Plan Review Details - Permit 18050905
Plan Review Stops For Permit 18050905
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-16 Cont ID  
Sent By rmcdouga Date 2018-07-16 Time 13:19 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 12:42 Sent To E
Notes
2018-07-16 12:51:05FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2018-07-02 Time 16:55 Sent To I
Notes
2018-07-02 17:13:56FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By rmcdouga Date 2018-05-25 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2018-05-25 Time 10:29 Sent To P
Notes
2018-05-25 10:33:19FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-19 Cont ID  
Sent By fgiaquin Date 2018-07-19 Time 05:40 Rev Time 0.00
Received By fgiaquin Date 2018-07-19 Time 05:33 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By fgiaquin Date 2018-06-30 Time 08:05 Rev Time 0.00
Received By fgiaquin Date 2018-06-30 Time 07:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 10:08 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 10:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 14:52 Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 14:51 Sent To  
Notes
2018-05-30 14:52:02THERE IS NO GAS ASSOCIATED WITH THIS POOL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-19 Cont ID  
Sent By fgiaquin Date 2018-07-19 Time 05:40 Rev Time 0.00
Received By fgiaquin Date 2018-07-05 Time 14:43 Sent To  
Notes
2018-07-06 14:43:42RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-02 Cont ID  
Sent By rmcdouga Date 2018-07-02 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2018-06-22 Time 13:05 Sent To  
Notes
2018-06-25 13:05:22RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 14:52 Rev Time 0.00
Received By tklarge Date 2018-05-18 Time 13:09 Sent To  
Notes
2018-05-21 13:09:10ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-16 Cont ID  
Sent By tklarge Date 2018-07-16 Time 08:45 Rev Time 0.00
Received By tklarge Date 2018-07-16 Time 07:25 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-30 Cont ID  
Sent By tklarge Date 2018-06-30 Time 04:15 Rev Time 0.00
Received By tklarge Date 2018-06-30 Time 03:40 Sent To  
Notes
2018-06-30 04:15:101) THE TDH CALCULATIONS MUST INCCLUDE ALL THE SYSTEM
 COMPONENTS IN THE PIPING SYSTEM INCLUDING THE FILTER.
 THIS HAS NOT BEEN DONE.SUBMIT NEW TDH CALCULATIONS.
 2) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS.
 3) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING
 INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) COMPILE ALL THE DOCUMENTS AND PLANS INTO TWO
 COMPLETE SETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 14:50 Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 13:46 Sent To I
Notes
2018-05-30 14:49:581) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE UNBLOCKABLE CHANNEL DRAIN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR
 THE POOL PUMP. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-11 Cont ID  
Sent By mcruz Date 2018-07-11 Time 14:44 Rev Time 0.00
Received By mcruz Date 2018-07-11 Time 14:43 Sent To P
Notes
2018-07-11 14:45:49FLOW RATE CORRECTION, SETBACK DIMENSIONS NOT AFFECTED.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By mcruz Date 2018-06-27 Time 14:08 Rev Time 0.00
Received By mcruz Date 2018-06-27 Time 14:02 Sent To P
Notes
2018-06-27 14:05:06NOTE - POOL EQUIPMENT SHALL BE 1' FROM SIDE PROPERTY
 LINE AND AT LEAST 6' FROM REAR.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By mcruz Date 2018-05-23 Time   Rev Time  
Received By mcruz Date 2018-05-23 Time   Sent To PC
Notes
2018-05-23 11:33:13NOTE - POOL EQUIPMENT SHALL BE 1' FROM SIDE PROPERTY
 LINE AND AT LEAST 6' FROM REAR.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  