| 2018-06-11 16:42:43 | 06/11/2018 2ND GAS REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) THE GAS METER AC-250 HAS A MAX OUTPUT OF 560 BTU'S @ |
| | 12" W.C AND 610 BTU'S @ 2PSI AND WOULD BE UNDERSIZED. |
| | 1" SCH 40 PIPING BASED OFF FBC FUEL AND GAS 402.4 (1) |
| | LIST A MAX BTU FLOW OF 514 BTU'S. YOU ENTIRE SYSTEM IS |
| | UNDERSIZED .WHAT IS YOUR INTENT ON UPGRADING IF |
| | NECESSARY AS PER YOUR COMMENT ON THE PLAN? FBC 107.2.1 |
| | |
| | 2) YOU REFERENCE NFPA 15 ON YOUR PLAN. NFPA 15 DOES NOT |
| | APPLY TO ANYTHING ON THIS PERMIT APPLICATION. PLEASE |
| | CORRECT. FBC 107.2.1 |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | 4) THE DORMONT FLEX CONNECT IS NOT PART OF THE U.L |
| | LISTING OF THIS GENERATOR. CALL'S TO GENERAC ABOUT THIS |
| | ISSUE HAVE GONE UNANSWERED IN THE PAST WITH CALLS TO |
| | DORMONT SAYING THAT THIS FLEX CONNECTOR IS ONLY |
| | APPROVED AS LABEL. THIS SAME CONNECTED IS SUPPLIED FOR |
| | ALL THERE GENERATORS UP TO 42KW. THE CHART PROVIDED BY |
| | DORMONT WILL BE WHAT THE INSPECTOR GOES BY ON THE |
| | INSPECTION. |
| | |
| | 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |