Plan Review Details - Permit 18050807
Plan Review Stops For Permit 18050807
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By skennedy Date 2018-11-01 Time 14:16 Rev Time 0.00
Received By skennedy Date 2018-11-01 Time 14:16 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By shill Date 2018-09-12 Time 11:32 Rev Time 0.00
Received By shill Date 2018-09-12 Time 11:32 Sent To  
Notes
2018-09-12 11:48:00FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
 IT APPEARS THAT SEVERAL UNITS HAVE BEEN COMBINED INTO
 ONE UNIT. PLEASE PROVIDE MR. ORIO WITH INFORMATION
 REGARDING SUITE NUMBERS STILL IN USE, AND ONES WHICH
 SHOULD BE "RETIRED".

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-19 Cont ID  
Sent By dbattles Date 2019-02-19 Time 08:41 Rev Time 0.00
Received By dbattles Date 2019-02-19 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By skennedy Date 2018-10-29 Time 12:52 Rev Time 0.00
Received By skennedy Date 2018-10-29 Time 12:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 18:16 Rev Time 0.00
Received By shill Date 2018-08-21 Time 18:16 Sent To  
Notes
2018-08-21 18:17:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO SHOW 18" CLEARANCE PULL SIDE AND 12"
 PUSH SIDE (IF THE DOOR HAS A CLOSER AND A LATCH)
 REQUIRED BY FBC A 404.2.4.1(A) AND (C).
  
 2ND REVIEW, SAME PLAN SUBMITTED. DOORS APPEAR TO HAVE
 AN OBSTRUCTION WHICH BLOCKS THE CLEARANCE.
  
 2. OK
  
 3. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY
 CLASSIFICATION. IF THIS IS A CHANGE OF OCCUPANCY,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 18:16 Rev Time 0.00
Received By shill Date 2018-06-07 Time 18:16 Sent To  
Notes
2018-06-07 18:20:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO SHOW 18" CLEARANCE PULL SIDE AND 12"
 PUSH SIDE (IF THE DOOR HAS A CLOSER AND A LATCH)
 REQUIRED BY FBC A 404.2.4.1(A) AND (C).
  
 2. FBC B 1004, REVISE PLAN TO INCLUDE OCCUPANT LOAD.
  
 3. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY
 CLASSIFICATION. IF THIS IS A CHANGE OF OCCUPANCY,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-01 Cont ID  
Sent By jpearson Date 2018-11-01 Time 15:43 Rev Time 0.00
Received By jpearson Date 2018-11-01 Time 15:43 Sent To M
Notes
2018-10-31 14:18:46VERIFY SECOND SET MATCHES FIRST SET.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 08:05 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 07:59 Sent To I
Notes
2018-10-30 08:05:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, TWO COPIES OF THE
 PLAN ARE REQUIRED. A PREVIOUSLY APPROVED COPY IS
 MISSING. PROVIDE CORRECTION. WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
2018-10-29 13:01:11NEED SECOND SET OF PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By jpearson Date 2018-08-10 Time 15:08 Rev Time 0.00
Received By jpearson Date 2018-08-10 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By jpearson Date 2018-05-23 Time 07:51 Rev Time 0.00
Received By jpearson Date 2018-05-21 Time 13:11 Sent To  
Notes
2018-05-23 07:51:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 2. IT APPEARS THE SERVICE TO THE BUILDING IS 3 PHASE,
 120/208 VOLT. THE RISER DIAGRAM IS SHOWING THE PANEL TO
 THE UNIT AS SINGLE PHASE 120/208. IF IT IS A SINGLE
 PHASE SERVICE, THE LOAD CALCULATION PROVIDED EXCEEDS
 THE VALUE OF THE DISCONNECT, TRANSFER SWITCH, FEEDER
 AND POSSIBLY THE METER. ADDITIONALLY, THE FACTOR FOR
 CONTINUOUS LOAD IS NOT INCLUDED. PROVIDE CORRECTION AND
 ACCURATE LOAD CALCULATION. NEC 220
 3. PROVIDE SPEC SHEET FOR TRANSFER SWTICH. NEC 110.3;
 WPB FBC 107.2.1
 4. IT APPEARS THAT THE GENERATOR WILL BE OVERLOADED. I
 HAVE NOT BEEN ABLE TO FIND A MANUFACTURER THAT MAKES A
 SINGLE PHASE 120/208 GENERATOR. WILL A THREE PHASE
 GENERATOR WILL BE USED AS A SINGLE PHASE SOURCE? A
 THREE PHASE GENERATOR WOULD HAVE AN OUTPUT OF
 APPROXIMATELY 61 AMPS. A SINGLE PHASE GENERATOR HAS A
 VOLTAGE OF 120/240, WHICH WOULD NOT BE COMPATIBLE WITH
 THIS SYSTEM. PROVIDE CLARIFICATION AND GENERATOR SPEC
 SHEETS. NEC 110.3, 110.4; WPB FBC 107.2.1
 5. PROVIDE CLARIFICATION FOR CIRCUITS 9A, 9B, 11A, AND
 11B. WHAT TYPE OF EQUIPMENT IS PLUGGING INTO THESE
 DEDICATED OUTLETS? PANEL SCHEDULE SHOWS A LOAD OF .4KW.
 PROVIDE SPEC SHEETS FOR THIS EQUIPMENT. NEC 110.3; WPB
 FBC 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 10:12 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 10:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-17 Cont ID  
Sent By scaldero Date 2018-10-17 Time 10:09 Rev Time 0.00
Received By scaldero Date 2018-10-17 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By scaldero Date 2018-05-25 Time 10:38 Rev Time 0.00
Received By scaldero Date 2018-05-25 Time 10:34 Sent To  
Notes
2018-05-25 10:38:14PERMIT # 18050807
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By skennedy Date 2018-10-29 Time 13:12 Rev Time 0.00
Received By skennedy Date 2018-10-29 Time 13:12 Sent To  
Notes
2018-10-29 13:13:38UPON APPLICATION FOR GENERATOR, PROVIDE GAS DETAILS.
 GAS FROM THIS PLAN TO BE REMOVED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By gjohnson Date 2018-08-21 Time 09:19 Rev Time 0.00
Received By gjohnson Date 2018-08-21 Time 09:19 Sent To  
Notes
2018-08-21 09:34:472NDREVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS REGULATOR'S VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 2ND REQUEST 2. HOW WILL THE MIRO INDUSTRIES PIPE
 SUPPORT BE ATTACHED TO THE ROOF PLEASE SPECIFY. PER WPB
 AMEND 107.2.1
  
 2ND REQUEST 3. ONE OF THE SIZING TABLES LISTED ON THE
 PLAN 402.4(8) IS FOR NATURAL GAS COPPER TUBING PLEASE
 CLARIFY. PER WPB AMEND 107.2.1 ALSO PROVIDE SIZING FOR
 PIPING DOWN STREAM OF .5LB REGULATOR
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 11:47 Sent To  
Notes
2018-06-07 12:04:541ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 2. HOW WILL THE MIRO INDUSTRIES PIPE SUPPORT BE
 ATTACHED TO THE ROOF PLEASE SPECIFY. PER WPB AMEND
 107.2.1
  
 3. ONE OF THE SIZING TABLES LISTED ON THE PLAN 402.4(8)
 IS FOR NATURAL GAS COPPER TUBING PLEASE CLARIFY. PER
 WPB AMEND 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2019-03-07 Cont ID  
Sent By dbattles Date 2019-03-07 Time 08:29 Rev Time 0.00
Received By dbattles Date 2019-03-05 Time 15:26 Sent To  
Notes
2019-03-06 15:27:08RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-03-04 Cont ID  
Sent By shill Date 2019-03-01 Time 06:26 Rev Time 0.00
Received By shill Date 2019-02-11 Time 11:22 Sent To  
Notes
2019-02-12 11:22:50B32

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-12-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-19 Time 14:04 Sent To  
Notes
2018-12-20 14:05:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-05 Time   Rev Time 0.00
Received By skennedy Date 2018-11-01 Time 13:51 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-10-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-15 Time 14:35 Sent To  
Notes
2018-10-16 14:35:09B18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 18:17 Rev Time 0.00
Received By shill Date 2018-07-26 Time 11:13 Sent To  
Notes
2018-07-27 11:13:16B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 18:21 Rev Time 0.00
Received By shill Date 2018-05-17 Time 14:48 Sent To  
Notes
2018-05-18 14:48:45B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By dbattles Date 2019-03-07 Time 08:28 Rev Time 0.00
Received By dbattles Date 2019-03-07 Time 08:28 Sent To  
Notes
2019-03-07 08:29:26OK - STAMP ON PLANS
 OK- RECEIPT N/A FOR NE FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 18:20 Rev Time 0.00
Received By shill Date 2018-06-07 Time 18:20 Sent To  
Notes
2018-06-07 18:21:26IF THIS IS A CHANGE OF OCCUPANCY, IMPACT FEE ASSESSMENT
 BY PALM BEACH COUNTY MAY BE REQUIRED, 561-233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2019-02-22 Cont ID  
Sent By ccole Date 2019-02-22 Time 10:03 Rev Time 0.00
Received By ccole Date 2019-02-15 Time 09:51 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2018-12-26 Cont ID  
Sent By ccole Date 2018-12-26 Time 12:06 Rev Time 0.00
Received By ccole Date 2018-12-26 Time 12:06 Sent To I
Notes
2018-12-26 12:24:455TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18050807
 12/26/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 REMAINING COMMENTS AND RESULTS FROM 4TH REVIEW LISTED
 BELOW:
  
 1) OK
  
 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM
 REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT
 SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR
 FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER
 IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE
 OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A
 COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES
 LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES,
 DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB.
 (PER THE RESPONSE NARRATIVE, SHOP DRAWINGS AND COST
 BREAKDOWN WERE TO BE PROVIDED ON THE ARCHITECTURAL
 PLANS, BUT WERE NOT PROVIDED)
  
 3) OK
  
 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES
 THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING
 BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS.
 (AIR DEVICE SCHEDULE ON SHEET M0.2 IS MISSING THE EC
 EXHAUST GRILL).
  
 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY
 CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST
 TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT
 WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED
 SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS
 FOR THE EXHAUST SYSTEM SHALL BE APPROVED AND STAMPED BY
 THE EOR, ALONG WITH ANY OTHER SPECILIZED EQUIPMENT TO
 BE INSTALLED IN THE CLEAN ROOMS.
 (NOT ADDRESSED- CABINETS NOT LABELED ON THE PLAN, TYPE
 OF EXHAUST DUCTWORK NOT PROVIDED. IT IS ACKNOWLEDGED
 THAT SPECS WILL BE DEFERRED SUBMITTALS.)
  
 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE
 STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT
 MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE
 A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE
 CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE
 FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST
 SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE
 PROVIDED- TABLE 403.3.1.1
 FBC M.
 (MSDS SHEETS AND LIST OF CHEMICALS SUBMITTED DO NOT
 MATCH THE LIST ON SHEET M0.2)
  
 7) OK
  
 8) OK, GENERATOR TO BE UNDER SEPARATE PERMIT.
  
 9) OK, GENERATOR TO BE UNDER SEPARATE PERMIT.
  
 10) OK, GENERATOR TO BE UNDER SEPARATE PERMIT.
  
 11) NEW COMMENT: PROVIDE AN UPDATED COVER SHEET WITH A
 COMPLETE INDEX TO MATCH THE PLANS, AND REMOVE THE NOTE
 INDICATING MECHANICAL UNDER SEPARATE PERMIT
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-11-05 Cont ID  
Sent By ccole Date 2018-11-05 Time 12:18 Rev Time 0.00
Received By ccole Date 2018-11-05 Time 12:17 Sent To I
Notes
2018-11-05 12:55:404TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18050807
 11/5/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 ON MONDAY, NOVEMBER 5, IN AN EFFORT TO HELP EXPEDITE
 THE APPROVAL OF THE PLANS, I HAD A TELEPHONE
 CONVERSATION WITH THE NEW MECHANICAL ENGINEER OF RECORD
 JOHN D. BUEROSSE. IN THAT CONVERSATION MR. BUEROSSE
 ACKNOWLEDGED THAT HE HAD NOT RECEIVED THE SUBMITTED USP
 GUIDLINES FOR THE CLEAN ROOM FACILITY, OR THE MSDS
 SHEETS FOR THE HAZARDOUS CHEMICALS THAT WILL BE USED IN
 THE MAKING OF THE PHARMACEUTICALS IN THE CLEAN ROOM. HE
 ALSO ACKNOWLEDGED THE CURRENT MECHANICAL DESIGN IS
 DEFICIENT AND WILL HAVE TO BE MODIFIED TO BE COMPLIANT
 WITH THE GUIDELINES AND THE MECHANICAL CODE. AS A
 RESULT, I HAVE EMAILED COPIES OF THE GUIDLEINES, MSDS
 SHEETS, AND OTHER SUBMITTED INFORMATION. PLEASE CONTACT
 MR. BUEROSSE AND SUBMIT TO HIM ALL OTHER SPEC SHEETS
 AND PERTINENT INFRMATION SO THAT HE CAN PROVIDE A
 CODE-COMPLIANT MECHANICAL DESIGN AS SOON AS POSSIBLE.
  
 PRINTED BELOW ARE THE REPEATED COMMENTS THAT STILL MUST
 BE ADDRESSED, AND SOME ADDITIONAL COMMENTS.
  
 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND
 HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE
 DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE,
 AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION
 TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND
 REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM.
  
 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM
 REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT
 SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR
 FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER
 IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE
 OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A
 COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES
 LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES,
 DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB.
  
 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY
 SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH
 REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF-
 PLEASE CORRECT.
  
