Plan Review Details - Permit 18050859
Plan Review Stops For Permit 18050859
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 14:04 Rev Time 0.00
Received By shill Date 2018-08-28 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 07:30 Rev Time 0.00
Received By shill Date 2018-08-09 Time 07:30 Sent To  
Notes
2018-08-09 07:31:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. VALUE IS TOO LOW, FBC 109. PROVIDE A COPY OF THE
 CONTRACT AND A COST BREAKDOWN. VALUE IS TO INCLUDE
 LABOR, MATERIALS, OVERHEAD, PROFIT, DESIGN FEES.
  
 3. OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:29 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:29 Sent To  
Notes
2018-06-16 15:30:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. VALUE IS TOO LOW, FBC 109. PROVIDE A COPY OF THE
 CONTRACT AND A COST BREAKDOWN. VALUE IS TO INCLUDE
 LABOR, MATERIALS, OVERHEAD, PROFIT, DESIGN FEES.
  
 3. SHEET A0 STATES THIS IS A LEVEL I ALTERATION. AS
 THERE IS RECONFIGURATION OF SPACE, THIS IS A LEVEL 2
 ALTERATION; REVISE, FBC EB 504.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-28 Cont ID  
Sent By jpearson Date 2018-08-28 Time 14:40 Rev Time 0.00
Received By jpearson Date 2018-08-28 Time 14:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By jpearson Date 2018-07-27 Time 10:17 Rev Time 0.00
Received By jpearson Date 2018-07-27 Time 08:07 Sent To  
Notes
2018-07-27 10:17:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (TEXT IN RISER DIAGRAM IS
 ILLEGIBLE. PROVIDE CORRECTED RISER DIAGRAM WHERE ALL
 INFORMATION IS LEGIBLE.)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (PANEL
 SCHEDULES FOR EACH PANEL NOT PROVIDED, MUST HAVE EACH
 PANEL SCHEDULE. CIRCUITS ARE NOT IDENTIFIED AS NEW OR
 EXISTING, PROVIDE CORRECTION.)
 4. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 (THIS SHOULD BE FOR THE TOTAL OF THE JOB, NOT JUST
 MECHANICAL AND ELECTRICAL. PROVIDE AS PREVIOUSLY
 REQUESTED.)
  
 NEW COMMENTS:
  
 5. LOAD CALCULATION PROVIDED FOR EACH PANEL SCHEDULE IS
 THE TYPE OF CALCULATION USED FOR RESIDENTIAL
 INSTALLATIONS. PROVIDE LOAD CALCULATION FOR SERVICE AND
 EACH PANEL, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 6. NOTE BELOW RISER DIAGRAM STATES THIS DESIGN IS BASED
 ON 2008 ENERGY CONSERVATION, WHICH IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (SEE ABOVE)
 7. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 8. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 9. PLAN SHOWS AN AIC CALCULATION THAT IS NOT COMPLETE.
 AIC CALCULATION IS NOT REQUIRED UNLESS THERE IS SERVICE
 EQUIPMENT BEING ADDED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1; NEC 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 13:04 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 10:40 Sent To  
Notes
2018-06-07 13:04:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SCOPE OF WORK IS NOT CLEAR ON PLAN. PROVIDE DETAILS
 OF WORK TO BE COMPLETED. WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By pleduc Date 2018-07-10 Time   Rev Time 0.00
Received By pleduc Date 2018-07-09 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-24 Cont ID  
Sent By pleduc Date 2018-05-24 Time   Rev Time 0.00
Received By pleduc Date 2018-05-21 Time 12:30 Sent To  
Notes
2018-05-23 13:07:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE VARIOUS INCORRECT REFERENCED EDITIONS
 INDICATED FOR THE VARIOUS FIRE CODES RELATED TO THIS
 PROJECT.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
  
 THOUGH THESE MAY NOT REPRESENT SIGNIFICANT IMPACT,
 PLEASE ENSURE COMPLIANCE AS THESE CODES WILL BE USED TO
 COMPLETE THE FIRE INSPECTIONS.
  
