Plan Review Details - Permit 18050874
Plan Review Stops For Permit 18050874
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 15:12 Rev Time 0.00
Received By shill Date 2018-07-30 Time 15:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 10:27 Rev Time 0.00
Received By shill Date 2018-06-15 Time 10:27 Sent To  
Notes
2018-06-15 10:31:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SCOPE NOT CLEAR. WHAT TYPE OF FLOORING IS PROPOSED
 AND WHERE; TILE OR WOOD?
  
 2. COMPLIANCE WITH THE FOLLOWING REQUIREMENTS IS NOT
 CLEAR. PLAN SPECIFIES "PROFLEX".
  
 PROVIDE TEST REPORTS FOR THE UNDERLAYMENT:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 WE MAY HAVE PROFLEX RCU250 AND PROFLEX SUPERSIM90 ON
 FILE (OR MAY BE ABLE TO OBTAIN THE TESTS FOR YOU); THEY
 WILL BE PROVIDED TO YOU UPON REQUEST VIA EMAIL. PRINT
 TWO SETS AND PROVIDE WITH RESUBMITTED PLAN. SINCE IT IS
 NOT CLEAR WHICH TYPE OF FLOORING IS PROPOSED (TILE OR
 WOOD), ADDITIONAL INFORMATION IS REQUIRED PRIOR TO
 RESUBMITTAL.
  
 3. ADDRESS IS NOT CORRECT ON THE PLAN (3800 FLAGLER
 DR). IF PAGES ARE REVISED, CORRECT THE ADDRESS.
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-24 Cont ID  
Sent By ppetty Date 2018-07-24 Time 11:20 Rev Time 0.00
Received By ppetty Date 2018-07-24 Time 11:43 Sent To  
Notes
2018-07-24 11:19:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By jpearson Date 2018-06-12 Time 13:04 Rev Time 0.00
Received By jpearson Date 2018-06-12 Time 09:21 Sent To  
Notes
2018-06-12 13:04:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS
 PER NEC 210.12(B), 406.4(D).
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 4. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 5. PLAN SHOWS A CARBON MONOXIDE/SMOKE ALARM IN DINING
 AREA. CARBON MONOXIDE ALARMS SHOULD BE WITHIN 10 FEET
 OF SLEEPING AREA IF USED. FBC RE R315.1
 6. LIGHTING SHOWN IN CLOSET APPEARS TO BE A STANDARD
 RECESS LIGHT. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-06 Cont ID  
Sent By pleduc Date 2018-07-06 Time   Rev Time 0.00
Received By pleduc Date 2018-07-05 Time 12:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By pleduc Date 2018-05-23 Time   Rev Time 0.00
Received By pleduc Date 2018-05-22 Time 17:01 Sent To  
Notes
2018-05-23 10:21:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE TITLE BLOCK INDICATES AND ADDRESS OF 3800 SOUTH
 FLAGLER DR, THE APPLICATION ADDRESS INDICATES 3800
 WASHINGTON RD.
  
 THE WASHINGTON RD ADDRESS WAS CONFIRMED ON THE PBC
 APPRAISER'S OFFICE WEBSITE.
  
 PLEASE REVIEW AND CORRECT WITH REVISION OR RESUBMITTAL
 AS, OR IF, DIRECTED BY BUILIND DEPARTMENT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 17:55 Rev Time 0.00
Received By gjohnson Date 2018-07-02 Time 13:42 Sent To  
Notes
2018-07-30 15:36:17TO GJ DESK
  
2018-07-03 13:43:00B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 10:31 Rev Time 0.00
Received By shill Date 2018-05-18 Time 13:49 Sent To  
Notes
2018-05-21 13:50:04B11

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 17:55 Rev Time 0.00
Received By gjohnson Date 2018-07-30 Time 17:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 13:07 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 11:15 Sent To  
Notes
***NONE***