Plan Review Details - Permit 18050846
Plan Review Stops For Permit 18050846
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By jwitmer Date 2018-06-16 Time 16:06 Rev Time 0.00
Received By shill Date 2018-06-16 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By jleahy Date 2018-06-08 Time 16:17 Rev Time 0.00
Received By jleahy Date 2018-06-08 Time 16:17 Sent To  
Notes
2018-06-08 16:19:43FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E-2-1-01
  
 ON PANEL SCHEDULES IT SHOWS 12K FOR AIC RATING? NEVER
 SEEN ONE AT 12K

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-09-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-27 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 16:07 Rev Time 0.00
Received By shill Date 2018-05-21 Time 16:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 10:08 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By ccole Date 2018-06-08 Time 11:05 Rev Time 0.00
Received By ccole Date 2018-06-08 Time 11:05 Sent To  
Notes
2018-06-08 11:17:071ST REVIEW FBC-2014 MECHANICAL
 REVISION #18050846
 MASTER #16120880
 6/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.3.01: THE RETURN TRANSFER DUCTS FROM
 OFFICES 103A & 103B ARE UNDERSIZED PER SECTION 601.5
 (1). THE TRANSFERS MUST BE SIZED AT 1-1/2 TIMES THE
 CROSS-SECTIONAL AREAS OF THE DUCTS SUPPLYING AIR TO THE
 ROOMS. ACCORDING TO THE ORIGINAL AIR DISTRIBUTION
 SCHEDULE ON PLAN SHEET M3.00, 12" FLEX DUCTS WILL BE
 SUPPLYING AIR TO THE NEW OFFICES. PLEASE INCREASE THE
 SIZES OF THE TRANSFER DUCTS TO MEET COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By shill Date 2018-08-29 Time 18:28 Rev Time 0.00
Received By shill Date 2018-08-29 Time 18:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 16:07 Rev Time 0.00
Received By shill Date 2018-06-16 Time 16:06 Sent To  
Notes
2018-06-16 16:07:10SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS
 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE NEXT
 REVIEW CYCLE REQUIRE REVIEW.