Plan Review Stops For Permit 18050787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 11:06 Rev Time 0.00
Received By shill Date 2018-07-30 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-19 Cont ID  
Sent By shill Date 2018-06-19 Time 12:08 Rev Time 0.00
Received By shill Date 2018-06-19 Time 12:08 Sent To  
Notes
2018-06-19 12:14:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROFLEX MAXXIM SIM90 ASTM E90 TEST REPORT WAS
 PROVIDED, BUT IT WAS TESTED WITH AN 8" SLAB AND DROPPED
 GYPSUM CEILING. SLAB THICKNESS FOR THIS BUILDING IS NOT
 KNOWN; CONFIRM IT IS 8" IF YOU WISH TO UTILIZE AN 8"
 TEST REPORT. DROPPED CEILING NOT ACCEPTABLE.
  
 PROFLEX RCU500 ASTM E492 TEST REPORT (IIC) SUBMITTED;
 THIS TEST REPORT IS ACCEPTABLE.
  
 FIRST SUBMITTAL PROVIDED SPEC SHEETS FOR PROFLEX MSC.
  
 SINCE TWO DIFFERENT TEST REPORTS AND A DIFFERENT SPEC
 SHEET WERE PROVIDED (THREE DIFFERENT PRODUCTS), IT IS
 NOT CLEAR WHAT PRODUCT IS PROPOSED. STC, IIC, FLAME
 SPREAD ARE REQUIRED. SELECT THE ONE PRODUCT YOU WISH TO
 PROPOSE AND PROVIDE THE THREE TEST REPORTS AS NOTED IN
 COMMENT #2.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 18:03 Rev Time 0.00
Received By shill Date 2018-06-07 Time 18:03 Sent To  
Notes
2018-06-07 18:06:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-18 Cont ID  
Sent By jpearson Date 2018-07-18 Time 15:57 Rev Time 0.00
Received By jpearson Date 2018-07-18 Time 15:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-18 Cont ID  
Sent By jpearson Date 2018-06-18 Time 16:37 Rev Time 0.00
Received By jpearson Date 2018-06-18 Time 16:37 Sent To B
Notes
2018-06-18 16:37:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY. PREVIOUS
 COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY HAVE
 BEEN NOTED AS CORRECTED. ITEMS REMAINING HAVE FURTHER
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). NEC 215.5, 230, 408.30 (COMMENT RESPONSE
 STATES THAT THIS IS AN EXISTING SERVICE. I UNDERSTAND
 THAT, BUT STILL REQUIRE A RISER DIAGRAM WHICH WILL SHOW
 WHAT THE SIZE OF THE EXISTING SERVICE. THERE IS NOTHING
 IN THE PLAN TO INDICATE THE CURRENT SERVICE SIZE.
 PROVIDE AS PREVIOUSLY CORRECTED.)
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (THE LOAD
 CALCULATION FOR THE UNIT WAS SUPPLIED, BUT I STILL NEED
 THE LOAD CALCULATION FOR THE RISER/SERVICE THAT
 SUPPLIES THIS UNIT. AS MANY LARGE BUILDINGS HAVE A
 SERVICE SIZED FOR TANK TYPE WATER HEATERS, INSTALLING
 TANKLESS UNITS WITH HIGH DEMAND CAN OVERLOAD THE
 SYSTEM. THIS LOAD CALCULATION IS REQUIRED. PROVIDE AS
 REQUESTED.)
 4. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS
 PER NEC 210.12(B). (COMMENT REAPOSE STATES THAT AFCI
 PROTECTION IS NOTED ON DRAWING, BUT THIS HAS NOT BEEN
 INCLUDED AS REQUESTED. PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By jpearson Date 2018-05-22 Time 09:02 Rev Time 0.00
Received By jpearson Date 2018-05-22 Time 07:15 Sent To  
Notes
2018-05-22 09:02:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER SHOWING
 ELECTRICAL REQUIREMENTS. NEC 110.3; WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). NEC 215.5, 230, 408.30
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS
 PER NEC 210.12(B).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By pleduc Date 2018-05-21 Time   Rev Time 0.00
Received By pleduc Date 2018-05-21 Time 12:30 Sent To  
Notes
2018-05-21 14:16:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
  
 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 11:25 Rev Time 0.00
Received By shill Date 2018-07-13 Time 13:37 Sent To  
Notes
2018-07-16 13:38:12RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By shill Date 2018-06-19 Time 12:14 Rev Time 0.00
Received By shill Date 2018-06-12 Time 13:56 Sent To  
Notes
2018-06-13 13:56:18RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 18:06 Rev Time 0.00
Received By shill Date 2018-05-16 Time 14:20 Sent To  
Notes
2018-05-17 15:40:09B14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-22 Cont ID  
Sent By ccole Date 2018-05-22 Time 14:47 Rev Time 0.00
Received By ccole Date 2018-05-22 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 14:52 Sent To  
Notes
***NONE***