 CHANGED TO I-1 WHCIH REQUIRES THE CORRIDOR WALL TO BE
 1HR. FIRE-RATED PER TABLE 1020.1 FBC B. THIS MAY RESULT
 IN FIRE DAMPERS HAVING TO BE INSTALLED IN SOME DUCT
 PENETRATIONS THROUGH THE CORRIDOR WALLS. PLEASE REVISE
 THE PLANS ACCORDINGLY.
  
 2) SHEET M2: PLEASE MODIFY THE DRYER MAKEUP AIR DETAIL
 TO SHOW THE DUCT RUN AND OPENING INTO THE LAUNDRY ROOM
 ACT CEILING. INDICATE THE DUCT AND INLET GRILL SIZES.
  
 3) M1 & M2: PLEASE LIST THE COOLING, HEATING AND CFM
 SUPPLY CAPACITIES OF THE EXISTING AIR HANDLERS ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By ccole Date 2018-07-31 Time 10:15 Rev Time 0.00
Received By ccole Date 2018-07-31 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By ccole Date 2018-06-18 Time 15:56 Rev Time 0.00
Received By ccole Date 2018-06-14 Time 17:39 Sent To  
Notes
2018-06-18 16:13:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050930
 6/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE AMOUNT OF RETURN AIR TAKEN FROM EACH
 SLEEPING ROOM SHALL NOT BE GREATER THAN THE FLOW RATE
 OF SUPPLY AIR DELIVERED TO THE SPACE- SECTION 601.5 (3)
 FBC M
  
 2) M2, LAUNDRY: A) SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE NEW DRYERS, THE EXHAUST DUCT WORK, AND
 TERMINATION CAP- SECTION 504.1. B) INDICATE HOW MAKEUP
 AIR IS BEING PROVIDED FOR THE DRYERS AND PROVIDE A
 CALCULATION- SECTION 504.6.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-10-22 Cont ID  
Sent By gjohnson Date 2018-10-22 Time 08:05 Rev Time 0.00
Received By gjohnson Date 2018-10-22 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-02 Cont ID  
Sent By gjohnson Date 2018-10-02 Time 08:53 Rev Time 0.00
Received By gjohnson Date 2018-10-01 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-16 Cont ID  
Sent By gjohnson Date 2018-08-16 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2018-08-16 Time 08:27 Sent To  
Notes
2018-08-16 11:54:002ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: IN ORDER EXPEDITE THE APPROVAL OF
 THIS PERMIT I SUGGEST A MEETING WITH THE PLAN REVIEWERS
 PRIOR TO RESUBMITTING.
  
 1.SHT. A-3 ON THE DETAIL FOR THE ALTERNATE ROLL IN
 SHOWER IT SHOWS THE WIDTH OF THE SHOWER AT 36" MIN.
 FIN. PER FBC ACC 608.2.3 THE 36" IS AN EXACT DIMENSION
 NOT MIN. OR MAX. PLEASE CLARIFY.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.THE
 SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR
 SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION.
  
 3. PLEASE SHOW DIMENSIONS FOR THE CLEAR FLOOR SPACE FOR
 THE TOILETS AND LAVATORY'S. PER FBC ACC 604.3.1, 606.2
  
 4. PLEASE EXPAND THE SANITARY ISOMETRIC DRAWING IT IS
 EXTREMELY CONGESTED AND I AM UNABLE TO DO A
 COMPREHENSIVE REVIEW TO DETERMINE CODE COMPLIANCE. PER
 WPB AMEND TO FBC 107.2.1
  
 5. IT APPEARS THAT THE SANITARY ISOMETRIC IS SHOWING
 THE TWO SOIL STACKS FROM THE SECOND FLOOR CONNECTING
 THROUGH THE THE BATHROOM GROUPS ON THE FIRST FLOOR THEY
 SHALL CONNECT TO THE BUILDING DRAIN SEPARATELY FROM THE
 BATHROOM GROUP. PER FBC PL 912.1, 704.3
  
