Plan Review Details - Permit 18050787
| Plan Review Stops For Permit 18050787 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-30 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-30 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-19 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-19 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2018-06-19 12:14:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PROFLEX MAXXIM SIM90 ASTM E90 TEST REPORT WAS | | | PROVIDED, BUT IT WAS TESTED WITH AN 8" SLAB AND DROPPED | | | GYPSUM CEILING. SLAB THICKNESS FOR THIS BUILDING IS NOT | | | KNOWN; CONFIRM IT IS 8" IF YOU WISH TO UTILIZE AN 8" | | | TEST REPORT. DROPPED CEILING NOT ACCEPTABLE. | | | | | | PROFLEX RCU500 ASTM E492 TEST REPORT (IIC) SUBMITTED; | | | THIS TEST REPORT IS ACCEPTABLE. | | | | | | FIRST SUBMITTAL PROVIDED SPEC SHEETS FOR PROFLEX MSC. | | | | | | SINCE TWO DIFFERENT TEST REPORTS AND A DIFFERENT SPEC | | | SHEET WERE PROVIDED (THREE DIFFERENT PRODUCTS), IT IS | | | NOT CLEAR WHAT PRODUCT IS PROPOSED. STC, IIC, FLAME | | | SPREAD ARE REQUIRED. SELECT THE ONE PRODUCT YOU WISH TO | | | PROPOSE AND PROVIDE THE THREE TEST REPORTS AS NOTED IN | | | COMMENT #2. | | | | | | 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING | | | TEST REPORTS: | | | | | | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-07 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-07 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2018-06-07 18:06:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING | | | TEST REPORTS: | | | | | | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-07-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-18 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-18 |
Time |
15:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-18 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-18 |
Time |
16:37 |
Sent To |
B |
|
| Notes |
| 2018-06-18 16:37:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY. PREVIOUS | | | COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY HAVE | | | BEEN NOTED AS CORRECTED. ITEMS REMAINING HAVE FURTHER | | | COMMENTS IN PARENTHESES. | | | | | | 1. CORRECTED. | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). NEC 215.5, 230, 408.30 (COMMENT RESPONSE | | | STATES THAT THIS IS AN EXISTING SERVICE. I UNDERSTAND | | | THAT, BUT STILL REQUIRE A RISER DIAGRAM WHICH WILL SHOW | | | WHAT THE SIZE OF THE EXISTING SERVICE. THERE IS NOTHING | | | IN THE PLAN TO INDICATE THE CURRENT SERVICE SIZE. | | | PROVIDE AS PREVIOUSLY CORRECTED.) | | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30 (THE LOAD | | | CALCULATION FOR THE UNIT WAS SUPPLIED, BUT I STILL NEED | | | THE LOAD CALCULATION FOR THE RISER/SERVICE THAT | | | SUPPLIES THIS UNIT. AS MANY LARGE BUILDINGS HAVE A | | | SERVICE SIZED FOR TANK TYPE WATER HEATERS, INSTALLING | | | TANKLESS UNITS WITH HIGH DEMAND CAN OVERLOAD THE | | | SYSTEM. THIS LOAD CALCULATION IS REQUIRED. PROVIDE AS | | | REQUESTED.) | | | 4. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS | | | PER NEC 210.12(B). (COMMENT REAPOSE STATES THAT AFCI | | | PROTECTION IS NOTED ON DRAWING, BUT THIS HAS NOT BEEN | | | INCLUDED AS REQUESTED. PROVIDE CORRECTION.) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-22 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-22 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2018-05-22 09:02:48 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER SHOWING | | | ELECTRICAL REQUIREMENTS. NEC 110.3; WPB FBC 107.2.1 | | | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). NEC 215.5, 230, 408.30 | | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30 | | | 4. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS | | | PER NEC 210.12(B). | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-21 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2018-05-21 14:16:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-30 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-13 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2018-07-16 13:38:12 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-19 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-12 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2018-06-13 13:56:18 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-07 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-16 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-22 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-22 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-06-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-06 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-06 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
|