Plan Review Details - Permit 18050924
Plan Review Stops For Permit 18050924
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-14 Cont ID  
Sent By pleduc Date 2018-06-14 Time   Rev Time 0.00
Received By pleduc Date 2018-06-13 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By pleduc Date 2018-05-22 Time   Rev Time 0.00
Received By pleduc Date 2018-05-21 Time 15:56 Sent To M
Notes
2018-05-22 09:11:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT APPEARS, THROUGH THE INDICATED DESIGN CIRLCES,
 THAT THE FAN # 3 IS WITHIN THE 10' MINIMUM CLEARENCE
 REQUIREMENT OF NFPA 96 OF AHU INTAKE 1-1.
  
 PER NFPA 96
  
 7.8.2 ROOFTOP TERMINATIONS.
 7.8.2.1 ROOFTOP TERMINATIONS SHALL BE ARRANGED WITH OR
 PROVIDED
 WITH THE FOLLOWING:
 (1) A MINIMUM OF 3 M (10 FT) OF HORIZONTAL CLEARANCE
 FROM
 THE OUTLET TO ADJACENT BUILDINGS, PROPERTY LINES, AND
 AIR
 INTAKES
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCE OR ACTUAL SCALED DIMENSIONS.
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-09 Cont ID  
Sent By hmoser Date 2018-07-09 Time 15:23 Rev Time 0.00
Received By hmoser Date 2018-06-12 Time 13:57 Sent To  
Notes
2018-06-13 13:58:04RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By hmoser Date 2018-05-23 Time 10:45 Rev Time 0.00
Received By hmoser Date 2018-05-18 Time 13:13 Sent To  
Notes
2018-05-21 13:13:30ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-09 Cont ID  
Sent By hmoser Date 2018-07-09 Time 15:23 Rev Time 0.00
Received By hmoser Date 2018-07-09 Time 14:34 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By pleduc Date 2018-05-23 Time 10:45 Rev Time 0.00
Received By hmoser Date 2018-05-23 Time 09:11 Sent To I
Notes
2018-05-23 10:44:56PLAN DENIED
 1) SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR
 FIRE SUPPRESSION . SECTION 107.2.1 CITY OF WEST PALM
 BEACH AMENDMENTS.
 2) REFER TO SECTION 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES. 2017 FBC (M)
 3) REFER TO SECTION 306.5.1 SLOPED ROOFS 2017
 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676