 6.SHT. THE FLOOR PLAN DOES NOT SHOW THE SOIL STACK THAT
 CONNECTS THE GANG SHOWER, WASHING MACHINES AND THE
 COMMON BATHROOM ON THE SECOND FLOOR PLEASE CLARIFY .
 PER WPB AMEND TO FBC 107.2.1
  
 7. I WAS UNABLE TO DETERMINE THE CODE COMPLIANCE OF THE
 HOT AND COLD WATER ISOMETRIC DRAWING PLEASE EXPAND TO
 SHOW THE FIRST AND SECOND FLOOR SEPARATELY AND NOT NEXT
 TO EACH OTHER. . PER WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE A COMPLETE 1ST AND 2ND FLOOR PLAN SHOWING
 ALL THE HOT AND COLD WATER PIPING AND ALL THE WATER
 HEATERS WITH RECIRCULATION SYSTEMS. . PER WPB AMEND TO
 FBC 107.2.1
  
 9. SHT. P-2 THE 2ND FLOOR FLOOR PLAN SHOWS A 3/4
 PRESSURE RELIEF LINE RUNNING TO THE EXTERIOR OF THE
 BUILDING. THE DISCHARGE PIPING SERVING A PRESSURE
 RELIEF VALVE, TEMPERATURE RELIEF VALVE OR COMBINATION
 THEREOF SHALL:DISCHARGE THROUGH AN AIR GAP LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By gjohnson Date 2018-06-26 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2018-06-26 Time 08:50 Sent To  
Notes
2018-06-26 17:56:041ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION\
  
 PLUMBING COMMENTS:
  
 1. SHT. A5 THE ROLL IN SHOWER SHALL HAVE A 60" MIN
 OPENING AND COMPLY WITH FBC ACC 608.2.2, 608.2.2.1
 2. THE TRANSFER SHOWER SHALL BE 36"X36" CLEAR INSIDE
 DIMENSION AND COMPLY WITH FBC ACC 608.2.2
 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR PLAN SNALL SHOW
 COMPLIANCE WITH FBC ACC 609.4
 4. TOILET PAPER DISPENSER SHALL BE 7" - 9" IN FRONT OF
 THE TOILET. PER FBC ACC 604.7
 5. SHOW COMPLIANCE WITHFBC ACC 610.3
 6. ON THE SANITARY ISOMETRIC THE VENT FOR THE NEW
 UNISEX BATHROOM SHALL REVENT INTO THE VENT STACK ABOVE
 TH FLOOD LEVEL RIM OF THE FIXTURES ON THE SECOND FLOOR
 IT CANNOT CONNECT TO THE SOIL STACK. PER FBC PL 905.5
 7. THE SHOWERS IN THE SHOWER ROOM ON THE 2ND FLOOR ARE
 NOT VENTED PER FBC PL 901.2.1
 8. THE SECOND FLOOR SANITARY ISOMETRIC DOES NOT MATCH
 THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 9.ON THE SANITARY ISOMETRIC THE LAVATORY IN THE
 BATHROOM FOR THE DOUBLE SLEEPING ROOM IS NOT VENTED
 COMPLY WITH FBC PL 901.2.1
 10.SHOW COMPLIANCE WITH FBC PL 504.6 REQUIREMENTS FOR
 DISCHARGE PIPING.
  
 THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL:
  
  
 1.NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM.
  
  
 2.DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM
 AS THE WATER HEATER.
  
  
 3.NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF THE
 VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE AIR
 GAP.
  
  
 4SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT TO
 PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT.
  
  
 5.DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUTDOORS.
  
  
 6.DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY OR STRUCTURAL DAMAGE.
  
  
 7.DISCHARGE TO A TERMINATION POINT THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS.
  
  
 8.NOT BE TRAPPED.
  
  
 9.BE INSTALLED SO AS TO FLOW BY GRAVITY.
  
  
 10.TERMINATE NOT MORE THAN 6 INCHES (152 MM) ABOVE AND
 NOT LESS THAN TWO TIMES THE DISCHARGE PIPE DIAMETER
 ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR.
  
  
 11.NOT HAVE A THREADED CONNECTION AT THE END OF SUCH
 PIPING.
  