  
  
 2) SHOULD THIS PERMIT BE REJECTED BY ANOTHER CITY
 DEPARTMENT PERMIT REVIEW, PLEASE CORRECT THESE REFENCES
 WITH REVISION CLOUDS AND RESUBMIT.
  
  
 3) PLEASE UPADTE YOUR RECORDS FOR FUTURE SUBMITTALS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2018-08-24 Cont ID  
Sent By gjohnson Date 2018-08-24 Time 10:59 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 10:59 Sent To  
Notes
2018-08-24 11:00:57GAS UNDER PERMIT 18080050 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-08-07 Cont ID  
Sent By gjohnson Date 2018-08-07 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2018-08-07 Time 11:56 Sent To  
Notes
2018-08-07 12:45:382ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER DIAGRAM
 IT IS CONFUSING BECAUSE OF THE NUMBER OF REGULATORS
 YOUR SHOWING, A SET OF REGULATORS ON THE TANKS ONE
 BEFORE THE FIRST TEE, TWO AFTER THE TEE AND ONE AT EACH
 APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 YOUR SHOWING THREE DIFFERENT REGULATOR WHICH WOULD
 THREE SYSTEM PRESSURES PLEASE SHOW THEM ON THE RISER
 AND IF THE PRESSURE IS UNDER 2PSI INDICATE IN INCHES OF
 WATER COLUMN.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR LP TANKS. PER
 WPB AMEND TO FBC 107.2.1 IF YOU GOING TO SUBMIT THE
 INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND
 SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS
 OF TANKS FROM THIS SET OF PLANS
  
 4.SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS REGULATORS TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5. CLEARLY SHOW THE CAPACITY OF LP TANK(S), TYPE OF
 TANK (DOT OR ASME), THE DISTANCE OF THE TANK FROM THE
 EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2. IF YOU GOING TO SUBMIT THE
 INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND
 SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS
 OF TANKS FROM THIS SET OF PLANS
  
  
 6. CLEARLY INDICATE ON THE PLAN THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. AND THE TANK SHALL BE SECURELY ANCHORED TO
 WITHSTAND 170 MPH ULT WIND LOAD PER THE FLORIDA
 BUILDING CODE. IF YOU GOING TO SUBMIT THE INFORMATION
 SPECIFICATION AND TANK DRAWING SETBACKS AND SITE
 DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS OF
 TANKS FROM THIS SET OF PLANS
  
 7. FOR THE SIZING TABLE THE INFORMATION YOU PROVIDED IS
 CONFUSING PLEASE CLARIFY, A) UNDER THE NOTES ON SHT P2
 YOU LIST TABLE 402.2 THERE IS NO TABLE UNDER THAT
 SECTION, B) IF YOU GOING TO USE THE EQUATION METHOD 4-1
 SHOW THE EQUATIONS FOR EACH SIZE ON THE PLAN. C)
 SECTIONS 402.4.1, 402.4.2, 402.4.2 ARE DIFFERENT SIZING
 METHODS PLEASE CLARIFY WHICH ONE YOU ARE USING. IT
 WOULD MAKE IT MUCH SIMPLER IF YOU JUST SPECIFIED THE
 TABLE 402.4(25)(26)(27)(28)
  
 NEW COMMENT:
  
 1. THE CONVECTION OVEN IS NOT SHOWN ON THE RISER
 DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 17:45 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 17:45 Sent To  
Notes
2018-06-07 17:51:211ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER DIAGRAM
 IT IS CONFUSING BECAUSE OF THE NUMBER OF REGULATORS
 YOUR SHOWING, A SET OF REGULATORS ON THE TANKS ONE
 BEFORE THE FIRST TEE, TWO AFTER THE TEE AND ONE AT EACH
 APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR LP TANKS. PER
 WPB AMEND TO FBC 107.2.1
  
 3. THE PLAN IS SHOWING 2 LP TANKS BUT THE NOTE ON THE
 RISER IS LISTING 3 PLEASE CLARIFY. . PER WPB AMEND TO
 FBC 107.2.1
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5. CLEARLY SHOW THE CAPACITY OF LP TANK(S), TYPE OF
 TANK (DOT OR ASME), THE DISTANCE OF THE TANK FROM THE
 EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 6. CLEARLY INDICATE ON THE PLAN THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. AND THE TANK SHALL BE SECURELY ANCHORED TO
 WITHSTAND 170 MPH ULT WIND LOAD PER THE FLORIDA
 BUILDING CODE.
  
