Plan Review Details - Permit 18050880
Plan Review Stops For Permit 18050880
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-07 Cont ID  
Sent By spalmer Date 2018-08-07 Time 14:22 Rev Time 0.00
Received By spalmer Date 2018-08-07 Time 14:22 Sent To  
Notes
2018-08-07 14:23:01PASSED ON MASTER#18050951

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 10:25 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 09:44 Sent To  
Notes
2018-06-03 10:25:461) THE SUBMITTED GAS DRAWING REFERS TO A 22KW GENERATOR
 AT 398,000 BTU'S BUT THE GENERATOR SPECS ARE FOR A 20
 KW GENERATOR WITH A RATING OF 281,000 BTU'S AT 100 %
 LOAD. CLARIFY.
 2) THE EXHAUST FROM THE GENERATOR SHALL BE LOCATED A
 MINIMUM OF 10 FEET FROM ANY BUILDING OPENING INCLUDING
 ATTIC/SOFFIT VENTS.
 3) SHOW THE SIZE AND TYPE OF PIPE AT THE OUTLET OF THE
 GAS METER.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHOW THE SIZE AND TYPE OF PIPE FROM THE OUTLET OF
 THE REGULATOR TO THE INTERIOR. WPB AMEND. TO FBC SEC.
 107.2.1.
 5) IDENTIFY ON THE REGULATOR SPECS WHICH SPECIFIC MODEL
 IS BEING INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1.
 6) A CLOTHES DRYER IS SHOWN ON THE EXISTING GAS PLAN IN
 CITY RECORDS BUT IS NOT SHOWN ON THIS PLAN. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 10:26 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 09:44 Sent To  
Notes
***NONE***