Plan Review Details - Permit 18050779
Plan Review Stops For Permit 18050779
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By jleahy Date 2018-06-07 Time 16:48 Rev Time 0.00
Received By jleahy Date 2018-06-07 Time 16:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-25 Cont ID  
Sent By rmcdouga Date 2018-05-25 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2018-05-25 Time 07:24 Sent To P
Notes
2018-05-25 08:10:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 GENERATOR PAD AND ANCHORING
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC 107.2.1.2 PROVIDE INSTALLATION GUIDE FOR THE
 GENERATOR. SEE NOTE NUMBER 1 ON SHEET 6 OF 11 GENERAC
 INSTALLATION LAYOUT. THE MINIMUM RECOMMENDED CONCRETE
 PAD SIZE IS 43" X 74.2".
  
 3) FBC 107.2.1 SPECIFY THE REQUIRED EMBED DEPTH OF THE
 3/8" DIAMETER CONCRETE ANCHORS.
  
 4) FBC 301.2.1 SPECIFY THE WIND SPEED DATA ON THE
 GENERATOR PAD PLANS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-24 Cont ID  
Sent By fgiaquin Date 2018-05-24 Time 07:11 Rev Time 0.00
Received By fgiaquin Date 2018-05-24 Time 07:11 Sent To B
Notes
2018-05-24 07:11:25FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 13:43 Rev Time 0.00
Received By tklarge Date 2018-05-30 Time 13:38 Sent To I
Notes
2018-05-30 13:44:07A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-30 Cont ID  
Sent By tklarge Date 2018-05-30 Time 13:45 Rev Time 0.00
Received By tklarge Date 2018-05-16 Time 13:13 Sent To  
Notes
2018-05-17 13:13:27ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By mcruz Date 2018-05-22 Time   Rev Time  
Received By   Date 2018-05-22 Time   Sent To PC
Notes
***NONE***