 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES
 THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING
 BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE
 DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE
 EOR.
  
 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY
 CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST
 TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT
 WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED
 SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS
 FOR THE EXHAUST SYSTEM SHALL BE APPROVED AND STAMPED BY
 THE EOR, ALONG WITH ANY OTHER SPECILIZED EQUIPMENT TO
 BE INSTALLED IN THE CLEAN ROOMS.
  
 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE
 STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT
 MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE
 A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE
 CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE
 FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST
 SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE
 PROVIDED- TABLE 403.3.1.1
  
 FBC M.
  
 7) BASED ON THE NEWLY SUBMITTED USP GUIDELINES FOR THE
 CLEAN ROOM, THE MSDS SHEETS AND EQUIPMENT SPECS, IN
 ORDER TO MAINTAIN THE REQUIRED NEGATIVE PRESSURE IN THE
 SPACE, AN EXHAUST VENTILATION SYSTEM MUST BE INSTALLED.
 PLEASE REFER TO THE GUIDELINES FOR REQUIRED EXHAUST
 RATE AND REQUIRED AIR CHANGES PER HOUR.
  
 8) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH
 GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE
 GENERATOR- SEE SECTION 304.11 FBC M. (THE REVISED SHEET
 A3 NOW SHOWS A "REMOVABLE" GUARD RAIL WHICH MUST BE
 PERMANENTLY INSTALLED. PROVIDE INSTALLATION DETAILS).
  
 9) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND
 ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION
 1609 FBC BC. (THE GENERATOR IS NOW DESIGNATED AS A
 "FUTURE INSTALLATION" ).
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE
 GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC
 M. (THE GENERATOR IS NOW DESGINATED AS A "FUTURE
 INSTALLATION").
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-10-25 Cont ID  
Sent By ccole Date 2018-10-25 Time 17:29 Rev Time 0.00
Received By ccole Date 2018-10-25 Time 17:29 Sent To  
Notes
2018-10-25 18:00:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050807
 10/2518
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PRINTED BELOW ARE THE 2ND REVIEW COMMENTS THAT STILL
 EXIST ON THE PROPOSED MECHANICAL PLAN SUBMITTAL FOR THE
 PROJECT. THESE COMMENTS WERE DISCUSSED IN LENGTH AT A
 MEETING HERE AT THE DEVELOPMENT SERVICES CONFERENCE
 ROOM AT 10:00 AM, MONDAY, SEPTEMBER 17, 2018. PRESENT
 AT THAT MEETING WERE THE PLANS EXAMNIERS, THE
 CONTRACTOR, THE ARCHITECT, REPRESENTATIVES OF THE
 OWNERSHIP OF THE COMPANY. CONCERNING THE MECHANICAL, IT
 WAS STATED THAT THE PLANS AND CALCULATIONS WOULD BE
 CORRECTED AND SUBMITTED ALONG WITH THE REQUESTED SHOP
 DRAWINGS, AND MANUFACTURER'S PRODUCT SPEC SHEETS FOR
 ALL MECHANICAL COMPONENTS AND EQUIPMENT. AS A RESULT,
 THE PLANS THAT HAVE BEEN SUBMITTED ON THIS 3RD REVIEW
 ARE ILLEGIBLE COPIES OF THE PREVIOUS PLANS WHICH NOW
 BEAR A COPIED TITLE BLOCK OF JOHN D. BUEROSE PE. MR.
 BUEROSE'S ORIGINAL SIGNATURE AND SEAL, AS REQUIRED BY
 FLORIDA STATUTE AND FAC, IS NOT ON THE PLANS. PLEASE
 NOTE THAT NO RESPONSE NARRATIVE WAS PROVIDED TO ADDRESS
 THE MECHANICAL COMMENTS WHICH WAS REQUESTED IN AN
 EFFORT TO HELP EXPEDITE THE PLAN APPROVAL PROCESS. UPON
 RECEIPT OF THESE COMMENTS PLEASE HAVE THE NEW ENGINEER
 MR. BUEROSE CONTACT ME SO THAT THE ISSUES CAN BE
 RESOLVED AND COMPLIANT PLANS CAN BE RESUBMITTED.
  
 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND
 HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE
 DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE,
 AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION
 TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND
 REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM.
  
 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM
 REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT
 SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR
 FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER
 IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE
 OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A
 COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES
 LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES,
 DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB.
  
 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY
 SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH
 REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF-
 PLEASE CORRECT.
  
 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES
 THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING
 BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE
 DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE
 EOR.
  