  
 12.NOT HAVE VALVES OR TEE FITTINGS.
  
 11. SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR TEMPERED
 WATER SUPPLY TO FIXTURES.THE DEVELOPED LENGTH OF HOT OR
 TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL
 NOT EXCEED 50 FEET (15 240 MM). RECIRCULATING SYSTEM
 PIPING AND HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE
 SOURCES OF HOT OR TEMPERED WATER.
  
 12. TEMPERED WATER REQUIRED AT LAVATORY IN UNISEX
 BATHROOM PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-19 Cont ID  
Sent By llouie Date 2018-09-19 Time   Rev Time 0.00
Received By llouie Date 2018-09-18 Time   Sent To  
Notes
2018-09-19 10:48:53MAXIMUM NUMBER OF BEDS PERMITTED IN THE GRADTITUDE
 HOUSE (TREATMENT CENTER) = 41 BEDS:
  
 * HIBISCUS HOUSE (313 LAKESIDE CT.) = 9 BEDS
 * LOTUS HOUSE (317 LAKESIDE CT.) = 26 BEDS
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-19 Cont ID  
Sent By llouie Date 2018-07-19 Time   Rev Time 0.00
Received By llouie Date 2018-07-19 Time   Sent To  
Notes
2018-07-19 09:10:50** FAILED - 5/31/18 COMMENT NOT ADDRESSED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CITY RECORDS INDICATE THAT A MAXIMUM NUMBER OF 41
 BEDS IS PERMITTED FOR THE COMPLEX (25 BEDS @ 313
 LAKESIDE CT. AND 16 BEDS @ 317 LAKESIDE CT.). THIS
 BUILDING PERMIT INDICATES THAT THE NUMBER OF BEDS
 EXCEEDS THE 16 BEDS APPROVED FOR 317 LAKESIDE COURT.
 PLEASE PROVIDE MORE INFORMATION ON WHETHER OR NOT THE
 NUMBER OF BEDS AT 313 LAKESIDE CT. HAVE BEEN DECREASED,
 AND IF SO, PLEASE DEMONSTRATE COMPLIANCE THAT THE
 NUMBER OF BEDS FOR BOTH BUILDINGS WILL NOT EXCEED 41
 BEDS.
  
 NOTES:
  
 * GRATITUDE HOUSE
  
 * EXISTING TREATMENT CENTER; MAXIMUM NUMBER OF BEDS 25
 (313 LAKESIDE CT.) + 16 BEDS (317 LAKESIDE CT.) TOTAL
 NUMBER OF BEDS ALLOWED = 41 BEDS
  
 * ZONING: GC AND POR
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By LL Date 2018-05-31 Time   Rev Time  
Received By llouie Date 2018-05-31 Time   Sent To  
Notes
2018-05-31 16:50:53** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 CITY RECORDS INDICATE THAT A MAXIMUM NUMBER OF 41 BEDS
 IS PERMITTED FOR THE COMPLEX (25 BEDS @ 313 LAKESIDE
 CT. AND 16 BEDS @ 317 LAKESIDE CT.). THIS BUILDING
 PERMIT INDICATES THAT THE NUMBER OF BEDS EXCEEDS THE 16
 BEDS APPROVED FOR 317 LAKESIDE COURT. PLEASE PROVIDE
 MORE INFORMATION ON WHETHER OR NOT THE NUMBER OF BEDS
 AT 313 LAKESIDE CT. HAVE BEEN DECREASED, AND IF SO,
 PLEASE DEMONSTRATE COMPLIANCE THAT THE NUMBER OF BEDS
 FOR BOTH BUILDINGS WILL NOT EXCEED 41 BEDS.
  
 NOTES:
  
 * GRATITUDE HOUSE
  
 * EXISTING TREATMENT CENTER; MAXIMUM NUMBER OF BEDS 25
 (313 LAKESIDE CT.) + 16 BEDS (317 LAKESIDE CT.) TOTAL
 NUMBER OF BEDS ALLOWED = 41 BEDS
  
 * ZONING: GC AND POR
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.