 7. I CANNOT VERIFY PIPE SIZINGOF THE SYSTEM PLEASE
 CLARIFY THE FOLLOWING
 A) SYSTEM PRESSURE
 B) THE TABLE LISTED 402.4(2)(3)(20) ARE FOR NATURAL
 GAS, IF SYSTEM IS LP GAS PROVIDE THOSE SIZING TABLES.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-28 Cont ID  
Sent By jpearson Date 2018-08-28 Time 14:40 Rev Time 0.00
Received By jpearson Date 2018-08-28 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 07:31 Rev Time 0.00
Received By shill Date 2018-07-05 Time 15:04 Sent To  
Notes
2018-07-06 15:04:56B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By cpuell Date 2018-06-25 Time 16:05 Rev Time 0.00
Received By cpuell Date 2018-05-17 Time 16:06 Sent To  
Notes
2018-05-18 16:07:03B17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 13:08 Rev Time 0.00
Received By ccole Date 2018-08-24 Time 13:08 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-16 Cont ID  
Sent By ccole Date 2018-07-16 Time 13:26 Rev Time 0.00
Received By ccole Date 2018-07-16 Time 13:24 Sent To  
Notes
2018-07-16 13:32:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050859
 7/16/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #6 FROM THE 1ST REVIEW STILL EXIST. THE
 COMBUSTION AIR CALCULATIONS ARE NOT IN COMPLIANCE WITH
 SECTION 304 FBC FG. SEE PREVIOUS COMMENT BELOW.
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES IN ACCORDANCE WITH SECTION
 304 FBC FG, AND INDICATE HOW THE COMBUSTION AIR WILL BE
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-01 Cont ID  
Sent By ccole Date 2018-06-01 Time 07:46 Rev Time 0.00
Received By ccole Date 2018-05-31 Time 17:52 Sent To  
Notes
2018-06-01 07:48:011ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By gjohnson Date 2018-08-24 Time 11:01 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-07 Cont ID  
Sent By gjohnson Date 2018-08-07 Time 14:47 Rev Time 0.00
Received By gjohnson Date 2018-08-07 Time 14:47 Sent To  
Notes
2018-08-07 14:55:342ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. IF ALL FLOOR DRAIN ARE EXISTING WHAT IS THE TRAP
 PRIMER DETAIL ON SHT P3 FOR ARE YOU ADDING OR REPLACING
 TRAP PRIMERS TO EXITING FLOOR DRAIN PLEASE CLARIFY. PER
 WPB AMEND TO FBC PL 407.2.1
  
 2. SHT. P3.0 ON THE TYPICAL DRAIN PIPING DETAIL IT
 SHOWS A CHROME PTRAP AND PIPING AND A TAP TEE WHICH IS
 CAST IRON IS THIS ACCURATE AS TO THE WAY THE HAND SINK
 WILL BE PIPED. PER WPB AMEND TO FBC PL 407.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 17:45 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 16:04 Sent To  
Notes
2018-06-07 17:45:031ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC
 DRAWING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. ARE ALL THE FLOOR DRAINS EXISTING THERE ARE SOME
 SHOWN ON SHT P-1.0 THAT DON'T INDICATE NEW OR EXISTING.
 PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 3. THE ONLY PLUMBING WORK APPEARS TO BE A NEW HAND SINK
 IS THIS CORRECT PLEASE CLARIFY ON THE PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-25 Cont ID  
Sent By AV Date 2018-06-25 Time 15:37 Rev Time 0.00
Received By ajones Date 2018-06-25 Time 15:37 Sent To I
Notes
***NONE***