Plan Review Details - Permit 18050779
| Plan Review Stops For Permit 18050779 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-06-07 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-06-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-25 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-25 |
Time |
07:24 |
Sent To |
P |
|
| Notes |
| 2018-05-25 08:10:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) FBC 107.2.1.2 PROVIDE INSTALLATION GUIDE FOR THE | | | GENERATOR. SEE NOTE NUMBER 1 ON SHEET 6 OF 11 GENERAC | | | INSTALLATION LAYOUT. THE MINIMUM RECOMMENDED CONCRETE | | | PAD SIZE IS 43" X 74.2". | | | | | | 3) FBC 107.2.1 SPECIFY THE REQUIRED EMBED DEPTH OF THE | | | 3/8" DIAMETER CONCRETE ANCHORS. | | | | | | 4) FBC 301.2.1 SPECIFY THE WIND SPEED DATA ON THE | | | GENERATOR PAD PLANS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-05-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-05-24 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-05-24 |
Time |
07:11 |
Sent To |
B |
|
| Notes |
| 2018-05-24 07:11:25 | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-05-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-30 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-30 |
Time |
13:38 |
Sent To |
I |
|
| Notes |
| 2018-05-30 13:44:07 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A | | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-30 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-16 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2018-05-17 13:13:27 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-05-22 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2018-05-22 |
Time |
|
Sent To |
PC |
|
| Notes |
|
|
|