 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY
 CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST
 TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT
 WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED
 SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS
 FOR THE EXHAUST SYSTEM (NOT PROVIDED), SHALL BE
 APPROVED AND STAMPED BY THE EOR, ALONG WITH ANY OTHER
 SPECILIZED EQUIPMENT TO BE INSTALLED IN THE CLEAN
 ROOMS.
  
 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE
 STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT
 MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE
 A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE
 CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE
 FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST
 SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE
 PROVIDED- TABLE 403.3.1.1 FBC M.
  
 7) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH
 GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE
 GENERATOR- SEE SECTION 304.11 FBC M.
  
 8) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND
 ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION
 1609 FBC BC.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE
 GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-07 Cont ID  
Sent By ccole Date 2018-08-07 Time 15:14 Rev Time 0.00
Received By ccole Date 2018-08-07 Time 15:13 Sent To  
Notes
2018-08-07 16:14:442ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050807
 8/7/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND
 HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE
 DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE,
 AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION
 TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND
 REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM.
  
 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM
 REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT
 SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR
 FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER
 IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE
 OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A
 COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES
 LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES,
 DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB.
  
 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY
 SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH
 REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF-
 PLEASE CORRECT.
  
 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES
 THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING
 BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE
 DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE
 EOR.
  
 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY
 CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST
 TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT
 WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED
 SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS
 FOR THE EXHAUST SYSTEM (NOT PROVIDED), SHALL BE
 APPROVED AND STAMPED BY THE EOR, ALONG WITH ANY OTHER
 SPECILIZED EQUIPMENT TO BE INSTALLED IN THE CLEAN
 ROOMS.
  
 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE
 STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT
 MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE
 A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE
 CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE
 FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST
 SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE
 PROVIDED- TABLE 403.3.1.1 FBC M.
  
 7) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH
 GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE
 GENERATOR- SEE SECTION 304.11 FBC M.
  
 8) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND
 ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION
 1609 FBC BC.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE
 GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By ccole Date 2018-05-23 Time 09:23 Rev Time 0.00
Received By ccole Date 2018-05-23 Time 08:59 Sent To  
Notes
2018-05-23 09:28:011ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE INCLUDED IN THE SETS FOR
 REVIEW. INADEQUATE MECHANICAL PLANS FOR THIS FACILITY
 WERE SUBMITTED UNDER PERMIT #17110631 BY SERVICE
 EXPERTS ON 11/17/17. TWO REVIEWS HAVE BEEN COMPLETED,
 THE LAST ONE BEING ON 12/18/17 AND NO CORRECTED PLANS
 HAVE BEEN RESUBMITTED. IN ORDER TO RESOLVE THIS ISSUE,
 IT MAY BE HELPFUL FOR THE ENGINEER DESIGNING THESE
 PLANS TO ALSO DESIGN THE MECHANICAL PLANS FOR THE
 FACILITY. THE OTHER PERMIT CAN THEN BE VOIDED OUT.
  
 2) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH
 GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE
 GENERATOR- SEE SECTION 304.11 FBC MC.
  
 3) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND
 ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION
 1609 FBC BC.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE
 GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC
 MC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By skennedy Date 2018-10-29 Time 13:13 Rev Time 0.00
Received By skennedy Date 2018-10-29 Time 13:13 Sent To  
Notes
2018-10-29 13:14:15NO WORK, OCCUPANT LOAD UNDER 15.

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By gjohnson Date 2018-08-21 Time 08:52 Rev Time 0.00
Received By gjohnson Date 2018-08-21 Time 08:52 Sent To  
Notes
2018-08-21 08:57:132ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
 2ND REQUEST.
  
 1. BY CONNECTING THE TWO BAYS YOU HAVE INCREASED YOUR
 OCCUPANT LOAD IF THERE IS NOT AN EXISTING WATER
 FOUNTAIN OR SERVICE SINK A NEW ONE SHALL BE PROVIDED.
 PER FBC PL TABLE 403.1
 PROVIDE PLAN SHOWING EXISTING.
  
 2. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC FOR
 NEW SINK PLUMBING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 NEW COMMENT:
  
 1. THE APPLICATION IS CALLING OUT UNIT 217 BUT PLANS
 SHOW UNITS 214 + 215 PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 09:33 Sent To  
Notes
2018-06-07 11:45:581ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. BY CONNECTING THE TWO BAYS YOU HAVE INCREASED YOUR
 OCCUPANT LOAD A IF THERE IS NOT AN EXISTING WATER
 FOUNTAIN OR SERVICE SINK A NEW ONE SHALL BE PROVIDED.
 PER FBC PL 810.1
  
 2. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC FOR
 ANY NEW PLUMBING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  